Pepperl+Fuchs 260435

HICTB08-SDC-44C-SC-RA

Termination Board

Bajo pedido. Envíenos un correo electrónico para consultar el precio y la disponibilidad.
"ucnguBrctvdgcxgt0eqo"

Descripción

For 8 modules, 24 V DC supply, Supported signal types: DI/DO/AI/TI/AO, Hazardous area: screw terminals, blue, Safe area: Sub-D connector (male), 37-pinpa

Parámetros técnicos

Connection: X20: terminals 3, 5 (+); 4, 6 (-)
Nominal voltage: 24 V DC , in consideration of rated voltage of used isolators
Voltage drop: 0.9 V , voltage drop across the series diode on the termination board must be considered
Ripple: ≤ 10 %
Fusing: 2 A , in each case for 8 modules
Power dissipation: ≤ 500 mW , without modules
Reverse polarity protection: yes
Supply: Redundancy available. The supply for the isolators is decoupled, monitored and fused.
Connection: X20: terminals 1, 2
Output type: volt-free contact
Contact loading: 30 V DC, 1 A
Display elements: LED PWR1 (Termination Board power supply), green LED LED PWR2 (Termination Board power supply), green LED LED FAULT (fault indication), red LED - LED lits: module failure - LED flashes: power supply failure
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Electromagnetic compatibility: NE 21:2012 For further information see system description.
Degree of protection: IEC 60529:2001
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Storage temperature: -40 ... 70 °C (-40 ... 158 °F)
Degree of protection: IP20
Connection: Field side: explosion hazardous area: 4 screw terminals per module , blue
Connection: Control side: non-explosion hazardous area: 1 37-pin Sub-D connector
Connection: Supply: pluggable screw terminals , black
Core cross-section: screw terminals: 0.25 ... 1.5 mm2 (24 ... 12 AWG)
Material: housing: polycarbonate, 10 % glass fiber reinforced
Mass: approx. 400 g
Dimensions: 108 x 200 x 163 mm (4.25 x 7.9 x 6.42 inch) , height including module assembly
Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001
EU-Type Examination Certificate: CESI 06 ATEX 022
Connection: Marking: II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
Safe area: Maximum safe voltage: 250 V (Attention! Um is no rated voltage.)
Galvanic isolation: Field circuit/control circuit: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 50303:2000
UL approval: Control drawing: 116-0327
IECEx approval: IECEx CES 06.0003
UL approval: Approved for: [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I

Parámetros logísticos

ECCN:
País de origen: Singapur
EAN: 4050143064984
Peso: 0,46 kg
Longitud: 0,00 m
Anchura: 0,00 m
Altura: 0,00 m