Pepperl+Fuchs 254610

LB1003C

Frequency / Counter Input

Bajo pedido. Envíenos un correo electrónico para consultar el precio y la disponibilidad.
"ucnguBrctvdgcxgt0eqo"

Descripción

1-channel, Input for frequency, counter, direction of rotation, Installation in Zone 2 or safe area, Digital input max. 400 Hzpa

Parámetros técnicos

Occupied slots: 1
Connection: backplane bus
Rated voltage: 12 V DC , only in connection with the power supplies LB9***
Power dissipation: 0.65 W
Power consumption: 0.65 W
Connection: backplane bus
Interface: manufacturer-specific bus to standard com unit
Number of channels: 1
Function: Function: Counter
Function: Function [2]: frequency
Function: Function [3]: direction of rotation
Sensor interface: Connection: NAMUR sensor
Sensor interface: Connection [2]: volt-free contact
Connection: channel I: 1+, 2-; direction: 4+, 5-
Rated values: acc. to EN 60947-5-6 (NAMUR)
Switching point/switching hysteresis: 1.2 ... 2.1 mA / ± 0.2 mA
Voltage: 8.2 V
Internal resistor: 1 kΩ
Line fault detection: can be switched on/off for each channel via configuration tool
Sensor interface: Connection: mechanical switch with additional resistors (see connection diagram) proximity switches without additional wiring
Sensor interface: Short-circuit: < 360 Ω
Sensor interface: Open-circuit: < 0.35 mA
Minimum pulse duration: ; in frequency + counter mode: 12.5 ms ; otherwise 20 µs
Operating frequency: 0 ... 400 Hz ; in frequency + counter mode ... 40 Hz
LED indication: Power LED (P) green: supply Status LED (1) red: line fault
Coding: optional mechanical coding via front socket
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1
Electromagnetic compatibility: NE 21
Degree of protection: IEC 60529
Environmental test: EN 60068-2-14
Shock resistance: EN 60068-2-27
Vibration resistance: EN 60068-2-6
Damaging gas: EN 60068-2-42
Relative humidity: EN 60068-2-56
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Relative humidity: 95 % non-condensing
Shock resistance: shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistance: frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gas: designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Degree of protection: IP20 when mounted on backplane
Connection: removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Mass: approx. 90 g
Dimensions: 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch)
Certificate: PF 08 CERT 1234 X
Electromagnetic compatibility: Marking: II 3 G Ex nA [ic] IIC T4 Gc
Galvanic isolation: Input/power supply, internal bus: safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010
ATEX approval: PTB 03 ATEX 2042 X
IECEx approval: BVS 09.0037X
Directive conformity: Approved for: Ex nA [ic] IIC T4 Gc
Marine approval: Lloyd Register: 15/20021
Marine approval: DNV GL Marine: TAA0000034
Marine approval: Bureau Veritas Marine: 22449/B0 BV
System information: The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2 or Zone 22) the module must be installed in an appropriate enclosure.
Supplementary information: EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Parámetros logísticos

ECCN:
País de origen: Deutschland
EAN: 4050143074662
Peso: 0,00 kg
Longitud: 0,00 m
Anchura: 0,00 m
Altura: 0,00 m