Pepperl+Fuchs 238626

VAN-115/230AC-K27

AS-Interface power supply

Bajo pedido. Envíenos un correo electrónico para consultar el precio y la disponibilidad.
"ucnguBrctvdgcxgt0eqo"

Descripción

AS-Interface power supply, data decoupling, 4 Afa

Parámetros técnicos

UL File Number: E223176
MTBF: 100 a
Reset push-button switch: earth fault simulation/reset of earth fault display
LED EFD: earth fault display; LED red
LED AS-i ok: LED green: ON: AS-Interface voltage OK OFF: overload or no supply voltage
Fusing: T3A 15/250 V HBC (not accessible)
Rated operating voltage: 85 … 132 VAC 184 … 264 VAC 240 … 300 VDC
Rated operating current: 2.7 A at 115 VAC 1.3 A at 230 VAC
Supply frequency: 47 ... 63 Hz (alternatively, DC possible)
Efficiency: typ. 90 % (230 VAC, 4 A)
Galvanic isolation: SELV/PELV
Peak inrush current: < 3.7 A2s (120 VAC) < 4.6 A2s (132 VAC) < 2.5 A2s (230 VAC) < 3.3 A2s (264 VAC)
Short-circuit protection/overload: > 4,2 A < 6.5 A
Current limit: starts at > 4.2 A
Voltage: 30.5 VDC ±3 % fixed
Current: 4 A
Residual ripple: < 50 mVSS (500 kHz bandwidth, 50 Ω measurement, with resistive load)
Overvoltage protected: limited to max. 55 V
Directive conformity: EMC Directive 2004/108/EC: EN 55022:2006, EN 55011:2009 Class B EN 61000-6-3:2001 , EN 61204-3:2001
Standard conformity: Noise immunity: EN 61000-6-2:2005
Standard conformity: Emitted interference: EN 61000-6-3:2007 EN 61000-3-2:2010 EN 61000-3-3:2009
Standard conformity: Galvanic isolation: IEC 60364-4-41:2005 (PELV) IEC 60950:1999 (SELV)
Standard conformity: Degree of protection: IEC 60529:2001
Standard conformity: Pollution degree: EN 50178:1997
Standard conformity: Mech. capacity: EN 60068-2-6:2008 (Sinus) EN 60068-2-64:2009 (Random)
Standard conformity: Shock and impact resistance: EN 60068-2-27:1995
Ambient temperature: -10 ... 70 °C (14 ... 158 °F) Note derating
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Shock and impact resistance: 15g/6 ms 10g/11 ms
Vibration resistance: Sine 2 - 17.8 Hz: ± 1.6 mm Sine 17.8 ... 500 Hz : 2 g Random 2 … 500 Hz: 0.5 m2 (s³)
Pollution degree: 2
Degree of protection: IP20
Protection class: 1 (IEC 60536); Protective conductor connection necessary
Connection: Connection terminals, max. conductor cross-section Flexible cable: 0.5 … 4 mm2 Rigid cable: 0.5 … 6 mm2 Stripping length 7 mm
Mass: 650 g
Mounting: DIN mounting rail

Parámetros logísticos

ECCN:
País de origen: DE
EAN:
Peso: 0,00 kg
Longitud: 0,00 m
Anchura: 0,00 m
Altura: 0,00 m