Pepperl+Fuchs 228630

VBA-4E3A-KE-ZEJQ/E2L

AS-Interface sensor/actuator module

Bajo pedido. Envíenos un correo electrónico para consultar el precio y la disponibilidad.
"ucnguBrctvdgcxgt0eqo"

Descripción

KE switch cabinet module. 4 inputs and 3 outputsfa

Parámetros técnicos

Slave type: A/B slave
AS-Interface specification: V3.0
Required master specification: ≥ V2.1
UL File Number: E223772
LED FAULT: Error display; red LED red: communication error, i.e. address is 0 red flashing: overload internal input supply, i.e. overload or lead interruption outputs
LED INT: Internal input supply active; LED green
LED PWR: AS-Interface voltage; green LED green: voltage OK flashing green: address 0
LED AUX: ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage
LED IN: switching state (input); 4 LED yellow
LED OUT: Switching state (output); 3 LED yellow/red yellow: Output active red: Output overload or lead breakage
Auxiliary voltage (input): 12 ... 30 V DC PELV
Auxiliary voltage (output): 20 ... 30 V DC PELV
Rated operating voltage: 26.5 ... 31.6 V from AS-Interface
Rated operating current: ≤ 35 mA (without sensors) / max. 190 mA
Protection class: III
Surge protection: UEXT, UAUX, Ue: Over voltage category III, safe isolated power supplies (PELV)
Number/Type: 4 inputs for 2- or 3-wire sensors (PNP), DC
Supply: from AS-Interface (switch position INT, default settings) or external UEXT (switch position EXT)
Voltage: 21 ... 31 V DC (INT)
Current loading capacity: ≤ 150 mA, overload- and short-circuit protected (INT)
Input current: ≤ 9 mA (limited internally)
Switching point: according to DIN EN 61131-2 (Type 2)
: 0 (unattenuated): ≤ 3 mA
: 1 (attenuated): ≥ 5 mA
Signal delay: < 1 ms (input/AS-Interface)
Number/Type: 3 electronic outputs, PNP, overload and short-circuit proof
Supply: from external auxiliary voltage UAUX
Current: O1 max. 3 A, O2/O3 max. 1.5 A, total 6 A (TB ≤ 40 °C) O1 max. 2 A, O2/O3 max. 1 A, total 4 A (TB ≤ 60 °C)
Voltage: ≥ (UAUX - 0.5 V)
Usage category: DC-13
Electromagnetic compatibility: Directive 2014/30/EU: EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007
Degree of protection: EN 60529:2000
Fieldbus standard: EN 62026-2:2013
Input: EN 61131-2:2004
Emitted interference: EN 61000-6-4:2007
AS-Interface: EN 62026-2:2013
Noise immunity: EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013
Profile: S-7.A.0
IO code: 7
ID code: A
ID1 code: 7
ID2 code: 0
Data bits (function via AS-Interface): input output
Electromagnetic compatibility: D0: IN1 O1
Electromagnetic compatibility: D1: IN2 O2
Electromagnetic compatibility: D2: IN3 O3
Electromagnetic compatibility: D3: IN4 -
Parameter bits (programmable via AS-i): function
Electromagnetic compatibility: P0: Communication monitoring P0 = 0 monitoring = off, the outputs maintain the status if communication fails P0 = 1 monitoring = on, i.e. if communication fails, the outputs are deenergised (default settings)
Electromagnetic compatibility: P1: Input filter P1 = 0 input filter on, pulse suppression ≤ 2 ms P1 = 1 input filter off (default settings)
Electromagnetic compatibility: P2: Lead breakage outputs P2 = 0 lead breakage on P2 = 1 lead breakage off (default settings)
Electromagnetic compatibility: P3: not used
Ambient temperature: -25 ... 60 °C (-13 ... 140 °F)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Relative humidity: 85 % , noncondensing
Climatic conditions: For indoor use only
Altitude: ≤ 2000 m above MSL
Pollution degree: 2
Degree of protection: IP20
Connection: removable terminals rated connection capacity: rigid/flexible (with and without wire-end ferrules): 0.25 mm2 ... 2.5 mm2 for multiple-wire connection with two wires of equal cross-section: flexible with twin wire-end ferrules: 0.5 mm2 ... 1.5 mm2
Material: Housing: PA 66-FR
Mass: 150 g
Mounting: DIN mounting rail
Tightening torque of clamping screws: 0.5 Nm ... 0.6 Nm

Parámetros logísticos

ECCN:
País de origen: ID
EAN:
Peso: 0,00 kg
Longitud: 0,00 m
Anchura: 0,00 m
Altura: 0,00 m