Pepperl+Fuchs 223079

FB1209B3

Digital Input

Bajo pedido. Envíenos un correo electrónico para consultar el precio y la disponibilidad.
"ucnguBrctvdgcxgt0eqo"

Descripción

8-channel, Inputs Ex ia, Installation in suitable enclosures in Zone 1, Module can be exchanged under voltage (hot swap)pa

Parámetros técnicos

Occupied slots: 1
Connection: backplane bus
Rated voltage: 12 V DC , only in connection with the power supplies FB92**
Power dissipation: 1.55 W
Power consumption: 1.55 W
Connection: backplane bus
Interface: manufacturer-specific bus to standard com unit
Number of channels: 8
Sensor interface: Connection: NAMUR sensor
Sensor interface: Connection [2]: volt-free contact
Connection: Terminals 1+, 2-, 3+, 4-, 5+, 6-, 7+, 8-, 9+, 10-, 11+, 12-, 13+,14-, 15+, 16-
Rated values: acc. to EN 60947-5-6 (NAMUR)
Switching point/switching hysteresis: 1.2 ... 2.1 mA / ± 0.2 mA
Internal resistor: 1 kΩ
Line fault detection: can be switched on/off for each channel via configuration tool
Sensor interface: Connection: mechanical switch with additional resistors (see connection diagram) proximity switches without additional wiring
Sensor interface: Short-circuit: < 360 Ω
Sensor interface: Open-circuit: < 0.35 mA
Minimum pulse duration: 15 ms
LED indication: LED green: supply LED red: line fault, per channel
Coding: optional mechanical coding via front socket
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1
Electromagnetic compatibility: NE 21
Degree of protection: IEC 60529
Environmental test: EN 60068-2-14
Shock resistance: EN 60068-2-27
Vibration resistance: EN 60068-2-6
Damaging gas: EN 60068-2-42
Relative humidity: EN 60068-2-56
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Relative humidity: 95 % non-condensing
Shock resistance: shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistance: frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gas: designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Degree of protection: IP20 (module) , a separate housing is required acc. to the system description
Connection: removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Mass: approx. 420 g
Dimensions: 28 x 107 x 132 mm (1.1 x 4.2 x 5.2 inch)
EU-Type Examination Certificate: Presafe 19 ATEX 14055U
Electromagnetic compatibility: Marking: II 2(1)G Ex db eb q [ia Ga] IIC Gb II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
Input: Voltage: 10 V
Input: Current: 13 mA
Input: Power: 33 mW (linear characteristic)
Galvanic isolation: Input/power supply, internal bus: safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 EN 60079-1:2014 EN 60079-5:2015 EN 60079-7:2015 EN 60079-11:2012
ATEX approval: Presafe 19 ATEX 14055U
IECEx approval: IECEx PRE 19.0010U
Directive conformity: Approved for: Ex db eb q [ia Ga] IIC Gb [Ex ia Da] IIIC [Ex ia Ma] I
System information: The module has to be mounted in appropriate backplanes and housings (FB92**) in Zone 1, 2, 21, 22 or outside hazardous areas (gas or dust). Here, observe the corresponding EC-type examination certificate.
Supplementary information: EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.