Pepperl+Fuchs 214242

KCD2-SON-Ex1

Amplificador

Bajo pedido. Envíenos un correo electrónico para consultar el precio y la disponibilidad.
"ucnguBrctvdgcxgt0eqo"

Descripción

Barrera aislada de 1 canal, Alimentación de 24 V CC (carril de alimentación), Contacto seco o entrada NAMUR, 2 salidas de transistor pasivas (resistivas conforme a EN 60947-5-6), Transparencia de fallo de línea (LFT), Ancho de la carcasa: 12,5 mm, Hasta SIL 2 según IEC 61508pa

Parámetros técnicos

Signal type: Digital Input
Safety Integrity Level (SIL): SIL 2
Connection: Power Rail or terminals 9+, 10-
Rated voltage: 19 ... 30 V DC
Ripple: ≤ 10 %
Rated current: 18 ... 14 mA
Power dissipation: ≤ 500 mW
Connection side: field side
Connection: terminals 1+, 2-
Rated values: acc. to EN 60947-5-6 (NAMUR)
Open circuit voltage/short-circuit current: approx. 10 V DC / approx. 8 mA
Switching point/switching hysteresis: 1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detection: breakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA
Pulse/Pause ratio: min. 100 µs / min. 100 µs
Connection side: control side
Connection: output I: terminals 5, 6 ; output II: terminals 7, 8
Rated voltage: typ. 8 V max. 20 V DC
Response time: ≤ 200 µs
Output I, II: signal or error message, passive transistor output (resistive) 0-signal: 14 kΩ ± 10 % 1-signal: 1.8 kΩ ± 10 % fault: > 100 kΩ
Collective error message: Power Rail
Switching frequency: ≤ 5 kHz
Input/Output: reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
Input/power supply: reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
Output/power supply: basic insulation according to EN 50178, rated insulation voltage 50 Veff
Output/Output: basic insulation according to EN 50178, rated insulation voltage 50 Veff
Display elements: LEDs
Control elements: DIP-switch
Configuration: via DIP switches
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Electromagnetic compatibility: NE 21:2011 , EN 61326-3-2:2008
Degree of protection: IEC 60529:2001
Protection against electrical shock: IEC 61010-1:2010
Input: EN 60947-5-6:2000
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Degree of protection: IP20
Connection: screw terminals
Mass: approx. 100 g
Dimensions: 12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 inch) , housing type A2
Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001
EU-type examination certificate: BASEEFA 13 ATEX 0080
Electromagnetic compatibility: Marking: II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
Electromagnetic compatibility: Input: Ex ia
Electromagnetic compatibility: Voltage: 10.5 V
Electromagnetic compatibility: Current: 17.1 mA
Electromagnetic compatibility: Power: 45 mW (linear characteristic)
Supply: Maximum safe voltage: 253 V AC (Attention! Um is no rated voltage.)
Output: Maximum safe voltage: 253 V AC (Attention! The rated voltage can be lower.)
Certificate: CML 19 ATEX 4410 X
Output: Marking: II 3G Ex ec IIC T4 Gc
Galvanic isolation: Input/Output: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Galvanic isolation: Input/power supply: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN IEC 60079-0:2018 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012
UL approval: Control drawing: 116-0374 (cULus)
IECEx approval: IECEx BAS 13.0046 IECEx CML 19.0147X
UL approval: Approved for: [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Ex ec IIC T4 Gc
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Optional accessories: - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-BU(-UPR-03)

Parámetros logísticos

ECCN:
País de origen: SG
EAN:
Peso: 0,00 kg
Longitud: 0,00 m
Anchura: 0,00 m
Altura: 0,00 m