Pepperl+Fuchs 200524

VBA-4E4E-G12-ZAJ

AS-Interface sensor module

Bajo pedido. Envíenos un correo electrónico para consultar el precio y la disponibilidad.
"ucnguBrctvdgcxgt0eqo"

Descripción

G12 flat module. 2 x 4 inputs (PNP)fa

Parámetros técnicos

Slave type: Double A/B slave
AS-Interface specification: V3.0
Required master specification: ≥ V2.1
UL File Number: E223772
MTTFd: 60 a
Mission Time (TM): 20 a
Diagnostic Coverage (DC): 0 %
LED PWR/FAULT: 2 Dual LEDs green/red green: AS-Interface voltage red: Communication error yellow/red flashing: Address 0 green/red flashing: Sensor supply overload
LED IN: switching state (input); 8 LED yellow
Rated operating voltage: 26.5 ... 31.6 V from AS-Interface
Rated operating current: ≤ 80 mA (without sensors) / max. 280 mA
Protection class: III
Surge protection: Ue: Over voltage category III, safe isolated power supplies (PELV) derived from mains up to 300 V AC line-to-neutral
Number/Type: 2x 4 inputs for 2- or 3-wire sensors (PNP), DC alternative 2x 2 inputs for 4-wire sensors (PNP), DC
Supply: from AS-Interface
Voltage: 21 ... 31 V
Current loading capacity: ≤ 200 mA, overload and short-circuit protected
Input current: ≤ 8 mA (limited internally)
Switching point: according to DIN EN 61131-2 (Type 2)
: 0 (unattenuated): ≤ 2 mA
: 1 (attenuated): ≥ 6 mA
Signal delay: < 1 ms (input/AS-Interface)
Electromagnetic compatibility: Directive 2014/30/EU: EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007
Degree of protection: EN 60529:2000
Fieldbus standard: EN 62026-2:2013
Input: EN 61131-2
Emitted interference: EN 61000-6-4:2007
AS-Interface: EN 62026-2:2013
Noise immunity: EN 61000-6-2:2005 EN 62026-2:2013
Profile: S-0.A.2
IO code: 0
ID code: A
ID1 code: Slave 1 Slave 2 1 2
ID2 code: 2
Data bits (function via AS-Interface): Input slave 1 input slave 2
Electromagnetic compatibility: D0: IN1.1 IN2.1
Electromagnetic compatibility: D1: IN1.2 IN2.2
Electromagnetic compatibility: D2: IN1.3 IN2.3
Electromagnetic compatibility: D3: IN1.4 IN2.4
Parameter bits (programmable via AS-i): function
Electromagnetic compatibility: P0: not used
Electromagnetic compatibility: P1: Input filter P1 = 0 input filter on, pulse suppression ≤ 2 ms P1 = 1 input filter off (default settings)
Electromagnetic compatibility: P2: Synchronous mode P2 = 0 synchronous mode on P2 = 1 synchronous mode off (default settings)
Electromagnetic compatibility: P3: not used
Ambient temperature: -25 ... 70 °C (-13 ... 158 °F)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Relative humidity: 85 % , noncondensing
Climatic conditions: For indoor use only
Altitude: ≤ 2000 m above MSL
Shock and impact resistance: 30 g, 11 ms in 6 spatial directions 3 shocks 10 g, 16 ms in 6 spatial directions 1000 shocks
Vibration resistance: 0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles
Pollution degree: 3
Degree of protection: IP67
Connection: cable piercing method flat cable yellow inputs: M12 round connector
Material: Housing: PBT
Mass: 230 g
Tightening torque, cable gland: 0.4 Nm
Mounting: Mounting plate

Parámetros logísticos

ECCN:
País de origen: ID
EAN:
Peso: 0,00 kg
Longitud: 0,00 m
Anchura: 0,00 m
Altura: 0,00 m