Pepperl+Fuchs 193671

VAA-2E2A-G12-SAJ/EA2L

AS-Interface Sicherheitsmodul VAA-2E2A-G12-SAJ/EA2L

Bajo pedido. Envíenos un correo electrónico para consultar el precio y la disponibilidad.
"ucnguBrctvdgcxgt0eqo"

Descripción

The VAA-2E2A-G12-SAJ/EA2L is an AS-Interface safety module with 2 safety-related inputs and 2 conventional outputs. A two-channel mechanical switch on both of the safety - related inputs or a one-channel mechanical switch on each one can be connected. The outputs are conventional electronic outputs which can be energized with a total of 4 A (max. 2A per output). The solid housing permits fast mounting without tools as well as easy removal without tools. The stainless steel shell and the cast housing ensure durability and a high protection category. The connection to the AS interface cable is achieved via penetration technology in the integrated flat cable. The insert for the flat cables can be turned in two orientations. All connections to inputs are implemented via metal inserts for high stability. The connection to the sensors is achieved via a M12 x 1 circular connector with SPEEDCON quick locking option. To indicate the current switching state there is an LED for each channel fitted to the top of the module. An LED for monitoring the AS interface communication and for displaying that the module has the address 0 is also available. For communiction errors the power is switched off the outputs (only for P1=1). According to approval the module can be used up to category 4/PL e as per ISO 13849-1, SIL 3 as per EN/IEC 61508 wiht the use of both input channels. When using two one-channel switches the module can be used up to category 2/PL c as per ISO 13849-1, SIL 2 as per EN/IEC 61508. Both channels of the mechanical switch are monitored for cross connection. One LED shows the voltage of the AS-Interface and another the external voltage supply.

Parámetros técnicos

Slave type: Safety-Slave
AS-Interface specification: V2.1
Required master specification: ≥ V2.1
UL File Number: E223772
Safety Integrity Level (SIL): SIL 3
Performance level (PL): PL e
Category: Cat. 4
MTTFd: no significant contribution to MTTFd of the overall system
PFHd: no significant contribution to PFH of the overall system
PFD: no significant contribution to PFD of the overall system
LED FAULT: error display; LED red red: communication error or address is 0 red flashing: Output supply overload
LED PWR: AS-Interface voltage; green LED green: voltage OK flashing green: address 0
LED AUX: ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage
LED IN: switching state (input); 2 LED yellow
LED OUT: Switching status (output); 2 yellow/red LEDs Yellow: output active Red: output overload
Auxiliary voltage (output): 24 V DC ± 15 % PELV
Rated operating voltage: 26.5 ... 31.6 V from AS-Interface
Rated operating current: ≤ 50 mA
Protection class: III
Surge protection: UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV) derived from mains up to 300 V AC line-to-neutral
Rated insulation voltage: 40 V
Pulse withstand voltage: 0.5 kV
Number/Type: 2 safety-related inputs for mechanical contacts, crossed-circuit monitored: 2 single-channel contacts: up to category 2/PL c to ISO 13849-1 or 1 2-channel contact: up to category 4/PL e to ISO 13849-1 Cable length must not exceed 300 m per input.
Supply: from AS-Interface
Voltage: 20 ... 30 V DC pulsed
Current loading capacity: input current limited ≤ 15 mA, overload and short-circuit resistant
Number/Type: 2 conventional electronic outputs, PNP
Supply: from external auxiliary voltage UAUX
Voltage: ≥ (UAUX - 0.5 V)
Current: 1.5 A per output , short-circuit protected
Electromagnetic compatibility: Directive 2014/30/EU: EN 62026-2:2013 EN 61000-6-2:2005 EN 61000-6-4:2007
Machinery Directive: Directive 2006/42/EC: EN ISO 13849-1:2008 + AC:2009 EN ISO 13849-2:2012 EN 62061:2005
Insulation coordination: EN 60947-1:2007
Degree of protection: EN 60529:2000
Fieldbus standard: EN 62026-2:2013
Electrical safety: IEC 60947-1, NFPA 79, IEC 60204-1:2007
Emitted interference: EN 61000-6-4:2007/A1:2011
AS-Interface: EN 62026-2:2013
Noise immunity: IEC 62026-2:2008 EN 62061:2005 EN 61000-6-2:2005
Functional safety: ISO 13849-1 (up to category 4/PL e), IEC 61508/IEC 62061 (up to SIL3)
Standards: NFPA 79:2007 ER 1
Profile: S-7.B
IO code: 7
ID code: B
ID1 code: F
ID2 code: 0
Data bits (function via AS-Interface): input output
Machinery Directive: D0: dyn. safety code 1 OUT 1
Machinery Directive: D1: dyn. safety code 1 OUT 2
Machinery Directive: D2: dyn. safety code 2 -
Machinery Directive: D3: dyn. safety code 2 -
Parameter bits (programmable via AS-i): function
Machinery Directive: P0: communication monitoring P0 = 1 (default settings), monitoring = ON, i.e. if communication fails, the outputs are de-energised P0 = 0, monitoring = OFF, if communication fails, the outputs maintain their condition
Machinery Directive: P1: Logic operation: P0 = 1 (default settings): The outputs are controlled via AS-Interface. P0 = 0: The outputs are controlled via AS-Interface or the inputs. The corresponding output is activated on opening the contacts of an input.
Machinery Directive: P2: not used
Machinery Directive: P3: not used
Ambient temperature: -25 ... 60 °C (-13 ... 140 °F)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Relative humidity: 85 % , noncondensing
Climatic conditions: For indoor use only
Altitude: ≤ 2000 m above MSL
Shock and impact resistance: 30 g, 11 ms in 6 spatial directions 3 shocks 10 g, 16 ms in 6 spatial directions 1000 shocks
Vibration resistance: 0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles
Pollution degree: 3
Degree of protection: IP67
Connection: Cable piercing method flat cable yellow/flat cable black inputs/outputs: M12 round connector
Material: Housing: PBT
Mass: 200 g
Tightening torque, cable gland: 0.4 Nm
Mounting: Mounting plate

Parámetros logísticos

ECCN:
País de origen: SG
EAN:
Peso: 0,00 kg
Longitud: 0,00 m
Anchura: 0,00 m
Altura: 0,00 m