180563
HD2-GTR-4PA
PROFIBUS Power Hub, Gateway Module
PROFIBUS DP V1 / For 4 segments PA, Couples PROFIBUS PA devices transparently to PROFIBUS DP, Optional redundant configuration, Installation in Zone 2/Class I, Div. 2, Up to 12 Mbit/s, auto adaptingpa
| Design / Mounting: | Motherboard based |
| Rated voltage: | 19.2 ... 35 V DC |
| Rated current: | 160 ... 90 mA |
| Power dissipation: | 3 W |
| PROFIBUS DP: Connection: | 9-pin Sub-D socket |
| PROFIBUS DP: Protocol: | PROFIBUS DP V1 |
| LED Seg 1...4: | red 2 Hz flashing: PA error, red and LED DP/ERR red: MAU error |
| LED PWR: | green: Power on |
| LED DP/ERR: | red 2 Hz flashing: DP error ; red: Hardware error |
| LED Red.: | yellow: redundant operation primary device ; yellow 2 Hz flashing: synchronization or redundancy not available |
| CH/PROFIBUS DP: | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff |
| PROFIBUS DP/Supply: | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff |
| CH/CH: | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff |
| All circuits/FE: | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1:2013 |
| Low voltage: Directive 73/23/EEC: | EN 50178 (identical to EN 62103) |
| Galvanic isolation: | IEC 62103 |
| Electromagnetic compatibility: | NE 21:2011 |
| Degree of protection: | IEC 60529 |
| Fieldbus standard: | IEC 61158-2 |
| Shock resistance: | EN 60068-2-27 |
| Vibration resistance: | EN 60068-2-6 |
| Ambient temperature: | -40 ... 60 °C (-40 ... 140 °F) |
| Storage temperature: | -40 ... 85 °C (-40 ... 185 °F) |
| Relative humidity: | < 95 % non-condensing |
| Shock resistance: | 15 g 11 ms |
| Vibration resistance: | 1 g , 10 ... 150 Hz |
| Pollution degree: | max. 2, according to IEC 60664 |
| Corrosion resistance: | acc. to ISA-S71.04-1985, severity level G3 |
| Housing material: | Polycarbonate |
| Housing width: | 40 mm |
| Housing height: | 106 mm |
| Housing depth: | 128 mm |
| Degree of protection: | IP20 |
| Mass: | 250 g |
| Mounting: | motherboard mounting , mounting in any orientation |
| Certificate: | TÜV 04 ATEX 2500 X |
| Low voltage: Marking: | II 3 G Ex nA IIC T4 Gc |
| Directive conformity: Directive 2014/34/EU: | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 |
| FM approval: FM certificate: | FM 19 US 0015 X and FM 19 CA 0011 X |
| FM approval: FM marking: | AEx/Ex ec IIC T4 |
| IECEx approval: IECEx certificate: | IECEx TUN 13.0038X |
| IECEx approval: IECEx marking: | Ex nA IIC T4 Gc |
| Marine approval: | DNV A-14038 |
| Supplementary information: | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| ECCN: | |
| País de origen: | SG |
| EAN: | |
| Peso: | 0,00 kg |
| Longitud: | 0,00 m |
| Anchura: | 0,00 m |
| Altura: | 0,00 m |