121495
HiD2030
SMART Transmitter Power Supply
2-channel isolated barrier, 24 V DC supply (bus powered), 2-wire SMART transmitters or current sources, Usable as signal splitter (1 input and 2 outputs), Dual output 4 mA .. 20 mA or 1 V .. 5 V, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508pa
| Signal type: | Analog input |
| Safety Integrity Level (SIL): | SIL 2 |
| Connection: | SL1: 1a(-), 1b(-); 2a(+), 2b(+) |
| Rated voltage: | 20.4 ... 30 V DC bus powered via Termination Board |
| Rated current: | 60 mA at 24 V, 20 mA output (per channel) |
| Power dissipation: | 1.05 W at 24 V (per channel) |
| Connection side: | field side |
| Connection: | SL2: 5a(+), 5b, 7a(-); 1a(+), 1b, 3b(-) |
| Input current: | 4 ... 20 mA , current limit 26 mA typ. |
| Input resistance: | 40 Ω , for current source |
| Ripple: | 10 mV eff |
| Voltage: | min. 15.5 V at 20 mA |
| Communication: | pass-through of HART signal to safe area The current sink terminals 4, 7 and 5, 6 do not pass the HART signal to safe area. |
| Connection side: | control side |
| Connection: | SL1: 8a(+), 7a(-); 10a(+), 9a(-) |
| Load: | 0 ... 650 Ω |
| Output signal: | 4 ... 20 mA or 1 ... 5 V (on 250 Ω, 0.1 % internal shunt) |
| Ripple: | 10 mV eff on a load of 250 Ω |
| Response time: | 70 ms , 10 ... 90 % step change |
| Signal level: | no fault: 1 mA ... 23.5 mA input current fault detection: < 0.2 mA or > 24 mA input current |
| Connection: | SL1: 6b |
| Output type: | open collector transistor (common to both channels) fault bus signal, collective error message |
| Calibrated accuracy: | < ± 0.1 % of full-scale value (current output) |
| Influence of temperature: | < ± 0.01 %/ K |
| Frequency range: | communication channel: 0.5 ... 40 kHz within 3 db, (-6 db at 100 kHz), Tx to output and output to Tx, suitable for use with SMART transmitters using HART or similar protocol |
| Influence of load: | < ± 0.1 % of full-scale value from 0 ... 650 Ω |
| Linearity: | < ± 0.05 % of full-scale value |
| Display elements: | LEDs |
| Control elements: | DIP-switch |
| Configuration: | via DIP switches |
| Labeling: | space for labeling at the front |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1:2013 (industrial locations) |
| Electromagnetic compatibility: | NE 21:2006 For further information see system description. |
| Degree of protection: | IEC 60529 |
| Ambient temperature: | -20 ... 60 °C (-4 ... 140 °F) |
| Degree of protection: | IP20 |
| Mass: | approx. 140 g |
| Dimensions: | 18 x 106 x 128 mm (0.7 x 4.2 x 5 inch) |
| Mounting: | on Termination Board |
| EU-Type Examination Certificate: | CESI 02 ATEX 086 |
| Electromagnetic compatibility: Marking: | II (1)G [Ex ia Ga] IIC , II (1)D [Ex ia Da] IIIC |
| Certificate: | PF 11 CERT 2109 X |
| Electromagnetic compatibility: Marking: | II 3G Ex nA IIC T4 Gc [device in zone 2] |
| Directive conformity: Directive 2014/34/EU: | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
| CSA approval: Control drawing: | 366-005CS-12B (cCSAus) |
| IECEx approval: | IECEx TUN 04.0012 |
| CSA approval: Approved for: | [Ex ia] IIC |
| ECCN: | |
| País de origen: | SG |
| EAN: | |
| Peso: | 0,00 kg |
| Longitud: | 0,00 m |
| Anchura: | 0,00 m |
| Altura: | 0,00 m |