KL4034
KL4034 | 4-channel analog output terminal -10…+10 V
The KL4034 analog output terminal generate signals in the range from +10 to -10 V. The power is supplied to the process level with a resolution of 12 bits and is electrically isolated. The output channels of a Bus Terminal have a common ground potential. The run LEDs give an indication of the data exchange with the Bus Coupler.
| Technology: | single-ended | 
| Number of outputs: | 4 | 
| Power supply: | via the K-bus | 
| Signal voltage: | -10…+10 V | 
| Load: | > 5 kΩ (short-circuit-proof) | 
| Output error: | < ±0.1 % (relative to end value) | 
| Resolution: | 12 bit | 
| Conversion time: | ~ 2 ms | 
| Electrical isolation: | 500 V (K-bus/signal voltage) | 
| Current consumption power contacts: | – (no power contacts) | 
| Current consumption K-bus: | typ. 85 mA | 
| Bit width in the process image: | output: 4 x 16 bit data (4 x 8 bit control/status optional) | 
| Configuration: | no address or configuration setting | 
| Weight: | approx. 85 g | 
| Operating/storage temperature: | 0…+55 °C/-25…+85 °C | 
| Relative humidity: | 95 %, no condensation | 
| Vibration/shock resistance: | conforms to EN 60068-2-6/EN 60068-2-27 | 
| EMC immunity/emission: | conforms to EN 61000-6-2/EN 61000-6-4 | 
| Protect. class/installation pos.: | IP 20/variable | 
| Pluggable wiring: | for all KSxxxx Bus Terminals | 
| Approvals: | CE, UL, Ex, GL | 
| ECCN: | |
| País de origen: | |
| EAN: | |
| Peso: | 0,00 kg | 
| Longitud: | 0,00 m | 
| Anchura: | 0,00 m | 
| Altura: | 0,00 m |