The KL3214 analog input terminal allows four resistance sensors to be connected directly. The Bus Terminal circuit can operate sensors using the 3-wire technique in a compact 12 mm housing. A microprocessor handles linearisation across the whole temperature range, which is freely selectable. The Bus Terminal’s standard settings are: resolution 0.1 °C. Sensor malfunctions such as broken wires are indicated by error LEDs.

Parámetros técnicos

Number of inputs: 4
Power supply: via the K-bus
Input filter limit frequency: typ. 1 kHz
Sensor types: PT100/200/500/1000, Ni100/120/1000, potentiometer: 10 Ω…1.2/4 kΩ, KTY sensors (types see documentation)
Connection method: 3-wire
Measuring range: -200…+850 °C (PT sensors); -60…+250 °C (Ni sensors)
Conversion time: approx. 170 ms default setting
Measuring current: < 0.5 mA (load-dependent)
Resolution: 0.1 °C per digit
Measuring error: < ±0.5 °C for PT sensors
Electrical isolation: 500 V (K-bus/signal voltage)
Current consumption power contacts:
Current consumption K-bus: typ. 120 mA
Special features: open-circuit recognition
Weight: approx. 60 g
Operating/storage temperature: 0…+55 °C/-25…+85 °C
Relative humidity: 95 %, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.: IP 20/variable
Approvals: CE, UL

Parámetros logísticos

ECCN:
País de origen:
EAN:
Peso: 0,00 kg
Longitud: 0,00 m
Anchura: 0,00 m