Descripción

The EP3314 EtherCAT Box with analog inputs permits four thermocouples to be directly connected. The module’s circuit can operate thermocouple sensors using the 2-wire technique. Linearisation over the full temperature range is realised with the aid of a microprocessor. The temperature range can be selected freely. The error LEDs indicate a broken wire. Compensation for the cold junction is made through a temperature measurement in the connecting plugs. This means that standard extension leads can be connected. The EP3314 can also be used for mV measurement.

Parámetros técnicos

Number of inputs: 4
Connection method: screw type M12, 2-wire connection for thermocouple
Protocol: EtherCAT
Bus interface: 2 x M8 socket, shielded, screw type
Sensor types: types J, K, L, B, E, N, R, S, T, U (default setting type K), mV measurement
Signal type: thermocouple
Measuring range: depending on sensor type; preset value is type K, -100…+1370 °C
Resolution: 0.1 °C per digit
Measuring error: < ±0.3 % for type K (relative to full scale value; further types see documentation)
Conversion time: 2.5 s up to 20 ms, see documentation, default: approx. 250 ms
Nominal voltage: 24 V DC (-15 %/+20 %)
Distributed clocks:
Input filter: 5 variations, configurable
Sensor supply:
Current consumption from US: 120 mA
Power supply connection: feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin
Bit width in the process image: 4 x 32 bit TC input, 4 x 16 bit TC output
Electrical isolation: 500 V
Special features: open-circuit recognition
Weight: approx. 165 g
Operating/storage temperature: -25…+60 °C/-40…+85 °C
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.: IP 65/66/67 (conforms to EN 60529)/variable
Approvals/Markings: CE, UL, ATEX
Ex-Marking: II 3 G Ex nA IIC T4 Gc