ELX1054
ELX1054 | 4-channel digital input terminal NAMUR, Ex i
The ELX1054 digital input terminal acquires signals from NAMUR field devices according to EN 60947-5-6. The sensors are supplied with a voltage of 8.2 V and return a diagnosable current signal. In this way, a wire breakage or short-circuit can be detected in addition to the switching state. The LEDs indicate signal or any error states, channel by channel.
| Technology: | DC switching amplifier |
| Specification: | IEC 60947-5-6 |
| Number of inputs: | 4 |
| Connection method: | 2-wire |
| Open circuit voltage: | typ. 8.2 V DC |
| “0” signal current: | ≤ 1.2 mA |
| “1” signal current: | ≥ 2.1 mA |
| Switching hysteresis: | 200 µA |
| Short-circuit current: | typ. 7 mA |
| Fault detection: | I ≤ 200 µA (cable break), I ≥ 6.3 mA (short circuit) |
| Max. switching frequency: | typ. 5 kHz (duty factor 50 %) |
| Supply voltage electronics: | 24 V DC (via power contacts), ELX9560 power supply |
| Current consumption power contacts: | typ. 15 mA + load |
| Current consumption E-bus: | typ. 70 mA |
| Weight: | approx. 55 g |
| Operating/storage temperature: | -25…+60 °C/-40…+85 °C |
| Relative humidity: | 95 %, no condensation |
| Vibration/shock resistance: | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission: | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos.: | IP 20/see documentation |
| Approvals/markings: | CE, UL, ATEX, IECEx, cFMus |
| Ex-Marking: | ATEX: II 3(1)G Ex ec [ia Ga] IIC T4 Gc II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I IECEx: Ex ec [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I cFMus: AIS Class I, II, III, Division 1, Groups A thru G Class I, Division 2, Groups A, B, C, D Class I, Zone 2, AEx nA [ia Ga] IIC T4 Gc Class I, Zone 2, AEx ec [ia Ga] IIC T4 Gc [AEx ia Da] IIIC T4 |
| ECCN: | |
| País de origen: | |
| EAN: | |
| Peso: | 0,00 kg |
| Longitud: | 0,00 m |
| Anchura: | 0,00 m |
| Altura: | 0,00 m |