Article image EL3204

Beckhoff EL3204

EL3204 | 4-channel input terminal PT100 (RTD)

Bajo pedido. Envíenos un correo electrónico para consultar el precio y la disponibilidad.
"ucnguBrctvdgcxgt0eqo"

Descripción

The EL3204 analog input terminal allows resistance sensors to be connected directly. The EtherCAT Terminal circuit can operate sensors using the 2-wire technique. A microprocessor handles linearisation across the whole temperature range, which is freely selectable. The EtherCAT Terminal’s standard settings are: resolution 0.1 °C in the temperature range of PT100 sensors. Sensor malfunctions such as broken wires are indicated by error LEDs.

Parámetros técnicos

Number of inputs: 4
Power supply: via the E-bus
Distributed clocks:
Input filter limit frequency: typ. 1 kHz
Sensor types: PT100, PT200, PT500, PT1000, Ni100, Ni120, Ni1000 resistance measurement (e.g. potentiometer, 10 Ω…1/4 kΩ), KTY sensors (types see documentation)
Connection method: 2-wire
Resolution: 0.1 °C per digit
Conversion time: approx. 85 ms default setting, 2…800 ms configurable
Temperature range: -200…+850 °C (PT sensors); -60…+250 °C (Ni sensors)
Measuring current: < 0.5 mA (load-dependent)
Measuring error: < ±0.5 °C for PT sensors
Electrical isolation: 500 V (E-bus/signal voltage)
Current consumption power contacts:
Current consumption E-bus: typ. 190 mA
Bit width in the process image: 4 x 32 bit RTD input
Special features: integrated digital filter, limit value monitoring
Weight: approx. 60 g
Operating/storage temperature: -25…+60 °C/-40…+85 °C
Relative humidity: 95 %, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.: IP 20/variable
Pluggable wiring: for all ESxxxx terminals
Approvals/markings: CE, UL, ATEX
Ex-Marking: II 3 G Ex nA IIC T4 Gc

Parámetros logísticos

ECCN:
País de origen:
EAN:
Peso: 0,00 kg
Longitud: 0,00 m
Anchura: 0,00 m
Altura: 0,00 m