2903144
TRIO-PS-2G/1AC/24DC/5/B+D
| Width: | 35 mm |
| Height: | 130 mm |
| Depth: | 115 mm |
| Installation distance right/left: | 0 mm / 0 mm |
| Installation distance top/bottom: | 50 mm / 50 mm |
| Degree of protection: | IP20 |
| Inflammability class in acc. with UL 94 (housing / terminal blocks): | V0 |
| Ambient temperature (operation): | -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
| Ambient temperature (start-up type tested): | -25 °C |
| Ambient temperature (storage/transport): | -40 °C ... 85 °C |
| Max. permissible relative humidity (operation): | ≤ 95 % (at 25 °C, non-condensing) |
| Climatic class: | 3K3 (in acc. with EN 60721) |
| Degree of pollution: | 2 |
| Installation height: | ≤ 5000 m (> 2000 m, observe derating) |
| Nominal input voltage range: | 100 V AC ... 240 V AC |
| Input voltage range: | 100 V AC ... 240 V AC -15 % ... +10 % |
| Dielectric strength maximum: | ≤ 300 V AC 15 s |
| AC frequency range: | 50 Hz ... 60 Hz ±5 Hz |
| Frequency range (fN): | 50 Hz ... 60 Hz ±10 % |
| Discharge current to PE: | < 0.25 mA |
| Current consumption: | 2.2 A (100 V AC) |
| Nominal power consumption: | 272 VA |
| Inrush current: | ≤ 16 A (typical) |
| Mains buffering time: | typ. 20 ms (120 V AC) |
| Input fuse: | 6.3 A (internal (device protection)) |
| Recommended breaker for input protection: | 6 A ... 16 A (Characteristics B, C, D, K) |
| Power factor (cos phi): | 0.5 |
| Type of protection: | Transient surge protection |
| Protective circuit/component: | Varistor |
| Nominal output voltage: | 24 V DC ±1 % |
| Setting range of the output voltage (USet): | 24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted) |
| Nominal output current (IN): | 5 A |
| Dynamic Boost (IDyn.Boost): | 7.5 A (5 s) |
| Derating: | > 60 °C ... 70 °C (2.5%/K) |
| Connection in parallel: | Yes, for redundancy and increased capacity |
| Connection in series: | yes |
| Feedback voltage resistance: | ≤ 35 V DC |
| Protection against overvoltage at the output (OVP): | ≤ 30 V DC |
| Control deviation: | < 1 % (change in load, static 10 % ... 90 %) |
| Residual ripple: | < 50 mVPP (with nominal values) |
| Output power: | 120 W |
| Typical response time: | < 1 s |
| Maximum power dissipation in no-load condition: | < 1 W |
| Power loss nominal load max.: | < 16 W |
| Net weight: | 0.45 kg |
| Efficiency: | > 89 % (for 230 V AC and nominal values) |
| MTBF (IEC 61709, SN 29500): | > 3380000 h (25 °C) |
| Insulation voltage input/output: | 3 kV AC (type test) |
| Degree of protection: | IP20 |
| Protection class: | II (in closed control cabinet) |
| Inflammability class in acc. with UL 94 (housing / terminal blocks): | V0 |
| Mounting position: | horizontal DIN rail NS 35, EN 60715 |
| Assembly instructions: | alignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm |
| Connection method: | Push-in connection |
| Conductor cross section solid min.: | 0.2 mm² |
| Conductor cross section solid max.: | 4 mm² |
| Conductor cross section flexible min.: | 0.2 mm² |
| Conductor cross section flexible max.: | 2.5 mm² |
| Conductor cross section AWG min.: | 24 |
| Conductor cross section AWG max.: | 12 |
| Stripping length: | 10 mm |
| Connection method: | Push-in connection |
| Conductor cross section solid min.: | 0.2 mm² |
| Conductor cross section solid max.: | 4 mm² |
| Conductor cross section flexible min.: | 0.2 mm² |
| Conductor cross section flexible max.: | 2.5 mm² |
| Conductor cross section AWG min.: | 24 |
| Conductor cross section AWG max.: | 12 |
| Stripping length: | 8 mm |
| Connection method: | Push-in connection |
| Conductor cross section solid min.: | 0.2 mm² |
| Conductor cross section solid max.: | 1.5 mm² |
| Conductor cross section flexible min.: | 0.2 mm² |
| Conductor cross section flexible max.: | 1.5 mm² |
| Conductor cross section AWG min.: | 24 |
| Conductor cross section AWG max.: | 16 |
| Stripping length: | 8 mm |
| EMC requirements for noise immunity: | EN 61000-6-1 |
| EMC requirements for noise emission: | EN 61000-6-3 |
| Standard - Safety of transformers: | EN 61558-2-16 (air clearances and creepage distances only) |
| Standard - Electrical safety: | IEC 60950-1/VDE 0805 (SELV) |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations: | EN 50178/VDE 0160 (PELV) |
| Standard – Safety extra-low voltage: | IEC 60950-1 (SELV) and EN 60204-1 (PELV) |
| Standard - Safe isolation: | DIN VDE 0100-410 |
| Standard – Limitation of mains harmonic currents: | EN 61000-3-2 |
| Mains variation/undervoltage: | Semi F47-0706 |
| Rail applications: | EN 50121-4 |
| UL approvals: | UL Listed UL 508 |
| Shipbuilding approval: | DNV GL (EMC B) |
| Electromagnetic compatibility: | Conformance with EMC Directive 2014/30/EU |
| Low Voltage Directive: | Conformance with Low Voltage Directive 2014/35/EC |
| Electrostatic discharge: | EN 61000-4-2 |
| Contact discharge: | 6 kV (Test Level 4) |
| Discharge in air: | 8 kV (Test Level 4) |
| Electromagnetic HF field: | EN 61000-4-3 |
| Frequency range: | 80 MHz ... 1 GHz |
| Test field strength: | 10 V/m (Test Level 3) |
| Frequency range: | 1 GHz ... 2 GHz |
| Test field strength: | 10 V/m (Test Level 3) |
| Frequency range: | 2 GHz ... 3 GHz |
| Test field strength: | 10 V/m (Test Level 3) |
| Comments: | Criterion A |
| Fast transients (burst): | EN 61000-4-4 |
| Input: | 4 kV (Test Level 4 - asymmetrical) |
| Output: | 2 kV (Test Level 3 - asymmetrical) |
| Signal: | 1 kV (Test Level 2 - asymmetrical) |
| Comments: | Criterion A |
| Surge voltage load (surge): | EN 61000-4-5 |
| Input: | 2 kV (Test Level 3 - symmetrical) |
| Output: | 1 kV (Test Level 2 - symmetrical) |
| Signal: | 1 kV (Test Level 2 - asymmetrical) |
| Comments: | Criterion B |
| Conducted interference: | EN 61000-4-6 |
| Frequency range: | 0.15 MHz ... 80 MHz |
| Voltage: | 10 V (Test Level 3) |
| Comments: | Criterion A |
| Criterion A: | Normal operating behavior within the specified limits. |
| Criterion B: | Temporary impairment to operational behavior that is corrected by the device itself. |
| REACh SVHC: | Lead 7439-92-1 |
| eCl@ss 10.0.1: | 27040701 |
| eCl@ss 4.0: | 27040700 |
| eCl@ss 4.1: | 27040700 |
| eCl@ss 5.0: | 27049000 |
| eCl@ss 5.1: | 27049000 |
| eCl@ss 6.0: | 27049000 |
| eCl@ss 7.0: | 27049002 |
| eCl@ss 8.0: | 27049002 |
| eCl@ss 9.0: | 27040701 |
| ETIM 3.0: | EC001039 |
| ETIM 4.0: | EC000599 |
| ETIM 5.0: | EC002540 |
| ETIM 6.0: | EC002540 |
| ETIM 7.0: | EC002540 |
| UNSPSC 6.01: | 30211502 |
| UNSPSC 7.0901: | 39121004 |
| UNSPSC 11: | 39121004 |
| UNSPSC 12.01: | 39121004 |
| UNSPSC 13.2: | 39121004 |
| UNSPSC 18.0: | 39121004 |
| UNSPSC 19.0: | 39121004 |
| UNSPSC 20.0: | 39121004 |
| UNSPSC 21.0: | 39121004 |
| ТН ВЭД: | |
| Страна происхождения: | CN |
| EAN: | |
| Вес: | 0,573 kg |
| Длина: | 0,00 m |
| Ширина: | 0,00 m |
| Высота: | 0,00 m |