70104166
VAA-2E2A-CB10-SJ/E2J-FL
AS-Interface Sicherheitsmodul VAA-2E2A-CB10-SJ/E2J-FL
The VAA-2E2A-CB10-SJ/E2J-* is an AS-Interface safety module with 2 safety-related inputs and two conventional outputs. A two-channel mechanical switch or a single channel mechanical switch each can be connected to the two safety-related inputs. The outputs are conventional electronic non-safety-related outputs, which can be loaded with 100 mA in total. The module is suitable for remote connection of switches in very limited space. The onepiece housing provides a degree of protection of IP20. The connection to the AS-Interface cable as well as to the inputs and outputs takes place via strands with open cable ends. To indicate the current switching state, an LED is available for each channel,mounted on top of the module. Two status LEDs are used to monitor the AS-Interface communication and indicate whether the module has the address 0. The module can be used up to Category 4/PL e according to ISO 13849-1, SIL 3 according to EN 62061. If two single-channel switches are connected, the module can be used up to Category 2/ PL c according to ISO 13849-1, SIL 1 according to EN 62061.
Slave type: | Safety-Slave |
AS-Interface specification: | V3.0 |
Required master specification: | ≥ V2.1 |
UL File Number: | E223772 |
LED FAULT: | error display; LED red red: communication error or address is 0 |
LED PWR: | AS-Interface voltage; green LED green: voltage OK flashing green: address 0 |
LED IN: | switching state (input); 2 LED yellow |
LED OUT: | Switching state (output); 2 LED yellow |
Rated operating voltage: | 26.5 ... 31.6 V from AS-Interface (PELV) |
Rated operating current: | ≤ 40 mA (without inputs/outputs)/max. 160 mA |
Protection class: | III |
Surge protection: | Ue: Over voltage category III, safe isolated power supplies (PELV) |
Rated insulation voltage: | 32 V |
Pulse withstand voltage: | 0.8 kV |
Number/Type: | 2 safety-related inputs for mechanical contacts, crossed-circuit monitored: 2 single-channel contacts: Up to category 2/PLc in accordance with ISO 13849-1 or SIL 1 in accordance with IEC 62061 1 two-channel contact: Up to category 4/PLe in accordance with ISO 13849-1 or SIL 3 in accordance with IEC 62061 |
Supply: | from AS-Interface |
Voltage: | 20 ... 30 V DC pulsed |
Current: | input current limited ≤ 15 mA, short-circuit protected |
Number/Type: | 2 conventional electronic outputs, PNP , overload and short-circuit resistant |
Supply: | from AS-Interface |
Voltage: | (UASI - 7.0 V) ≤ UOUT ≤ UASI |
Current: | ≤ 100 mA per output, ≤ 100 mA total |
Electromagnetic compatibility: Directive 2014/30/EU: | IEC 62026-2:2013 EN 61000-6-2:2005 EN 61000-6-4:2007 EN 61326-1:2013 |
Machinery Directive: Directive 2006/42/EC: | EN ISO 13849-1:2015 EN ISO 13849-2:2012 EN 62061:2005 + AC:2010 + A1:2013 + A2:2015 |
Degree of protection: | EN 60529:2000 |
Fieldbus standard: | EN 62026-2:2013 |
Electrical safety: | IEC 61140:2009 |
Emitted interference: | EN 61000-6-4:2007 |
AS-Interface: | EN 62026-2:2013 |
Noise immunity: | IEC 62026-2:2013 EN 61326-3-1:2017 EN 61000-6-2:2005 |
Functional safety: | EN ISO 13849-1:2015 EN ISO 13849-2:2012 EN 62061:2005 + AC:2010 + A1:2013 + A2:2015 |
Profile: | S-7.B |
IO code: | 7 |
ID code: | B |
ID1 code: | F |
ID2 code: | 0 |
Data bits (function via AS-Interface): | input output |
Machinery Directive: D0: | dyn. safety code 1 OUT 1 |
Machinery Directive: D1: | dyn. safety code 1 OUT 2 |
Machinery Directive: D2: | dyn. safety code 2 - |
Machinery Directive: D3: | dyn. safety code 2 - |
Parameter bits (programmable via AS-i): | function |
Machinery Directive: P0: | not used |
Machinery Directive: P1: | not used |
Machinery Directive: P2: | not used |
Machinery Directive: P3: | not used |
UL approval: | Protection class IP20 is not included in the UL approval. The protection class is tested by Pepperl+Fuchs. |
Ambient temperature: | -25 ... 70 °C (-13 ... 158 °F) |
Storage temperature: | -25 ... 85 °C (-13 ... 185 °F) |
Relative humidity: | 85 % , noncondensing |
Climatic conditions: | For indoor use only |
Altitude: | ≤ 5000 m above MSL |
Shock and impact resistance: | 30 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks |
Vibration resistance: | 0.35 mm 10 ... 57 Hz , 5 g 57 ... 2000 Hz, 10 cycles |
Pollution degree: | 2 |
Degree of protection: | IP20 according to EN 60529 |
Connection: | 200 mm, PVC cable 0.5 mm2 |
Material: Contacts: | open conductor ends with connector sleeves |
Material: Housing: | Polyamide hot-melt adhesive |
Mass: | 31 g |
Note: | This device is maintenance-free. If the device is used in a manner not specified by the manufaturer, the protection provided by the device may be impaired. |
ТН ВЭД: | |
Страна происхождения: | ID |
EAN: | |
Вес: | 0,00 kg |
Длина: | 0,00 m |
Ширина: | 0,00 m |
Высота: | 0,00 m |