1-channel isolated barrier, 24 V DC supply (bus powered), Analog input, digital input,, analog output, digital output, No configuration required, device is self-adapting, HART transparency, Low power dissipation, 3-way isolation, Up to SIL 2 acc. to IEC 61508pa. This isolated barrier is used for intrinsic safety applications. The device can transfer the following signals:, as an analog input: 0/4 mA .. 20 mA, as an analog output: 0/4 mA .. 20 mA, as a digital input: signals from NAMUR sensors or, dry contacts, as a digital output: max. 45 mA. The device requires no configuration and adapts itself automatically to the function of the active input/output of the connected process control system. The device permits the bi-directional pass-through of the HART communication. The device is designed primarily for use with universal I/O cards (e. g. Honeywell Universal Process IO). This device mounts on a HiC Termination Board.

Технические характеристики

Signal type: Universal
Safety Integrity Level (SIL): SIL 2
Connection: SL1: 1a(-), 1b(-); 2a(+), 2b(+)
Rated voltage: 19 ... 30 V DC via Termination Board
Ripple: ≤ 10 %
Rated current: ≤ 30 mA
Power consumption: ≤ 700 mW
Suitable field devices: 2-wire SMART transmitters, current sources
Signal: 0/4 ... 20 mA , limited to approx. 40 mA (depends on control system) , reverse polarity protected
Field circuit: SL2: 5a(+), 5b(-) (2-wire SMART transmitter) SL2: 5a(+), 1b(-) (2-wire SMART transmitter with current source)
Voltage drop: approx. 4 V (current source)
Control circuit: SL1: 8a(+), 7a(-)
Supply voltage: min. 16 V at 20 mA (2-wire SMART transmitter)
Voltage: 15 ... 30 V
Signal: 0/4 ... 20 mA , sink mode , working voltage 15 ... 30 V
Ripple: 20 mV rms
Suitable field devices: I/P converters (positioner), on-site-displays
Signal: 0/4 ... 20 mA
Field circuit: SL2: 5a(+), 5b(-)
Load: 0 ... 650 Ω
Voltage: ≥ 13 V at 20 mA
Ripple: 20 mV rms
Control circuit: SL1: 8a(+), 7a(-)
Voltage: 12 ... 30 V
Signal: 0/4 ... 20 mA
Line fault detection: > 100 kΩ at max. 30 V, with field wiring open
Field circuit: SL2: 5a(+), 1a(-) (NAMUR sensor) SL2: 5a(+), 5b(-) (dry contact)
Suitable field devices: NAMUR sensors according to IEC/EN 60947-5-6, dry contacts
Signal: 0.1 ... 9 mA , sink mode
Open loop voltage: approx. 10 V DC , 1 kΩ series resistance
Signal: 0.1 ... 9 mA
Control circuit: SL1: 8a(+), 7a(-)
Voltage: 13 ... 30 V
Field circuit: SL2: 5a(+), 5b(-)
Suitable field devices: solenoid valves, acoustic or visual alarms
Drive capability: 12 V / 40 mA at 300 Ω load
Open loop voltage: approx. 22 V
Current limit: 45 mA
Internal resistor: min. 240 Ω
Control circuit: SL1: 8a(+), 7a(-)
Voltage: 1-signal: 19 ... 30 V DC 0-signal: 0 ... 5 V DC
Current: 1-signal: 0 ... 45 mA, depending on the output load 0-signal: < 0.1 mA, independent of the output load
Power dissipation: 1.1 W at 24 V, 300 Ω load (digital output)
Deviation: at 20 °C (68 °F) ≤ ±20 µA incl. linearity, hysteresis and supply fluctuations at 4 ... 20 mA (analog input, analog output) ≤ ±60 µA incl. linearity, hysteresis and supply fluctuations at 0 ... 45 mA (digital output)
: Influence of ambient temperature: < 2 µA/K (0 ... 70 °C (32 ... 158 °F)) < 3 µA/K (-40 ... 0 °C (-40 ... 32 °F))
Switching frequency: ≤ 500 Hz with 50 % duty cycle (digital input, NAMUR sensor) ≤ 5 Hz (digital input, dry contact) ≤ 20 Hz (digital output)
Frequency range: HART: bandwidth by 0.5 Vpp signal and/or 1 mApp signal 950 ... 2500 Hz (analog input, analog output)
Settling time: ≤ 20 ms (analog input, analog output) ≤ 1 ms (digital input, NAMUR sensor)
Reaction time: ≤ 5 ms , turn-on/turn-off time (digital output)
Control/power supply: basic insulation according to IEC/EN 61010-1, rated insulation voltage 60 Veff
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Electromagnetic compatibility: NE 21:2011
Degree of protection: IEC 60529:2001
Protection against electrical shock: IEC 61010-1:2010
Input: EN 60947-5-6:2000
Ambient temperature: -40 ... 70 °C (-40 ... 158 °F) Observe the temperature range limited by derating, see section derating.
Storage temperature: -40 ... 85 °C (-40 ... 185 °F)
Relative humidity: 95 % non-condensing
Degree of protection: IP20
Mass: approx. 100 g
Dimensions: 12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 inch)
Mounting: on Termination Board
Coding: pin 1 and 4 trimmed For further information see system description.
EU-Type Examination Certificate: TÜV 14 ATEX 153522 X
Electromagnetic compatibility: Marking: II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
Supply: Maximum safe voltage: 250 V (Attention! The rated voltage can be lower.)
Equipment: SL2: 5a(+), 5b(-)
Supply: Voltage Uo: 25.2 V
Supply: Current Io: 110 mA
Supply: Power Po: 693 mW
Equipment: SL2: 5a(+), 1b(-)
Supply: Voltage Ui: < 28 V
Supply: Current Ii: < 115 mA
Supply: Voltage Uo: 7.2 V
Supply: Current Io: 0 mA
Supply: Power Po: 0 mW
Equipment: SL2: 5a(+), 1a(-)
Supply: Voltage Uo: 12.6 V
Supply: Current Io: 13 mA
Supply: Power Po: 41 mW
Certificate: TÜV 14 ATEX 153523 X
Supply: Marking: II 3G Ex ec IIC T4 Gc
Galvanic isolation: Input/Other circuits: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-7:2015
UL approval: E106378
Directive conformity: Control drawing: 116-0408 (cULus)
IECEx approval: IECEx certificate: IECEx TUN 15.0004X
IECEx approval: IECEx marking: [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Логистические характеристики