306126
NJ2-11-N-G
Inductive sensor
Series: Cylindrical type, Housing material: Stainless steel 1.4305 / AISI 303, Output type: 2-wire, Installation: flush, Type of voltage: DC, Connection type: cable PVC , 2 m, Degree of protection: IP68fa
Switching function: | Normally closed (NC) |
Output type: | NAMUR |
Rated operating distance: | 2 mm |
Installation: | flush |
Assured operating distance: | 0 ... 1.62 mm |
Actual operating distance: | 1.8 ... 2.2 mm |
Reduction factor rAl: | 0.4 |
Reduction factor rCu: | 0.3 |
Reduction factor r304: | 0.85 |
Output type: | 2-wire |
Nominal voltage: | 8.2 V (Ri approx. 1 kΩ) |
Switching frequency: | 0 ... 3000 Hz |
Hysteresis: | 0.5 ... 3.5 typ. 2 % |
Current consumption: Measuring plate not detected: | min. 3 mA |
Current consumption: Measuring plate detected: | ≤ 1 mA |
Safety Integrity Level (SIL): | SIL 2 |
MTTFd: | 5887 a |
Mission Time (TM): | 20 a |
Diagnostic Coverage (DC): | 0 % |
Standard conformity: NAMUR: | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
Standard conformity: Standards: | EN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012 |
EAC conformity: | TR CU 012/2011 |
FM approval: Control drawing: | 116-0165 |
UL approval: Ordinary Location: | E87056 |
UL approval: Hazardous Location: | E501628 |
UL approval: Control drawing: | 116-0452 |
CCC approval: | CCC approval / marking not required for products rated ≤36 V |
Ambient temperature: | -25 ... 100 °C (-13 ... 212 °F) |
Connection type: | cable PVC , 2 m |
Core cross-section: | 0.34 mm2 |
Housing material: | Stainless steel 1.4305 / AISI 303 |
Sensing face: | PVDF |
Degree of protection: | IP68 |
Cable: Bending radius: | > 10 x cable diameter |
Use in the hazardous area: | see instruction manuals |
ТН ВЭД: | |
Страна происхождения: | ID |
EAN: | |
Вес: | 0,00 kg |
Длина: | 0,00 m |
Ширина: | 0,00 m |
Высота: | 0,00 m |