294980
KFD0-CS-Ex1.51P
Current Driver/Repeater
1-channel isolated barrier, 24 V DC supply (loop powered), Current input/output 0 mA .. 40 mA, I/P or transmitter power supply, Accuracy 1 %, Reverse polarity protection, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the field / to the control systempa. This isolated barrier is used for intrinsic safety applications. The device transfers DC signals of fire alarms and smoke alarms from the hazardous area to the non-hazardous area. The device can also be used to control I/P converters, valves, indicators, and audible alarms. A reverse polarity protection prevents damage to the device caused by faulty wiring. The device is loop powered. From the control side no additional power supply has to be connected. Use the technical data to verify that proper voltage is available to the field devices.
Signal type: | Analog input/analog output |
Safety Integrity Level (SIL): | SIL 2 |
Rated voltage: | loop powered |
Connection: | terminals 12-, 11+ |
Voltage: | 4 ... 35 V DC |
Current: | 0 ... 40 mA |
Power dissipation: | at 40 mA and Uin < 22 V: 700 mW per channel at 40 mA and Uin > 22 V: 1.2 W per channel |
Connection: | terminals 1+, 2- |
Voltage: | for 4 V < Uin < 24 V: ≥ Uin - (0.37 x current in mA) - 1.0 for Uin > 24 V: ≥ 21 V - (0.36 x current in mA) |
Short-circuit current: | at Uin > 24 V: ≤ 65 mA |
Transfer current: | ≤ 40 mA |
Accuracy: | 1 % |
Deviation: After calibration: | ≤ ± 200 µA; incl. calibration, linearity, hysteresis and load fluctuations at the field side up to a load of 1 kΩ and current ≤ 20 mA at 20 °C (68 °F) |
Deviation: Influence of ambient temperature: | ≤ ± 2 µA/K at Uin ≤ 20 V; ≤ ± 5 µA/K at Uin > 20 V |
Rise time: | ≤ 5 ms at bounce from 4 ... 20 mA and Uin < 24 V |
Field circuit/control circuit: | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Labeling: | space for labeling at the front |
Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1:2013 (industrial locations) |
Electromagnetic compatibility: | NE 21:2012 EN 61326-3-2:2008 |
Degree of protection: | IEC 60529:2001 |
Protection against electrical shock: | UL 61010-1:2012 |
Ambient temperature: | -20 ... 60 °C (-4 ... 140 °F) |
Degree of protection: | IP20 |
Connection: | screw terminals |
Mass: | approx. 100 g |
Dimensions: | 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1 |
Mounting: | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
EU-type examination certificate: | BAS 98 ATEX 7343 X |
Electromagnetic compatibility: Marking: | II (1)G [Ex ia Ga] IIC, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I (-20 °C ≤ Tamb ≤ 60 °C) |
Electromagnetic compatibility: Voltage: | 25.2 V |
Electromagnetic compatibility: Current: | 93 mA |
Electromagnetic compatibility: Power: | 585 mW |
Control circuit: Maximum safe voltage: | 250 V eff (Attention! The rated voltage can be lower.) |
Field circuit: Maximum safe voltage: | 250 V eff (Attention! The rated voltage can be lower.) |
Certificate: | TÜV 99 ATEX 1499 X |
Field circuit: Marking: | II 3G Ex nA II T4 [device in zone 2] |
Galvanic isolation: Field circuit/control circuit: | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Directive conformity: Directive 2014/34/EU: | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
FM approval: Control drawing: | 116-0437 |
UL approval: Control drawing: | 116-0438 (cULus) |
IECEx approval: IECEx certificate: | IECEx BAS 05.0004X IECEx CML 19.0040X |
IECEx approval: IECEx marking: | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
Supplementary information: | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
ТН ВЭД: | |
Страна происхождения: | SG |
EAN: | |
Вес: | 0,00 kg |
Длина: | 0,00 m |
Ширина: | 0,00 m |
Высота: | 0,00 m |