292461
KFD2-GS-1.2W
Current/Voltage Trip Value
1-channel signal conditioner, 24 V DC supply (Power Rail), Current and voltage input, 2 relay contact outputs, Programmable high/low alarm, Configurable via DIP switches and potentiometer, Terminal blocks with test socketspa. This signal conditioner provides the galvanic isolation beetween field circuits and control circuits. The device is a trip amplifier with two trip points. Trip points, hysteresis and mode of operation can be set independently for both relay outputs. 0/4 mA ... 20 mA-, 0/1 V ... 5 V- or 0/2 V ... 10 V signals can be connected at the input. The device actuates the relay output when it reaches the adjusted trip points. The device is easily configured by the use of DIP switches and potentiometers.
Signal type: | Analog input |
Connection: | Power Rail or terminals 14+, 15- |
Rated voltage: | 20 ... 30 V DC |
Rated current: | < 50 mA |
Power consumption: | < 1.5 W |
Connection side: | field side |
Measurement range: | terminals 1+, 3-: voltage 0/1 ... 5 V, load ≥ 50 kΩ or voltage 0/2 ... 10 V, load ≥ 100 kΩ terminals 2+, 3-: current 0/4 ... 20 mA ; load ≤ 50 Ω |
Connection side: | control side |
Output I, II: | terminals 7, 8, 9; 10, 11, 12 |
: Contact loading: | 250 V AC / 4 A / cos φ > 0.7; 40 V DC / 2 A resistive load |
Output III: | device configuration : terminals 4, 5, 6 |
Deviation: | ≤ 1 % |
: Influence of ambient temperature: | 0.01 % / K of adjusted trip value |
Input delay: | 200 ms |
Input/power supply: | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Input/output I, II: | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Output I, II/power supply: | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Display elements: | LEDs |
Control elements: | DIP-switch potentiometer |
Configuration: | via DIP switches via potentiometer |
Labeling: | space for labeling at the front |
Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1:2013 (industrial locations) |
Low voltage: Directive 2014/35/EU: | EN 61010-1:2010 |
Degree of protection: | IEC 60529 |
Protection against electrical shock: | EN 61010-1:2010 |
Ambient temperature: | -20 ... 60 °C (-4 ... 140 °F) |
Degree of protection: | IP20 |
Connection: | screw terminals |
Mass: | approx. 120 g |
Dimensions: | 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) , housing type B2 |
Mounting: | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Supplementary information: | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Optional accessories: | - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-GY(-UPR-03) |
ТН ВЭД: | |
Страна происхождения: | SG |
EAN: | |
Вес: | 0,00 kg |
Длина: | 0,00 m |
Ширина: | 0,00 m |
Высота: | 0,00 m |