Pepperl+Fuchs 248763

KFD2-UT2-2-1

Universal Temperature Converter

По запросу. Пожалуйста, отправьте нам письмо, чтобы узнать цену и наличие.
"ucnguBrctvdgcxgt0eqo"

Описание

This signal conditioner provides the galvanic isolation between field circuits and control circuits. 2-channel signal conditioner, 24 V DC supply (Power Rail), Thermocouple, RTD, potentiometer or voltage input, Usable as signal splitter (1 input and 2 outputs), Voltage output 0/1 V .. 5 V, Configurable by PACTware, Line fault (LFD) and sensor burnout detection, Up to SIL 2 acc. to IEC 61508/IEC 61511pa. The device converts the signal of a resistance thermometer, thermocouple, or potentiometer to a proportional output voltage. The device can also be configured as a signal splitter. The removable terminal block K-CJC-** is available as an accessory for internal cold junction compensation of thermocouples. A fault is signalized by LEDs acc. to NAMUR NE44 and a separate collective error message output. The device is easily configured by the use of the PACTware configuration software. For additional information, refer to the manual and www.pepperl-fuchs.com.

Технические характеристики

Signal type: Analog input
Safety Integrity Level (SIL): SIL 2
Connection: terminals 14+, 15- or power feed module/Power Rail
Rated voltage: 20 ... 30 V DC
Ripple: within the supply tolerance
Power dissipation/power consumption: ≤ 0.8 W / 0.8 W
Programming interface: programming socket
Connection side: field side
Connection: terminals 1, 2, 3; 4, 5, 6
RTD: type Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995) type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94) type Cu10, Cu50, Cu100 (P50353-92) type Ni100 (DIN 43760)
: Measuring current: approx. 200 µA with RTD
: Types of measuring: 2-, 3-wire connection
: Lead resistance: max. 50 Ω per line
: Measurement loop monitoring: sensor breakage, sensor short-circuit
Thermocouples: type B, E, J, K, N, R, S, T (IEC 584-1: 1995) type L (DIN 43710: 1985) type TXK, TXKH, TXA (P8.585-2001)
: Cold junction compensation: external and internal
: Measurement loop monitoring: sensor breakage
Potentiometer: 0 ... 20 kΩ (2-wire connection), 0.8 ... 20 kΩ (3-wire connection)
Voltage: selectable within the range -100 ... 100 mV
Input resistance: ≥ 1 MΩ (-100 ... 100 mV)
Connection side: control side
Voltage output: 0 ... 5 V or 1 ... 5 V ; output resistance: ≤ 5 Ω ; load: ≥ 10 kΩ
Connection: output I: terminals 7-, 8+ output II: terminals 10-, 11+
Fault signal: downscale 0 V or 0.5 V, upscale 5.375 V
Deviation: After calibration: Pt100: ± (0.06 % of measurement value in K + 0.1 K (4-wire connection)) thermocouple: ± (0.05 % of measurement value in °C + 1 K (1.2 K for types R and S)) this includes ± 0.8 K error of the cold junction compensation mV: ± 50 µV potentiometer: ± 0.05 % of full scale, (excludes errors due to lead resistance) output: 1 to 5 V output: ± 4 mV from 0 to 103.1 % of span; 0 to 5 V output: ± 4 mV from 0.3 to 102.5 % of span
Deviation: Influence of ambient temperature: deviation of CJC included: Pt100: ± (0.0015 % of measurement value in K + 0.006 % of span)/K ΔTamb*) thermocouple: ± (0.02 K + 0.005 % of measurement value in °C + 0.006 % of span)/K ΔTamb*) mV: ± (0.01 % of measurement value + 0.006 % of span)/K ΔTamb*) potentiometer: ± 0.006 % of span/K ΔTamb*) *) ΔTamb = ambient temperature change referenced to 23 °C (296 K)
Deviation: Influence of supply voltage: < 0.01 % of span
Reaction time: worst case value (sensor breakage and/or sensor short circuit detection enabled) mV: 1.2 s, thermocouples with CJC: 1.4 s, thermocouples with fixed ref. temp: 1.4 s, 3- or 4-wire RTD: 1.1 s, 2-wire RTD: 920 ms, Potentiometer: 3-wire connection 2.8 s, 2-wire connection 2.25 s
Input/Other circuits: basic insulation according to IEC 61010-1, rated insulation voltage 300 Veff
Output/supply, programming input: functional insulation, rated insulation voltage 50 V AC There is no electrical isolation between the programming input and the supply. The programming cable provides galvanic isolation so that ground loops are avoided.
Display elements: LEDs
Configuration: via PACTware
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Electromagnetic compatibility: NE 21:2006
Degree of protection: IEC 60529:2001
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Degree of protection: IP20
Connection: screw terminals
Mass: approx. 130 g
Dimensions: 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Optional accessories: - FDT framework PACTware 5.X - device type manager DTM Interface Technology - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-GY(-UPR-03)

Логистические характеристики

ТН ВЭД:
Страна происхождения: Singapur
EAN: 4050143074617
Вес: 0,15 kg
Длина: 0,00 m
Ширина: 0,00 m
Высота: 0,00 m