235078
NCN3-F31K2-N4-B13-S
Inductive sensor
Series: Double sensor, Housing material: rugged, translucent polycarbonate (PC) optimised for outdoor use, Output type: 2-wire, Installation: flush mountable, Type of voltage: DC, Connection type: screw terminals, Degree of protection: IP66 / IP68 / IP69fa
Switching function: | 2 x normally closed (NC) |
Output type: | NAMUR |
Rated operating distance: | 3 mm |
Installation: | flush mountable |
Assured operating distance: | 0 ... 2.4 mm For assured operating distance sar see Manual Functional Safety. |
Actual operating distance: | 2.7 ... 3.3 mm typ. |
Actuating element: | Stainless steel 1.4305 / AISI 303 8.5 mm x 8.5 mm x 0.5 mm |
Reduction factor rAl: | 0.4 |
Reduction factor rCu: | 0.4 |
Reduction factor r304: | 0.7 |
Reduction factor rSt37: | 1 |
Reduction factor rBrass: | 0.5 |
Output type: | 2-wire |
Nominal voltage: | 8 V |
Switching frequency: | 0 ... 3 kHz |
Hysteresis: | typ. 5 % |
Reverse polarity protection: | reverse polarity protected |
Short-circuit protection: | yes |
Suitable for 2:1 technology: | yes , Reverse polarity protection diode not required |
Current consumption: Measuring plate not detected: | ≥ 3 mA |
Current consumption: Measuring plate detected: | ≤ 1 mA |
Time delay before availability: | ≤ 1 ms |
Switching state indicator: | LED, yellow |
Valve status indicator: | LED, yellow |
Safety Integrity Level (SIL): | SIL 2 |
MTTFd: | 1730 a |
Mission Time (TM): | 20 a |
Diagnostic Coverage (DC): | 0 % |
Voltage: | max. 32 V DC |
Current: | max. 240 mA |
Short-circuit protection: | no |
Reverse polarity protection: | yes, with reversed output LED is out of function, therfore more power for solenoid valve |
Standard conformity: NAMUR: | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
Standard conformity: Electromagnetic compatibility: | NE 21:2007 |
Standard conformity: Standards: | EN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012 |
UL approval: | cULus Listed, General Purpose, Class 2 Power Source |
Standard conformity: Ordinary Location: | E87056 |
Standard conformity: Hazardous Location: | E501628 |
Standard conformity: Control drawing: | 116-0455 |
CCC approval: | CCC approval / marking not required for products rated ≤36 V |
Ambient temperature: | -40 ... 100 °C (-40 ... 212 °F) |
Storage temperature: | -40 ... 100 °C (-40 ... 212 °F) |
Connection type: | screw terminals |
Connection (system side): | Screw terminals, tightening torque min. 0.5 Nm Stripped length 7 mm , M20 x 1.5 cable gland , usable thread length 13.5 mm , screw-in depth max. 13.5 mm |
Core cross-section (system side): | rigid: 0.14 ... 2.5 mm2 flexible: 0.14 ... 1.5 mm2 flexible with core-end sleeve: 0.25 ... 1.5 mm2 |
Connection (valve side): | like connection (system side) |
Core cross-section (valve side): | like core cross section (system side) |
Housing material: | rugged, translucent polycarbonate (PC) optimised for outdoor use |
Housing base: | PC |
Degree of protection: | IP66 / IP68 / IP69 |
Tightening torque, housing screws: | ≤ 2 Nm |
Tightening torque, cable gland: | M20 x 1.5 ; max. 7 Nm |
Tightening torque, stopping plug: | 1 Nm |
Note: | LED switch-off |
Use in the hazardous area: | see instruction manuals |
ТН ВЭД: | |
Страна происхождения: | CZ |
EAN: | |
Вес: | 0,00 kg |
Длина: | 0,00 m |
Ширина: | 0,00 m |
Высота: | 0,00 m |