8951510000
VSPC 1CL PW 24V
| Type: | VSPC 1CL PW 24V |
| Order No.: | 8951510000 |
| Version: | Surge protection for instrumentation and control, 24 V, 24 V, 10 A, IEC 61643-21, HART-compatible |
| GTIN (EAN): | 4032248742752 |
| Qty.: | 1 pc(s). |
| Width: | 17.8 mm |
| Width (inches): | 0.701 inch |
| Height: | 90 mm |
| Height (inches): | 3.543 inch |
| Depth: | 69 mm |
| Depth (inches): | 2.717 inch |
| Net weight: | 50 g |
| Humidity: | 5...96 % |
| Operating temperature, max.: | 70 °C |
| Operating temperature, min.: | -40 °C |
| Storage temperature, max.: | 80 °C |
| Storage temperature, min.: | -40 °C |
| Operating temperature: | -40 °C...70 °C |
| Storage temperature: | -40 °C...80 °C |
| λges: | 45 |
| MTTF: | 2,537 Years |
| PFH in 1*10-9 per hour: | 1.95 |
| SFF: | 95.67 % |
| SIL in compliance with IEC 61508: | 3 |
| REACH SVHC: | Lead 7439-92-1 |
| Combined pulse UOC: | 6 kV |
| Max. continuous voltage, Uc (AC): | 27 V |
| Max. continuous voltage, Uc (DC): | 38 V |
| Protection level UP (typ.): | ≤ 0.8 kV |
| Rated voltage (AC): | 24 V |
| Rated voltage (DC): | 24 V |
| Certificate No. (UL): | E311081 |
| Gas group C: | IIB |
| Gas group D: | IIA |
| Gas groups A, B: | IIC |
| Input voltage, max. Ui: | 39 V |
| Internal inductance, max. LI: | 0 µH |
| Colour: | orange |
| Design: | Terminal, miscellaneous |
| Optical function display: | For Class III protection, green = OK; red = arrester is defective - replace |
| Protection degree: | IP20 |
| Segment: | Measurement - Monitoring - Setting |
| UL 94 flammability rating: | V-0 |
| Version: | without warning function / function indicator |
| Pollution severity: | 2 |
| Surge voltage category: | III |
| Rated voltage (AC): | 24 V |
| Rated voltage (DC): | 24 V |
| Voltage type: | AC/DC |
| Max. continuous voltage, Uc (AC): | 27 V |
| Max. continuous voltage, Uc (DC): | 38 V |
| Discharge current In (8/20µs) GND-PE: | 2.5 kA |
| Discharge current Imax (8/20µs) GND-PE: | 10 kA |
| Discharge current In (8/20µs) wire-PE: | 2.5 kA |
| Discharge current Imax (8/20µs) wire-PE: | 10 kA |
| Discharge current In (8/20µs) wire-wire: | 2.5 kA |
| Discharge current Imax (8/20µs) wire-wire: | 10 kA |
| Lightning test current, Iimp (10/350 µs) GND-PE: | 2.5 kA |
| Lightning test current, Iimp (10/350 µs) Wire–PE: | 2.5 kA |
| Lightning test current, Iimp (10/350 µs) wire-wire: | 2.5 kA |
| Fuse: | 0.5 A |
| Standards: | IEC 61643-21, HART-compatible |
| Protection level UP (typ.): | ≤ 0.8 kV |
| Protection level on output side Wire-PE 1kV/µs, typically: | 450 V |
| Protection level on output side Wire-wire 1 kV/µs, typically: | 60 V |
| Protection level on output side Wire-wire 8/20 µs, typically: | 60 V |
| Protection level, UP GND - PE: | 450 V |
| Protection level, UP wire - PE: | 450 V |
| Combined pulse UOC: | 6 kV |
| Number of poles: | 1 |
| Overload - failure mode: | Modus 2 |
| Protection level, UP wire - wire: | 40 V |
| Pulse-reset capacity: | ≤ 10 ms |
| Rated current: | 450 mA |
| Rated current IN: | 10 A |
| Requirements category acc. to IEC 61643-21: | C1, C2, C3, D1 |
| Signal transmission properties (-3 dB): | 3 MHz |
| Signalling contact: | No |
| Surge current-carrying capacity C1: | < 1 kA 8/20 μs |
| Surge current-carrying capacity C2: | 5 kA 8/20 μs |
| Surge current-carrying capacity C3: | 100 A 10/1000 μs |
| Surge current-carrying capacity D1: | 2.5 kA 10/350 μs |
| Volume resistance: | 2.20 Ω |
| Type of connection: | Pluggable in VSPC BASE |
| Long specification: | Surge protection plug for base element VSPC BASE 1CL PW with dual protective circuits, for power supply and a paired cable for floating-ground powered signal circuit (forexample, supply isolation amplifiers) protective switched power supply: temperature controlled varistors as a cross-protection between the active lines. Coarse protection of the common mode voltage to earth. Optical defect signal coupled with the temperature monitoring. Protective circuits, floating-ground driven signal circuits: two-stage protection switches consisting of coarse and fine protection between the signal wires as well as decoupling resistors. Mechanical identification of the plug to the base element according to the switching type and rated voltage. Protected plug with coding pin and counter-profile for the base element. Optical identification of the protected plug based on the type of protected switching and the voltage level. It is possible to mark the plug. |
| Short specification: | Surge protection plug for base element VSPC BASE 1CL PW with dual protective circuits, for 24 V power supply and a paired cable for floating-ground powered signal circuit. |
| ETIM 6.0: | EC000943 |
| ETIM 7.0: | EC000943 |
| eClass 9.0: | 27-13-08-07 |
| eClass 9.1: | 27-13-08-07 |
| eClass 10.0: | 27-13-08-07 |
| UNSPSC: | 30-21-19-21 |
| ROHS: | Conform |
| Type: | VSPC 1CL PW 24V |
| Order No.: | 8951510000 |
| Version: | Surge protection for instrumentation and control, 24 V, 24 V, 10 A, IEC 61643-21, HART-compatible |
| GTIN (EAN): | 4032248742752 |
| Qty.: | 1 pc(s). |
| Width: | 17.8 mm |
| Width (inches): | 0.701 inch |
| Height: | 90 mm |
| Height (inches): | 3.543 inch |
| Depth: | 69 mm |
| Depth (inches): | 2.717 inch |
| Net weight: | 50 g |
| Humidity: | 5...96 % |
| Operating temperature, max.: | 70 °C |
| Operating temperature, min.: | -40 °C |
| Storage temperature, max.: | 80 °C |
| Storage temperature, min.: | -40 °C |
| Operating temperature: | -40 °C...70 °C |
| Storage temperature: | -40 °C...80 °C |
| λges: | 45 |
| MTTF: | 2,537 Years |
| PFH in 1*10-9 per hour: | 1.95 |
| SFF: | 95.67 % |
| SIL in compliance with IEC 61508: | 3 |
| REACH SVHC: | Lead 7439-92-1 |
| Combined pulse UOC: | 6 kV |
| Max. continuous voltage, Uc (AC): | 27 V |
| Max. continuous voltage, Uc (DC): | 38 V |
| Protection level UP (typ.): | ≤ 0.8 kV |
| Rated voltage (AC): | 24 V |
| Rated voltage (DC): | 24 V |
| Certificate No. (UL): | E311081 |
| Gas group C: | IIB |
| Gas group D: | IIA |
| Gas groups A, B: | IIC |
| Input voltage, max. Ui: | 39 V |
| Internal inductance, max. LI: | 0 µH |
| Colour: | orange |
| Design: | Terminal, miscellaneous |
| Optical function display: | For Class III protection, green = OK; red = arrester is defective - replace |
| Protection degree: | IP20 |
| Segment: | Measurement - Monitoring - Setting |
| UL 94 flammability rating: | V-0 |
| Version: | without warning function / function indicator |
| Pollution severity: | 2 |
| Surge voltage category: | III |
| Rated voltage (AC): | 24 V |
| Rated voltage (DC): | 24 V |
| Voltage type: | AC/DC |
| Max. continuous voltage, Uc (AC): | 27 V |
| Max. continuous voltage, Uc (DC): | 38 V |
| Discharge current In (8/20µs) GND-PE: | 2.5 kA |
| Discharge current Imax (8/20µs) GND-PE: | 10 kA |
| Discharge current In (8/20µs) wire-PE: | 2.5 kA |
| Discharge current Imax (8/20µs) wire-PE: | 10 kA |
| Discharge current In (8/20µs) wire-wire: | 2.5 kA |
| Discharge current Imax (8/20µs) wire-wire: | 10 kA |
| Lightning test current, Iimp (10/350 µs) GND-PE: | 2.5 kA |
| Lightning test current, Iimp (10/350 µs) Wire–PE: | 2.5 kA |
| Lightning test current, Iimp (10/350 µs) wire-wire: | 2.5 kA |
| Fuse: | 0.5 A |
| Standards: | IEC 61643-21, HART-compatible |
| Protection level UP (typ.): | ≤ 0.8 kV |
| Protection level on output side Wire-PE 1kV/µs, typically: | 450 V |
| Protection level on output side Wire-wire 1 kV/µs, typically: | 60 V |
| Protection level on output side Wire-wire 8/20 µs, typically: | 60 V |
| Protection level, UP GND - PE: | 450 V |
| Protection level, UP wire - PE: | 450 V |
| Combined pulse UOC: | 6 kV |
| Number of poles: | 1 |
| Overload - failure mode: | Modus 2 |
| Protection level, UP wire - wire: | 40 V |
| Pulse-reset capacity: | ≤ 10 ms |
| Rated current: | 450 mA |
| Rated current IN: | 10 A |
| Requirements category acc. to IEC 61643-21: | C1, C2, C3, D1 |
| Signal transmission properties (-3 dB): | 3 MHz |
| Signalling contact: | No |
| Surge current-carrying capacity C1: | < 1 kA 8/20 μs |
| Surge current-carrying capacity C2: | 5 kA 8/20 μs |
| Surge current-carrying capacity C3: | 100 A 10/1000 μs |
| Surge current-carrying capacity D1: | 2.5 kA 10/350 μs |
| Volume resistance: | 2.20 Ω |
| Type of connection: | Pluggable in VSPC BASE |
| Long specification: | Surge protection plug for base element VSPC BASE 1CL PW with dual protective circuits, for power supply and a paired cable for floating-ground powered signal circuit (forexample, supply isolation amplifiers) protective switched power supply: temperature controlled varistors as a cross-protection between the active lines. Coarse protection of the common mode voltage to earth. Optical defect signal coupled with the temperature monitoring. Protective circuits, floating-ground driven signal circuits: two-stage protection switches consisting of coarse and fine protection between the signal wires as well as decoupling resistors. Mechanical identification of the plug to the base element according to the switching type and rated voltage. Protected plug with coding pin and counter-profile for the base element. Optical identification of the protected plug based on the type of protected switching and the voltage level. It is possible to mark the plug. |
| Short specification: | Surge protection plug for base element VSPC BASE 1CL PW with dual protective circuits, for 24 V power supply and a paired cable for floating-ground powered signal circuit. |
| ETIM 6.0: | EC000943 |
| ETIM 7.0: | EC000943 |
| eClass 9.0: | 27-13-08-07 |
| eClass 9.1: | 27-13-08-07 |
| eClass 10.0: | 27-13-08-07 |
| UNSPSC: | 30-21-19-21 |
| ROHS: | Conform |
| ECCN: | |
| Kraj pochodzenia: | |
| EAN: | |
| Waga: | 0,052 kg |
| Długość: | 0,00 m |
| Szerokość: | 0,00 m |
| Wysokość: | 0,00 m |