1064230000
VSSC6 TRCL24VAC/DC0.5A
| Type: | VSSC6 TRCL24VAC/DC0.5A |
| Order No.: | 1064230000 |
| Version: | Surge protection for instrumentation and control, 24 V, 34 V, 500 mA, IEC 61643-21, HART-compatible |
| GTIN (EAN): | 4032248829590 |
| Qty.: | 10 pc(s). |
| Width: | 6.2 mm |
| Width (inches): | 0.244 inch |
| Height: | 88.5 mm |
| Height (inches): | 3.484 inch |
| Depth: | 81 mm |
| Depth (inches): | 3.189 inch |
| Net weight: | 43.4 g |
| Humidity: | 5...96 % |
| Operating temperature, max.: | 70 °C |
| Operating temperature, min.: | -40 °C |
| Storage temperature, max.: | 80 °C |
| Storage temperature, min.: | -40 °C |
| Operating temperature: | -40 °C...70 °C |
| Storage temperature: | -40 °C...80 °C |
| λges: | 19 |
| MTTF: | 6,008 Years |
| PFH in 1*10-9 per hour: | 1.95 |
| SFF: | 89.74 % |
| SIL in compliance with IEC 61508: | 2 |
| REACH SVHC: | Lead 7439-92-1 |
| Certificate No. (UL): | E311081 |
| Gas group C: | IIB |
| Gas group D: | IIA |
| Gas groups A, B: | IIC |
| Input current, max. II: | 500 mA |
| Input voltage, max. Ui: | 42 V |
| Internal capacity, max. CI: | 1 nF |
| Internal inductance, max. LI: | 0 µH |
| Colour: | black |
| Design: | Terminal |
| Isolating function: | Yes |
| Optical function display: | No |
| Protection degree: | IP20 |
| Rail: | TS 35 |
| Segment: | Measurement - Monitoring - Setting |
| Testing option: | Functional screw with test plug receptacle, connections 1, 2, 4, 5 |
| UL 94 flammability rating: | V-0 |
| Version: | Surge protection for measurement and control |
| Pollution severity: | 2 |
| Surge voltage category: | III |
| Rated voltage (AC): | 24 V |
| Rated voltage (DC): | 34 V |
| Voltage type: | AC/DC |
| Max. continuous voltage, Uc (AC): | 30 V |
| Max. continuous voltage, Uc (DC): | 42 V |
| Discharge current, max. (8/20 µs): | 10 kA |
| Discharge current In (8/20µs) wire-PE: | 2.5 kA |
| Discharge current Imax (8/20µs) wire-PE: | 5 kA |
| Discharge current In (8/20µs) wire-wire: | 2.5 kA |
| Discharge current Imax (8/20µs) wire-wire: | 5 kA |
| Lightning test current Iimp (10/350 µs): | 0.5 kA |
| Lightning test current, Iimp (10/350 µs) Wire–PE: | 0.5 kA |
| Fuse: | 0.5 A |
| Standards: | IEC 61643-21, HART-compatible |
| Protection level UP (typ.): | 900 V |
| Protection level UP for C1 with 500V/250A (wire-PE): | 456 V |
| Protection level UP for C2 with 10kV/5kA (wire-PE): | 960 V |
| Protection level UP for C2 with 10kV/5kA (wire-wire): | 108 V |
| Protection level UP for C3 with 1kV/µs (wire-PE): | 572 V |
| Protection level UP for C3 with 1kV/µs (wire-wire): | 55 V |
| Protection level UP for D1 with 0.5kA (wire-wire): | 94 V |
| Protection level on output side Wire-wire 1 kV/µs, typically: | 70 V |
| Insertion loss: | 250 MHz |
| Number of poles: | 1 |
| Overload - failure mode: | Modus 2 |
| Protection level UP for C1 with 500V/250A (wire-wire): | 62 V |
| Protection level, UP wire - wire: | 90 V |
| Pulse-reset capacity: | ≤ 170 ms |
| Rated current IN: | 500 mA |
| Requirements category acc. to IEC 61643-21: | C2, C3, D1 |
| Signal transmission properties (-3 dB): | 270 Mhz |
| Surge current-carrying capacity C2: | 2.5 kA 8/20 µs 5 kV 1.2/50 µs |
| Surge current-carrying capacity C3: | 50 A 10/1000 μs |
| Surge current-carrying capacity D1: | 0.5 kA 10/350 μs |
| Volume resistance: | 1.8 Ω 10 % |
| Type of connection: | Screw connection |
| Tightening torque, min.: | 0.5 Nm |
| Tightening torque, max.: | 0.8 Nm |
| Clamping range, min.: | 0.5 mm² |
| Clamping range, max.: | 4 mm² |
| Wire cross-section, solid, min.: | 0.5 mm² |
| Wire cross-section, solid, max.: | 6 mm² |
| Conductor cross-section, flexible, AEH (DIN 46228-1), min.: | 0.5 mm² |
| Conductor cross-section, flexible, AEH (DIN 46228-1), max.: | 4 mm² |
| Connection cross-section, stranded, min.: | 0.5 mm² |
| Connection cross-section, stranded, max.: | 4 mm² |
| Long specification: | Surge protection in a one piece, 6.2 mm wide DIN rail module for a floating-ground signal circuit with 24 V UC, 2-wire technology. Each signal path can be opened using an isolator. A current loop with max. 0.6A can be protected here. When the terminal is fitted, a simultaneous electrically conducting contact is made between the mounting rail (earth) and the reference potential (ground) of the protection circuit in the terminal. Optical identification of the terminal based on the type of protected switching and the voltage level. The terminal can be labelled or marked. |
| Short specification: | Surge protection in a one piece, 6.2 mm wide DIN rail module for a floating-ground driven signal circuit with 2-wire technology and a common wire. Each signal path can be opened using an isolator. Version: 24V UC |
| ETIM 6.0: | EC000943 |
| ETIM 7.0: | EC000943 |
| eClass 9.0: | 27-13-08-07 |
| eClass 9.1: | 27-13-08-07 |
| eClass 10.0: | 27-13-08-07 |
| UNSPSC: | 30-21-19-21 |
| ROHS: | Conform |
| Type: | VSSC6 TRCL24VAC/DC0.5A |
| Order No.: | 1064230000 |
| Version: | Surge protection for instrumentation and control, 24 V, 34 V, 500 mA, IEC 61643-21, HART-compatible |
| GTIN (EAN): | 4032248829590 |
| Qty.: | 10 pc(s). |
| Width: | 6.2 mm |
| Width (inches): | 0.244 inch |
| Height: | 88.5 mm |
| Height (inches): | 3.484 inch |
| Depth: | 81 mm |
| Depth (inches): | 3.189 inch |
| Net weight: | 43.4 g |
| Humidity: | 5...96 % |
| Operating temperature, max.: | 70 °C |
| Operating temperature, min.: | -40 °C |
| Storage temperature, max.: | 80 °C |
| Storage temperature, min.: | -40 °C |
| Operating temperature: | -40 °C...70 °C |
| Storage temperature: | -40 °C...80 °C |
| λges: | 19 |
| MTTF: | 6,008 Years |
| PFH in 1*10-9 per hour: | 1.95 |
| SFF: | 89.74 % |
| SIL in compliance with IEC 61508: | 2 |
| REACH SVHC: | Lead 7439-92-1 |
| Certificate No. (UL): | E311081 |
| Gas group C: | IIB |
| Gas group D: | IIA |
| Gas groups A, B: | IIC |
| Input current, max. II: | 500 mA |
| Input voltage, max. Ui: | 42 V |
| Internal capacity, max. CI: | 1 nF |
| Internal inductance, max. LI: | 0 µH |
| Colour: | black |
| Design: | Terminal |
| Isolating function: | Yes |
| Optical function display: | No |
| Protection degree: | IP20 |
| Rail: | TS 35 |
| Segment: | Measurement - Monitoring - Setting |
| Testing option: | Functional screw with test plug receptacle, connections 1, 2, 4, 5 |
| UL 94 flammability rating: | V-0 |
| Version: | Surge protection for measurement and control |
| Pollution severity: | 2 |
| Surge voltage category: | III |
| Rated voltage (AC): | 24 V |
| Rated voltage (DC): | 34 V |
| Voltage type: | AC/DC |
| Max. continuous voltage, Uc (AC): | 30 V |
| Max. continuous voltage, Uc (DC): | 42 V |
| Discharge current, max. (8/20 µs): | 10 kA |
| Discharge current In (8/20µs) wire-PE: | 2.5 kA |
| Discharge current Imax (8/20µs) wire-PE: | 5 kA |
| Discharge current In (8/20µs) wire-wire: | 2.5 kA |
| Discharge current Imax (8/20µs) wire-wire: | 5 kA |
| Lightning test current Iimp (10/350 µs): | 0.5 kA |
| Lightning test current, Iimp (10/350 µs) Wire–PE: | 0.5 kA |
| Fuse: | 0.5 A |
| Standards: | IEC 61643-21, HART-compatible |
| Protection level UP (typ.): | 900 V |
| Protection level UP for C1 with 500V/250A (wire-PE): | 456 V |
| Protection level UP for C2 with 10kV/5kA (wire-PE): | 960 V |
| Protection level UP for C2 with 10kV/5kA (wire-wire): | 108 V |
| Protection level UP for C3 with 1kV/µs (wire-PE): | 572 V |
| Protection level UP for C3 with 1kV/µs (wire-wire): | 55 V |
| Protection level UP for D1 with 0.5kA (wire-wire): | 94 V |
| Protection level on output side Wire-wire 1 kV/µs, typically: | 70 V |
| Insertion loss: | 250 MHz |
| Number of poles: | 1 |
| Overload - failure mode: | Modus 2 |
| Protection level UP for C1 with 500V/250A (wire-wire): | 62 V |
| Protection level, UP wire - wire: | 90 V |
| Pulse-reset capacity: | ≤ 170 ms |
| Rated current IN: | 500 mA |
| Requirements category acc. to IEC 61643-21: | C2, C3, D1 |
| Signal transmission properties (-3 dB): | 270 Mhz |
| Surge current-carrying capacity C2: | 2.5 kA 8/20 µs 5 kV 1.2/50 µs |
| Surge current-carrying capacity C3: | 50 A 10/1000 μs |
| Surge current-carrying capacity D1: | 0.5 kA 10/350 μs |
| Volume resistance: | 1.8 Ω 10 % |
| Type of connection: | Screw connection |
| Tightening torque, min.: | 0.5 Nm |
| Tightening torque, max.: | 0.8 Nm |
| Clamping range, min.: | 0.5 mm² |
| Clamping range, max.: | 4 mm² |
| Wire cross-section, solid, min.: | 0.5 mm² |
| Wire cross-section, solid, max.: | 6 mm² |
| Conductor cross-section, flexible, AEH (DIN 46228-1), min.: | 0.5 mm² |
| Conductor cross-section, flexible, AEH (DIN 46228-1), max.: | 4 mm² |
| Connection cross-section, stranded, min.: | 0.5 mm² |
| Connection cross-section, stranded, max.: | 4 mm² |
| Long specification: | Surge protection in a one piece, 6.2 mm wide DIN rail module for a floating-ground signal circuit with 24 V UC, 2-wire technology. Each signal path can be opened using an isolator. A current loop with max. 0.6A can be protected here. When the terminal is fitted, a simultaneous electrically conducting contact is made between the mounting rail (earth) and the reference potential (ground) of the protection circuit in the terminal. Optical identification of the terminal based on the type of protected switching and the voltage level. The terminal can be labelled or marked. |
| Short specification: | Surge protection in a one piece, 6.2 mm wide DIN rail module for a floating-ground driven signal circuit with 2-wire technology and a common wire. Each signal path can be opened using an isolator. Version: 24V UC |
| ETIM 6.0: | EC000943 |
| ETIM 7.0: | EC000943 |
| eClass 9.0: | 27-13-08-07 |
| eClass 9.1: | 27-13-08-07 |
| eClass 10.0: | 27-13-08-07 |
| UNSPSC: | 30-21-19-21 |
| ROHS: | Conform |
| ECCN: | |
| Kraj pochodzenia: | |
| EAN: | |
| Waga: | 0,047 kg |
| Długość: | 0,00 m |
| Szerokość: | 0,00 m |
| Wysokość: | 0,00 m |