Phoenix Contact 2901527

EM-RS485-GATEWAY-IFS

For more complex applications with Interface system devices (IFS), the extension module offers digital inputs and outputs for processing additional signals in the field. Easy connection to IFS gateway via the DIN rail connector as the slave. PLC logic set consisting of: plug-in basic logic module (BM2) and eight relay terminal blocks with Push-in connection (1 changeover contact, 250 V AC/DC, max.6 A). Gateway for the connection of up to 32 INTERFACE system devices to a higher-level controller via Modbus/RS-485. The INTERFACE system devices are connected to the Gateway via DIN rail connectors, the DIN rail connectors are provided. PLC logic starter kit 3, consisting of: plug-in stand-alone logic module (SAM 2), eight relay output terminal blocks with Push-in connection (250 V AC/DC, max. 6 A), and micro USB programming cable. Gateway for the connection of up to 32 INTERFACE system devices to a higher-level controller via PROFIBUS DP. The INTERFACE system devices are connected to the Gateway via DIN rail connectors, the DIN rail connectors are provided. Connecting cable, for connecting the controller to a PC for PC Worx and LOGIC+, USB A to micro USB B, 2 m in length. Gateway for the connection of up to 32 INTERFACE system devices to a higher-level controller via EtherNet/IP™. The INTERFACE system devices are connected to the Gateway via DIN rail connectors, the DIN rail connectors are provided. Multi-functional memory block for the INTERFACE systemf for easy storage and backup of the configuration. Gateway for the connection of up to 32 INTERFACE system devices via PROFINET to a higher-level controller. The INTERFACE system devices are connected to the Gateway via DIN rail connectors, the DIN rail connectors are provided. Gateway for the connection of up to 32 INTERFACE system devices to a higher-level controller via CANopen. The INTERFACE system devices are connected to the Gateway via DIN rail connectors, the DIN rail connectors are provided. Gateway for the connection of up to 32 INTERFACE system devices via Modbus/TCP to a higher-level controller. The INTERFACE system devices are connected to the Gateway via DIN rail connectors, the DIN rail connectors are provided. Configuration package for the EMM .. IFS, comprising CONTACTRON-DTM-IFS, USB programming adapter, and user manual on CD. Multi-functional memory block with handle for the INTERFACE system; for easy storage and back up of the configuration. The voltage transducer set makes it possible to insert the electronic motor management module (EMM 3-.../500AC-IFS) in 690 V mains.

Na prośbę. Prześlij nam wiadomość e-mail z zapytaniem o cenę i dostępność.
"ucnguBrctvdgcxgt0eqo"

Opis

Parametry techniczne

Width: 22.5 mm
Height: 99 mm
Depth: 114.5 mm
Ambient temperature (operation): -25 °C ... 50 °C
Ambient temperature (storage/transport): -35 °C ... 80 °C
Degree of protection: IP20
Rated control circuit supply voltage US: 24 V DC -20 % ... +25 %
Rated control supply current IS: 85 mA (plus load current of the outputs)
Protective circuit: Reverse polarity protection
Number: 8
Rated actuating voltage UC: 24 V DC ±20 %
Rated actuating current IC: 3 mA
Protective circuit: Reverse polarity protection
Designation: Switching outputs
Number: 4
Residual voltage: 1 V
Maximum switching voltage: 23 V DC (UB - Uresid. of the output)
Max. switching current: 500 mA
Protective circuit: Parallel protection against polarity reversal, pay attention to the fuse Fusing with max. 8 A F-fuse
Operating mode: 100% operating factor
Mounting position: any
Assembly instructions: In rows with zero spacing
Mounting type: DIN rail mounting
Housing material: Polyamide PA non-reinforced
Color: green
Interface 1: Interface-System
Serial transmission speed: 76.8 kbps
Connection method: DIN rail bus connectors
Interface 2: RS-485
Serial transmission speed: 9.6 k ... 115 kbaud
Connection method: MSTB plug entry
Connection name: Supply
Connection method: Screw connection
Stripping length: 8 mm
Screw thread: M3
Conductor cross section solid: 0.2 mm² ... 2 mm²
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross section AWG: 24 ... 12
Connection name: Programming connection
Connection method: S-PORT (socket)
Number of connections: 1
Number of positions: 12
Connection name: INTERFACE system
Connection method: DIN rail bus connectors
Number of connections: 1
Number of positions: 5
Connection name: RS-485
Connection method: Screw connection
Number of connections: 1
Number of positions: 5
Standards/regulations: EN 50178
Pollution degree: 2
Overvoltage category: III
REACh SVHC: Lead 7439-92-1
China RoHS: Environmentally Friendly Use Period = 50 years
eCl@ss 10.0.1: 27242608
eCl@ss 4.0: 27371100
eCl@ss 4.1: 27371100
eCl@ss 5.0: 27371600
eCl@ss 5.1: 27371600
eCl@ss 6.0: 27242600
eCl@ss 7.0: 27242608
eCl@ss 8.0: 27242608
eCl@ss 9.0: 27242608
ETIM 3.0: EC001604
ETIM 4.0: EC001604
ETIM 5.0: EC001604
ETIM 6.0: EC001604
ETIM 7.0: EC001604
UNSPSC 6.01: 30211915
UNSPSC 7.0901: 39121514
UNSPSC 11: 39121514
UNSPSC 12.01: 39121514
UNSPSC 13.2: 32151602
UNSPSC 18.0: 32151602
UNSPSC 19.0: 32151602
UNSPSC 20.0: 32151602
UNSPSC 21.0: 32151602

Parametry logistyczne

ECCN:
Kraj pochodzenia: DE
EAN:
Waga: 0,00 kg
Długość: 0,00 m
Szerokość: 0,00 m