Pepperl+Fuchs 282276

FB2217E3

Digital Output with Position Feedback

Na prośbę. Prześlij nam wiadomość e-mail z zapytaniem o cenę i dostępność.
"ucnguBrctvdgcxgt0eqo"

Opis

1-channel, 1 digital output, 2 digital inputs, Inputs and output Ex ia, Installation in suitable enclosures in Zone 1pa. The digital output features 1 output with 2 feedback inputs. The device can be used to switch solenoids, sounders, or indicators (without line fault detection) in the field. Furthermore, the device accepts digital input signals of NAMUR sensors or mechanical contacts from the field. The output can be switched off via a contact. This can be used for bus-independent safety applications. Open and short circuit line faults are detected in on and off state. The intrinsically safe inputs and the output are galvanically isolated from the bus and the power supply.

Parametry techniczne

Occupied slots: 1
Connection: backplane bus / booster terminals
Rated voltage: Use only in connection with the power supplies FB92**
Power dissipation: 1.3 W
Power consumption: 1.85 W
Connection: backplane bus
Interface: manufacturer-specific bus to standard com unit
Number of channels: 2
Sensor interface: Connection: NAMUR sensor
Sensor interface: Connection [2]: volt-free contact
Connection: channel I: 2+, 5-; channel II: 3+, 6-
Rated values: acc. to EN 60947-5-6 (NAMUR)
Switching point/switching hysteresis: 1.2 ... 2.1 mA / ± 0.2 mA
Internal resistor: 1 kΩ
Line fault detection: can be switched on/off for each channel via configuration tool
Sensor interface: Connection: mechanical switch with additional resistors (see connection diagram) proximity switches without additional wiring
Sensor interface: Short-circuit: < 360 Ω
Sensor interface: Open-circuit: < 0.35 mA
Minimum pulse duration: 1 ms
Number of channels: 1
Suitable field devices: Field device: Solenoid Valve
Suitable field devices: Field device [2]: audible alarm
Suitable field devices: Field device [3]: visual alarm
Connection: channel I: 1+, 4-
Open loop voltage: 16.5 V
Current limit: 50 mA
Internal resistor: 131 Ω
Line fault detection: can be switched on/off for each channel via configuration tool , also when turned off (every 2.5 s the valve is turned on for 2 ms)
Suitable field devices: Short-circuit: < 50 Ω
Suitable field devices: Open-circuit: > 10 kΩ
Response time: 10 ms (depending on bus cycle time)
Watchdog: within 0.5 s the device goes in safe state, e.g. after loss of communication
LED indication: Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (O: output, I1: input 1, I2: input 2) red: line fault (lead breakage or short circuit) , yellow: state of digital I/O (0/1)
Coding: optional mechanical coding via front socket
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1
Electromagnetic compatibility: NE 21
Degree of protection: IEC 60529
Environmental test: EN 60068-2-14
Shock resistance: EN 60068-2-27
Vibration resistance: EN 60068-2-6
Damaging gas: EN 60068-2-42
Relative humidity: EN 60068-2-56
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Relative humidity: 95 % non-condensing
Shock resistance: shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistance: frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gas: designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Degree of protection: IP20 (module) , a separate housing is required acc. to the system description
Connection: removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Mass: approx. 750 g
Dimensions: 28 x 107 x 132 mm (1.1 x 4.2 x 5.2 inch)
EU-type examination certificate: Presafe 19 ATEX 14054U
Electromagnetic compatibility: Marking: II 2(1)G Ex db eb q [ia Ga] IIC Gb II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
Input: Voltage: 10 V
Input: Current: 13 mA
Input: Power: 33 mW (linear characteristic)
Input: Internal capacitance: 1.2 nF
Input: Internal inductance: 0 mH
Output: Voltage: 17.8 V
Output: Current: 162 mA
Output: Power: 721 mW
Output: Internal capacitance: 12 nF
Output: Internal inductance: 0 mH
Galvanic isolation: Input/power supply, internal bus: safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V
Galvanic isolation: Output/power supply, internal bus: safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 EN 60079-1:2014 EN 60079-5:2015 EN 60079-7:2015 EN 60079-11:2012
ATEX approval: Presafe 19 ATEX 14054U
IECEx approval: IECEx PRE 19.0009U
Directive conformity: Approved for: Ex db eb q [ia Ga] IIC Gb [Ex ia Da] IIIC [Ex ia Ma] I
System information: The module has to be mounted in appropriate backplanes and housings (FB92**) in Zone 1, 2, 21, 22 or outside hazardous areas (gas or dust). Here, observe the corresponding EC-type examination certificate.
Supplementary information: EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Parametry logistyczne

ECCN:
Kraj pochodzenia: DE
EAN:
Waga: 0,00 kg
Długość: 0,00 m
Szerokość: 0,00 m
Wysokość: 0,00 m