Pepperl+Fuchs 263812

VBA-4E-KE5-ZEJQ

AS-Interface sensor/actuator module

Na prośbę. Prześlij nam wiadomość e-mail z zapytaniem o cenę i dostępność.
"ucnguBrctvdgcxgt0eqo"

Opis

Cabinet module. 4 inputs (PNP)fa. The AS-Interface connecting module VBA-4E-KE5-ZEJQ is a switch cabinet module with 4 inputs and. The housing is only 19 mm wide and takes up little space in the switch cabinet. The module is mounted by snapping onto the 35 mm DIN rail in compliance with EN 50022. The connection is made via removable 4-pin push-in terminal blocks. For AS-i+ and AS-i-, two connections are available in each case; these connections are bridged in the terminal block. If the terminal block is disconnected from the module, the link between these connections is retained. The terminal blocks are mechanically coded. The supply to the inputs and the connected sensors can be fed either from the internal supply of the module from the AS-Interface or via an external UEXT voltage source. A switch located on the side of the module changes the source. The internal input supply is displayed via the INT LED. The relevant IN LEDs display the current switching status of the inputs. Notes:. Filters that suppress pulses with a duration of 2 ms or less at the inputs can be connected via the parameter P1. Parameter P2 activates the synchronous mode. A signal indicating an overload of the internal input supply is transmitted to the AS-Interface master via the 'peripheral fault' function. Communication via the AS-Interface continues even if a peripheral fault is set.

Parametry techniczne

Slave type: A/B slave
AS-Interface specification: V3.0
Required master specification: ≥ V3.0
UL File Number: E223772
MTBF: 368 a
LED FAULT: Fault display; Red LED red: Communication fault or address is 0 red, flashing: Overload, internal input supply
LED INT: Internal input supply active; LED green
LED PWR: AS-Interface voltage; green LED green: voltage OK flashing green: address 0
LED IN: switching state (input); 4 LED yellow
Auxiliary voltage (input): 12 ... 30 V DC PELV
Rated operating voltage: 26.5 ... 31.6 V from AS-Interface
Rated operating current: ≤ 35 mA (without sensors) / max. 190 mA
Protection class: III
Surge protection: UEXT, Ue: Over voltage category III, safe isolated power supplies (PELV)
Number/Type: 4 inputs for 3-wire sensors (PNP), DC
Supply: from AS-Interface (switch position INT, default settings) or external UEXT (switch position EXT)
Voltage: 21 ... 31 V DC (INT)
Current loading capacity: ≤ 150 mA, overload- and short-circuit protected (INT)
Input current: ≤ 5.6 mA (max.)
Switching point: according to DIN EN 61131-2 (type 1)
: 0 (unattenuated): ≤ 0.5 mA
: 1 (attenuated): ≥ 2 mA
Signal delay: < 1 ms (input/AS-Interface)
Electromagnetic compatibility: Directive 2014/30/EU: EN 62026-2:2013
Degree of protection: EN 60529:2000
Fieldbus standard: EN 62026-2:2013
Input: EN 61131-2:2004
Emitted interference: EN 61000-6-4:2007
AS-Interface: EN 62026-2:2013
Noise immunity: EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013
Profile: S-0.A.0
IO code: 0
ID code: A
ID1 code: 7
ID2 code: 0
Data bits (function via AS-Interface): input output
Electromagnetic compatibility: D0: IN1
Electromagnetic compatibility: D1: IN2
Electromagnetic compatibility: D2: IN3
Electromagnetic compatibility: D3: IN4
Parameter bits (programmable via AS-i): function
Electromagnetic compatibility: P0: not used
Electromagnetic compatibility: P1: Input filter P1 = 0 input filter on, pulse suppression ≤ 2 ms P1 = 1 input filter off (default settings)
Electromagnetic compatibility: P2: Synchronous mode P2 = 0 synchronous mode on P2 = 1 synchronous mode off (default settings)
Electromagnetic compatibility: P3: not used
Ambient temperature: -25 ... 70 °C (-13 ... 158 °F)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Relative humidity: 85 % , noncondensing
Climatic conditions: For indoor use only
Altitude: ≤ 2000 m above MSL
Shock and impact resistance: 15 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks
Vibration resistance: 0.35 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles
Pollution degree: 2
Degree of protection: IP20 For safety applications: Installation in an enclosure with a minimum protection class of IP54 required
Connection: Removable push-in terminals rated connection capacity: rigid: 0.20 mm2 ... 1.5 mm2 flexible (without wire end ferrule): 0.20 mm2 ... 2.5 mm2 flexible (with wire end ferrule): 0.25 mm2 ... 1.5 mm2
Material: Housing: PA 66-FR
Mass: 110 g
Mounting: DIN mounting rail

Parametry logistyczne

ECCN:
Kraj pochodzenia: SG
EAN:
Waga: 0,00 kg
Długość: 0,00 m
Szerokość: 0,00 m