Pepperl+Fuchs 262113

KFD2-SR3-2.2S

Switch Amplifier

Na prośbę. Prześlij nam wiadomość e-mail z zapytaniem o cenę i dostępność.
"ucnguBrctvdgcxgt0eqo"

Opis

2-channel signal conditioner, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Usable as signal splitter (1 input and 2 outputs), 2 x 2 relay contact outputs with AND logic, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 acc. to IEC 61508/IEC 61511pa. This signal conditioner provides the galvanic isolation between field circuits and control circuits. The device transfers digital signals (NAMUR sensors or dry contacts) from the field to the control system. Each input controls a relay contact output. Via switches the mode of operation can be reversed and the line fault detection can be switched off. A fault is signalized by LEDs acc. to NAMUR NE44 and a separate collective error message output.

Parametry techniczne

Signal type: Digital Input
Safety Integrity Level (SIL): SIL 2
Connection: Power Rail or terminals 14+, 15-
Rated voltage: 19 ... 30 V DC
Ripple: ≤ 10 %
Rated current: 30 ... 20 mA
Power consumption: < 600 mW
Connection side: field side
Connection: terminals 1+, 2+, 3-; 4+, 5+, 6-
Rated values: acc. to EN 60947-5-6 (NAMUR)
Open circuit voltage/short-circuit current: approx. 10 V DC / approx. 8 mA
Switching point/switching hysteresis: 1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detection: breakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA
Pulse/Pause ratio: min. 20 ms / min. 20 ms
Connection side: control side
Connection: output I: terminals 7, 8 ; output II: terminals 8, 9 ; output III: terminals 10, 11 ; output IV: terminals 11, 12
Output I, II, III, IV: channel 1, 2; relay
Contact loading: 48 V AC/1 A/cos φ > 0.7; 40 V DC/1 A resistive load
Minimum switch current: 1 mA / 24 V DC
Energized/De-energized delay: approx. 20 ms / approx. 20 ms
Mechanical life: 108 switching cycles
Collective error message: Power Rail
Switching frequency: ≤ 10 Hz
Input/Output: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supply: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/power supply: basic insulation according to IEC/EN 61010-1, rated insulation voltage 32 Veff , functional insulation, rated insulation voltage 50 Veff
Output/Output: basic insulation according to IEC/EN 61010-1, rated insulation voltage 32 Veff , functional insulation, rated insulation voltage 50 Veff
Display elements: LEDs
Control elements: DIP-switch
Configuration: via DIP switches
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Electromagnetic compatibility: NE 21:2012 , EN 61326-3-2:2008
Degree of protection: IEC 60529:2001
Input: EN 60947-5-6:2000
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Degree of protection: IP20
Connection: screw terminals
Mass: approx. 150 g
Dimensions: 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001
Certificate: PF 16 CERT 3903 X
Electromagnetic compatibility: Marking: II 3G Ex nA nC IIC T4 Gc
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-15:2010
UL approval: E106378
IECEx approval: IECEx certificate: IECEx EXA 16.0001X
IECEx approval: IECEx marking: Ex nA nC IIC T4 Gc
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Optional accessories: - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-GY(-UPR-03)

Parametry logistyczne

ECCN:
Kraj pochodzenia: SG
EAN:
Waga: 0,00 kg
Długość: 0,00 m
Szerokość: 0,00 m
Wysokość: 0,00 m