Pepperl+Fuchs 262106

KFD2-SOT3-Ex1.LB

Switch Amplifier

Na prośbę. Prześlij nam wiadomość e-mail z zapytaniem o cenę i dostępność.
"ucnguBrctvdgcxgt0eqo"

Opis

1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Passive transistor output, non-polarized, Passive fault output, non-polarized, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 acc. to IEC 61508pa. This isolated barrier is used for intrinsic safety applications. The device transfers digital signals (NAMUR sensors or dry contacts) from a hazardous area to a safe area. The input controls two passive transistor outputs. Via switches the mode of operation can be reversed and the line fault detection can be switched off. Via switch the function of the second output can be defined as a signal output or a fault indication output. A fault is signalized by LEDs acc. to NAMUR NE44 and a separate collective error message output.

Parametry techniczne

Signal type: Digital Input
Safety Integrity Level (SIL): SIL 2
Connection: Power Rail or terminals 14+, 15-
Rated voltage: 19 ... 30 V DC
Ripple: ≤ 10 %
Rated current: 20 ... 15 mA
Power dissipation: ≤ 1 W including maximum power dissipation in the output
Connection side: field side
Connection: terminals 1+, 2+, 3-
Rated values: acc. to EN 60947-5-6 (NAMUR), see system description for electrical data
Open circuit voltage/short-circuit current: approx. 10 V DC / approx. 8 mA
Switching point/switching hysteresis: 1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detection: breakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA
Pulse/Pause ratio: min. 100 µs / min. 100 µs
Connection side: control side
Connection: output I: terminals 7, 8 ; output II: terminals 8, 9
Rated voltage: 30 V DC
Rated current: 100 mA , short-circuit protected
Response time: ≤ 200 µs
Signal level: 1-signal: (external voltage) - 3 V max. for 100 mA 0-signal: blocked output (off-state current ≤ 10 µA)
Output I: signal ; Transistor
Output II: signal or error message ; Transistor
Collective error message: Power Rail
Switching frequency: ≤ 5 kHz
Input/Output: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supply: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/power supply: basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Display elements: LEDs
Control elements: DIP-switch
Configuration: via DIP switches
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Electromagnetic compatibility: NE 21:2012 , EN 61326-3-2:2008
Degree of protection: IEC 60529:2001
Input: EN 60947-5-6:2000
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Degree of protection: IP20
Connection: screw terminals
Mass: approx. 150 g
Dimensions: 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001
EU-type examination certificate: EXA 16 ATEX 0016 X
Electromagnetic compatibility: Marking: II 3(1)G Ex nA [ia Ga] IIC T4 Gc II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
Electromagnetic compatibility: Input: Ex ia
Electromagnetic compatibility: Voltage: 10.5 V
Electromagnetic compatibility: Current: 17.1 mA
Electromagnetic compatibility: Power: 45 mW (linear characteristic)
Supply: Maximum safe voltage: 253 V AC (Attention! Um is no rated voltage.)
Output: Maximum safe voltage: 253 V AC (Attention! The rated voltage can be lower.)
Galvanic isolation: Input/Output: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Galvanic isolation: Input/power supply: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
UL approval: E106378
Directive conformity: Control drawing: 116-0424 (cULus)
IECEx approval: IECEx certificate: IECEx EXA 16.0009X
IECEx approval: IECEx marking: Ex nA [ia Ga] IIC T4 Gc , [Ex ia Da] IIIC , [Ex ia Ma] I
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Optional accessories: power feed module KFD2-EB2 Universal Power Rail UPR-03 Universal Power Rail UPR-03-S profile rail K-DUCT-BU profile rail K-DUCT-UPR-03

Parametry logistyczne

ECCN:
Kraj pochodzenia: SG
EAN:
Waga: 0,00 kg
Długość: 0,00 m
Szerokość: 0,00 m
Wysokość: 0,00 m