Pepperl+Fuchs 258077

KCD2-RR-EX1.SP

Resistance Repeater

Na prośbę. Prześlij nam wiadomość e-mail z zapytaniem o cenę i dostępność.
"ucnguBrctvdgcxgt0eqo"

Opis

This isolated barrier is used for intrinsic safety applications. 1-channel isolated barrier, 24 V DC supply (Power Rail), Resistance and RTD input (Pt100, Pt500, Pt1000), Resistance output, Accuracy 0.1 %, Line fault detection (LFD) for Pt100, Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the control systempa. It transfers resistance values of RTDs or potentiometers from hazardous areas to safe areas. A 2-, 3-, or 4-wire technique is available depending on the required accuracy. The input card of the control system measures the same load as if it were connected directly to the resistance in a hazardous area.

Parametry techniczne

Signal type: Analog input
Safety Integrity Level (SIL): SIL 2
Connection: Power Rail or terminals 9+, 10-
Rated voltage: 19 ... 30 V DC
Ripple: within the supply tolerance
Rated current: < 20 mA
Power consumption: 0.35 W (24 V and 1 mA sense current)
Connection side: field side
Connection: terminals 1, 2, 3, 4
Line fault detection: yes , at Pt100
Lead resistance: ≤ 10 % of resistance value
Transmission range: 0 ... 10 mA
Available voltage: 9 V
Line fault detection: 8 nA
Connection side: control side
Connection: terminals 5-, 7-, 6+, 8+
Current: 0 ... 10 mA
Available voltage: 0 ... 4.2 V
Fault signal: < 10 Ω or > 400 Ω, depending on lead disconnected (measuring current ≤ 1 mA) > 400 Ω, terminal 3 lead disconnected in 2-/4-wire (measuring current ≤ 0.3 mA)
Accuracy: 0.1 %
Deviation: Im ≥ 1 mA: ±0.1 % of Rm or ± 0.1 Ω (the larger value is applicable) Im < 1 mA: accuracy reduces in proportion to Im. e. g. Im = 0.1 mA: ± 1 % of Rm or 1 Ω (the larger value is applicable).
: Influence of ambient temperature: Im ≥ 1 mA, Rm ≥ 100 Ω : 0.01 %/K in the range -20 ... +60 °C (253 ... 333 K) Im < 1 mA or Rm < 100 Ω: temperature stability reduces in proportion to Im or Rm
Rise time: signal response time ≤ 2 ms (10 ... 90 %) response to application of Im: Rm > 50 Ω and Im < 5mA: < 5ms response to application of Im: Rm > 30 Ω and Im < 5mA: < 10ms response to application of Im: Rm > 18 Ω and Im < 5mA: < 20ms
Input/Output: reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
Input/power supply: reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
Output/power supply: functional insulation, rated insulation voltage 50 V AC
Display elements: LED
Control elements: DIP-switch
Configuration: via DIP switches
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Electromagnetic compatibility: NE 21:2011
Degree of protection: IEC 60529:2001
Protection against electrical shock: UL 61010-1
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Degree of protection: IP20
Connection: spring terminals
Mass: approx. 100 g
Dimensions: 12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 inch) , housing type A2
Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001
EU-type examination certificate: BASEEFA 10 ATEX 0061
Electromagnetic compatibility: Marking: II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
Electromagnetic compatibility: Input: [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Electromagnetic compatibility: Voltage: 12.4 V
Electromagnetic compatibility: Current: 17.4 mA
Electromagnetic compatibility: Power: 54 mW
Supply: Maximum safe voltage: 253 V (Attention! The rated voltage can be lower.)
Output: Maximum safe voltage: 253 V (Attention! The rated voltage can be lower.)
Certificate: BASEEFA 10 ATEX 0062X
Output: Marking: II 3G Ex ec IIC T4 Gc
Galvanic isolation: Input/Output: safe electrical isolation acc. to IEC/EN 60079-11:2012, voltage peak value 375 V
Galvanic isolation: Input/power supply: safe electrical isolation acc. to IEC/EN 60079-11:2012, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN IEC 60079-0:2018 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012
FM approval: Control drawing: 116-0129 (cFMus)
UL approval: Control drawing: 116-0332 (cULus)
IECEx approval: IECEx certificate: IECEx BAS 10.0024 IECEx BAS 10.0025X
IECEx approval: IECEx marking: [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Optional accessories: - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-BU(-UPR-03) - insertion bridge EBP 2- 5

Parametry logistyczne

ECCN:
Kraj pochodzenia: Singapur
EAN: 4050143064878
Waga: 0,14 kg
Długość: 0,00 m
Szerokość: 0,00 m
Wysokość: 0,00 m