Pepperl+Fuchs 256922

M-LB-EX-5214

Protection Module

Na prośbę. Prześlij nam wiadomość e-mail z zapytaniem o cenę i dostępność.
"ucnguBrctvdgcxgt0eqo"

Opis

Surge protection for 2 signal lines, Nominal voltage 1 V DC, Protection module for grounded signal lines, Max. surge current (8/20 µs) 20 kA, Uninterruptable operation (auto reset), Status indication output, Mounting on base module, pluggable, Up to SIL 3 acc. to IEC 61508pa. The protection module limits induced transients of different causes, e. g. lightning or switching operations. The limitation is achieved by diverting the current to earth and limiting the signal circuit voltage during the duration of the overvoltage pulse. The device has LEDs for the status indication. If required, this status is transferred to the corresponding function module via a status indication output. The device is HART transparent. The device is inserted onto the base module and forms the surge protection barrier together with the base module. The device can be replaced without tools by a locking lever.

Parametry techniczne

Number of protected signal lines: 2
Topology: grounded
Safety Integrity Level (SIL): SIL 3
Connection: via Universal Power Rail M-UPR-03-S
Nominal voltage: see power feed module M-LB-5300
Current: ≤ 8 mA
Connection: protected area: terminals 3, 4 unprotected area: terminals 1, 2
Rated current: 500 mA , restrictions see derating characteristics
Leakage current: < 10 µA at 1 V and 25 °C (77 °F) , line-line
Nominal voltage: 1 V DC
Maximum continuous operating voltage: 6 V DC
Series resistance: ≤ 0.6 Ω per line
Impulse rating: 1 kV/0.5 kA (category C1) 10 kV/5 kA (category C2) 1 kA (category D1)
Impulse discharge current (10/350 µs): 1 kA per line (2x)
Nominal discharge current (8/20 µs): 5 kA per line (10x)
Rated surge current (8/20 µs): 10 kA per line (1x)
Total discharge current (8/20 µs): 20 kA (1x)
Voltage protection level: max. 12 V line-line for nominal discharge current In max. 31 V line-earth for nominal discharge current In
Impulse reset time: < 500 ms
Insertion loss: ≤ 0.05 dB, at 0 ... 4 kHz, in 600 Ω-System ≤ 3 dB, at 0 ... 350 kHz, in 100 Ω-System
Status indication: fault and maintenance signal via Universal Power Rail M-UPR-03-S
Signal lines/fault indication output: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Signal lines/power supply: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Display elements: LED PWR (power supply), green LED LED FLT (fault signal), red LED LED CHK (maintenance signal), yellow LED
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Degree of protection: IEC 60529:2013
Functional safety: IEC/EN 61508:2010
Surge protective devices for low voltage: EN 61643-21:2001+A1:2009+A2:2013 IEC 61643-21:2001+A1:2008+A2:2012
Ambient temperature: -40 ... 60 °C (-40 ... 140 °F) Observe the temperature range limited by derating, see section derating.
Storage temperature: -40 ... 85 °C (-40 ... 185 °F)
Relative humidity: max. 95 % , without condensation
Degree of protection: IP20
Mass: approx. 20 g
Dimensions: 6.2 x 77 x 79 mm
Mounting: pluggable in base module for mounting on 35 mm DIN mounting rail
EU-type examination certificate: BVS 17 ATEX E 069 X
Electromagnetic compatibility: Marking: II 3(1)G Ex ec [ia Ga] IIC T4 Gc II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
Electromagnetic compatibility: Voltage: 6 V
Electromagnetic compatibility: Current: 500 mA , restrictions see derating characteristics
Electromagnetic compatibility: Internal capacitance: negligible
Electromagnetic compatibility: Internal inductance: 36 µH
Supply: Maximum safe voltage: 60 V AC/DC (Attention! The rated voltage can be lower.)
Fault indication output: Maximum safe voltage: 60 V AC/DC (Attention! The rated voltage can be lower.)
Galvanic isolation: Signal lines/fault indication output: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Galvanic isolation: Signal lines/power supply: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-7:2015 , EN 60079-11:2012
IECEx approval: IECEx certificate: IECEx BVS 17.0061X
IECEx approval: IECEx marking: Ex ec [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Designation: system components: - base module with screw terminals M-LB-Ex-5000 - base module with spring terminals M-LB-Ex-5000.SP - power feed module M-LB-5300 - fault status module M-LB-5400 - maintenance status module M-LB-5500 - universal power rail M-UPR-03-S - place holder module M-LB-Ex-5900 - separation wall M-UPR-I

Parametry logistyczne

ECCN:
Kraj pochodzenia: Singapur
EAN: 4050143064502
Waga: 0,03 kg
Długość: 0,00 m
Szerokość: 0,00 m
Wysokość: 0,00 m