256889
HICTB16-SDC-44C-SC-RA
Termination Board
The termination board has 16 plugin slots for isolators. Any isolator can be inserted into any slot, enabling a mixture of I/O types on one termination board. For 16 modules, 24 V DC supply, Supported signal types: DI/DO/AI/TI/AO, Hazardous area: screw terminals, blue, Safe area: Sub-D connector (male), 37-pinpa. The termination board features fixed screw terminals for the field side connection and 37-pin Sub- D connectors for the control side connection along with a HART cordset for interconnection to a separate HART Communication Board. Information about missing supply voltage of the isolators is available for the system as volt-free contact at the redundant power supply terminals. Wiring errors from field side will be reported via the same relay contact, if this function supported by the the isolators. The termination board is supplied with a robust plastic housing as standard. This design permits the fast and reliable installation on 35 mm DIN mounting rail acc. to EN 60715 in the cabinet.
| Connection: | X20: terminals 3, 5 (+); 4, 6 (-) |
| Nominal voltage: | 24 V DC , in consideration of rated voltage of used isolators |
| Voltage drop: | 0.9 V , voltage drop across the series diode on the termination board must be considered |
| Ripple: | ≤ 10 % |
| Fusing: | 4 A , in each case for 16 modules |
| Power dissipation: | ≤ 500 mW , without modules |
| Reverse polarity protection: | yes |
| Supply: | Redundancy available. The supply for the isolators is decoupled, monitored and fused. |
| Connection: | X20: terminals 1, 2 |
| Output type: | volt-free contact |
| Contact loading: | 30 V DC, 1 A |
| Display elements: | LED PWR1 (Termination Board power supply), green LED LED PWR2 (Termination Board power supply), green LED LED FAULT (fault indication), red LED - LED lits: module failure - LED flashes: power supply failure |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1:2013 (industrial locations) |
| Electromagnetic compatibility: | NE 21:2012 For further information see system description. |
| Degree of protection: | IEC 60529:2001 |
| Ambient temperature: | -20 ... 60 °C (-4 ... 140 °F) |
| Storage temperature: | -40 ... 70 °C (-40 ... 158 °F) |
| Degree of protection: | IP20 |
| Connection: Field side: | explosion hazardous area: 4 screw terminals per module , blue |
| Connection: Control side: | non-explosion hazardous area: 2 37-pin Sub-D connector |
| Connection: Supply: | pluggable screw terminals , black |
| Core cross-section: | screw terminals: 0.25 ... 1.5 mm2 (24 ... 12 AWG) |
| Material: | housing: polycarbonate, 10 % glass fiber reinforced |
| Mass: | approx. 760 g |
| Dimensions: | 216 x 200 x 163 mm (8.5 x 7.9 x 6.42 inch) , height including module assembly |
| Mounting: | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| EU-Type Examination Certificate: | CESI 06 ATEX 022 |
| Connection: Marking: | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
| Safe area: Maximum safe voltage: | 250 V (Attention! Um is no rated voltage.) |
| Galvanic isolation: Field circuit/control circuit: | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Directive conformity: Directive 2014/34/EU: | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 50303:2000 |
| UL approval: Control drawing: | 116-0327 |
| IECEx approval: | IECEx CES 06.0003 |
| UL approval: Approved for: | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I |
| ECCN: | |
| Kraj pochodzenia: | Singapur |
| EAN: | 4050143074877 |
| Waga: | 0,91 kg |
| Długość: | 0,00 m |
| Szerokość: | 0,00 m |
| Wysokość: | 0,00 m |