Opis

The function of the Termination Board as well as the connector pin assignment exactly fit the requirement of DeltaV Traditional I/O systems. System board for Emerson DeltaV, For two 8-channel AI/AO/DO cards via 16-pin Mass Termination Block, For four 8-channel DI cards via 16-pin Mass Termination Block, For 8 modules/16 or 32 channels, Recommended modules: HiD2030SK (AI), HiD2038 (AO), HiD2824 (DI), HiD2844 (DI), HiD2872 (DO), Volt-free fault indication output, 24 V DC supply, Hazardous area: screw terminals, blue, Non-hazardous area: IDC connector, 16-pinpa. Information about missing supply voltage of the interface modules is available for the system as potential-free contact. Wiring errors from field will be reported via the same relay contact if the interface module supports this function. The Termination Boards are supplied with a robust glass fiber reinforced plastic housing as standard. This design permits the fast and reliable installation on 35 mm DIN mounting rail acc. to EN 60715 in the cabinet.

Parametry techniczne

Connection: X20: terminals 3, 5(+); 4, 6(-)
Nominal voltage: 24 V DC , in consideration of rated voltage of used isolators
Voltage drop: 0.9 V , voltage drop across the series diode on the termination board must be considered
Ripple: ≤ 10 %
Fusing: 2 A , in each case for 8 modules
Power dissipation: ≤ 500 mW , without modules
Reverse polarity protection: yes
Supply: Redundancy available. The supply for the isolators is decoupled, monitored and fused.
Connection: X20: terminals 1, 2
Output type: volt-free contact
Contact loading: 30 V DC , 1 A
Display elements: LEDs PWR ON (Termination Board power supply) - LED power supply I, green LED - LED power supply II, green LED LED FAULT (fault indication), red LED - LED lits: module failure - LED flashes: power supply failure
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Electromagnetic compatibility: NE 21:2012 For further information see system description.
Degree of protection: IEC 60529:2001
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Storage temperature: -40 ... 70 °C (-40 ... 158 °F)
Degree of protection: IP20
Connection: Field side: explosion hazardous area: screw terminals , blue
Connection: Control side: non-explosion hazardous area: IDC plug, 16-pin
Connection: Supply: pluggable screw terminals , black
Connection: Fault output: pluggable screw terminals , black
Core cross-section: screw terminals: 0.2 ... 2.5 mm2 (24 ... 12 AWG)
Material: housing: polycarbonate, 10 % glass fiber reinforced
Mass: approx. 600 g
Dimensions: 150 x 200 x 163 mm (5.9 x 7.9 x 6.42 inch) , height including module assembly
Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001
EU-type examination certificate: CESI 11 ATEX 062
Connection: Marking: II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
Non-hazardous area: Maximum safe voltage: 250 V (Attention! Um is no rated voltage.)
Galvanic isolation: Field circuit/control circuit: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 50303:2000
CSA approval: Control drawing: see control drawing of correspoding modules
IECEx approval: IECEx CES 11.0022
CSA approval: Approved for: [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.