Opis

15-channel, Active digital signal 24 V DC, Installation in Zone 2 or safe area, Positive or negative logic selectablepa. The device accepts 24 V status information from the field. The inputs are galvanically isolated from the bus and the power supply (EN 60079-11).

Parametry techniczne

Occupied slots: 2
Connection: backplane bus
Rated voltage: 12 V DC , only in connection with the power supplies LB9***
Power dissipation: 0.6 W
Power consumption: 0.6 W
Connection: backplane bus
Interface: manufacturer-specific bus to standard com unit
Input resistance: 10 kΩ
Number of channels: 15
Connection: channel I: 1+, 16-; channel II: 2+, 16-; channel III: 3+, 16-; channel IV: 4+, 16-; channel V: 5+, 16-; channel VI: 6+, 16-; channel VII: 7+, 16-; channel VIII: 8+, 16-; channel IX: 9+, 16-; channel X: 10+, 16-; channel XI: 11+, 16-; channel XII: 12+, 16-; channel XIII: 13+, 16-; channel XIV: 14+, 16-; channel XV: 15+, 16-
Digital signals (active): DC 24 V (30 V max.)
: Switching point: ON: < 12 V
: Switching point: OFF: > 2 V
Minimum pulse duration: 40 ms
LED indication: Power LED (P) green: supply Status LED (I) red: communication error
Coding: optional mechanical coding via front socket
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1
Electromagnetic compatibility: NE 21
Degree of protection: IEC 60529
Environmental test: EN 60068-2-14
Shock resistance: EN 60068-2-27
Vibration resistance: EN 60068-2-6
Damaging gas: EN 60068-2-42
Relative humidity: EN 60068-2-56
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Relative humidity: 95 % non-condensing
Shock resistance: shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistance: frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gas: designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Degree of protection: IP20 when mounted on backplane
Connection: removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Mass: approx. 130 g
Dimensions: 32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch)
Certificate: PF 08 CERT 1234 X
Electromagnetic compatibility: Marking: II 3 G Ex nA IIC T4 Gc
Galvanic isolation: Input/power supply, internal bus: safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010
IECEx approval: BVS 09.0037X
Directive conformity: Approved for: Ex nA [ic] IIC T4 Gc
Marine approval: Lloyd Register: 15/20021
Marine approval: DNV GL Marine: TAA0000034
Marine approval: Bureau Veritas Marine: 22449/B0 BV
System information: The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2 or Zone 22) the module must be installed in an appropriate enclosure.
Supplementary information: EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Parametry logistyczne

ECCN:
Kraj pochodzenia: Deutschland
EAN: 4050143063796
Waga: 0,15 kg
Długość: 0,00 m