254534
VBG-ENX-K20-DMD-EV
AS-Interface gateway
EtherNet/IP + MODBUS/TCP com unit with data decoupling, double master for 2 AS-Interface networksfa. The VBG-ENX-K20-DMD-EV is a EtherNet/IP gateway with a double master according to AS-Interface specification 3.0. The design of the K20 in stainless steel with IP20 is particularly suited for use in switching cabinets for snap on mounting on the 35 mm mounting rail. The gateway in accordance with the AS-Interface specification V 3.0 is used to connect AS-Interface systems to a higher-level net. It acts as a master for the AS-Interface segment and as a slave for the higher-level net. During cyclic data exchange, the digital data of an AS-Interface segment is transferred. Analog values as well as the complete command set of the new AS-Interface specification are transferred using a command interface. The address allocation and acceptance of the target configuration can be achieved via the keys. 7 LEDs fitted to the front panel indicate the actual state of the AS-Interface branch. With the graphical display, the commissioning of the AS-Interface circuits and testing of the connected peripherals can take place completely separately from the commissioning of the higher-level network and the programming. With the 4 switches, all functions can be controlled and visualized on the display. An RJ-45 Ethernet port provides a way of exporting data relating to the gateway, network and operation directly from the gateway for extended local diagnosis purposes. Via the RJ-45 Ethernet diagnostic interface, up to 31 devices can establish a secure cross-communication. The device has a card slot for a memory card for the storage of configuration data. The integrated data decoupling allows to operate 2 AS-Interface circuits with just a standard power supply. The device level ring protocol DLR increases the reliability of a ring topology at the device level, thus optimizing the machine running times. The redundant power supply guarantees that the double master remains in function and is diagnosticable, when a failure of a power supply unit in one of the two AS-interfaces circles occures. Also communication with the superior field bus is not disturbed by the failure of a power supply. PLC Functionality. Optionally the gateway is also available with PLC functionality. Therefor you can order a code key VAZ-CTR additionally.
| AS-Interface specification: | V3.0 |
| PLC-Functionality: | activateable |
| Duplicate address detection: | from AS-Interface slaves |
| Earth fault detection: | integrated |
| EMC monitoring: | integrated |
| Diagnostics function: | Extended function via display |
| Data decoupling: | integrated |
| UL File Number: | E223772 only from low voltage, limited energy source (SELV or PELV) or listed Class 2 source |
| Display: | Illuminated graphical LC display for addressing and error messages |
| LED AS-i ACTIVE: | AS-Interface operation normal; LED green |
| LED CONFIG ERR: | configuration error; LED red |
| LED PRG ENABLE: | autom. programming; LED green |
| LED POWER: | voltage ON; LED green |
| LED PRJ MODE: | projecting mode active; LED yellow |
| LED SER ACTIVE: | ethernet active; LED green |
| LED U AS-i: | AS-Interface voltage; LED green |
| Button: | 4 |
| Switch SET: | Selection and setting of a slave address |
| OK button: | Mode selection traditional-graphical/confirmation |
| Button MODE: | Mode selection PRJ-operation/save configuration/cursor |
| ESC button: | Mode selection traditional-graphical/cancel |
| Insulation voltage: | ≥ 500 V |
| Rated operating voltage: | from AS-Interface 30 V DC |
| Rated operating current: | ≤ 250 mA PELV |
| Interface type: | 2 x RJ-45 |
| Protocol: | EtherNet/IP + MODBUS TCP/IP acc. to IEEE 802.3 supports device level ring protocol DLR |
| Transfer rate: | 10 MBit/s / 100 MBit/s , Automatic baud rate detection |
| Interface type: | RS 232, serial Diagnostic Interface |
| Transfer rate: | 19,2 kBit/s |
| Interface type: | Chip card slot |
| Ethernet: | RJ-45 |
| AS-Interface: | spring terminals, removable |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007 |
| Electromagnetic compatibility: | EN 61000-6-2:2005, EN 61000-6-4:2007 |
| Degree of protection: | EN 60529:2000 |
| AS-Interface: | EN 62026-2:2013 |
| Shock resistance: | EN 61131-2:2004 |
| UL approval: | An isolated source with a secondary open circuit voltage of ≤ 30 VDC with a 3 A maximum over current protection. Over current protection is not required when a Class 2 source is employed. UL mark does not provide UL certification for any functional safety rating or aspects of the device. |
| Ambient temperature: | 0 ... 55 °C (32 ... 131 °F) |
| Storage temperature: | -25 ... 85 °C (-13 ... 185 °F) |
| Degree of protection: | IP20 |
| Material: Housing: | Stainless steel |
| Mass: | 500 g |
| Construction type: | Low profile housing , Stainless steel |
| ECCN: | |
| Kraj pochodzenia: | Deutschland |
| EAN: | 4050143042074 |
| Waga: | 0,59 kg |
| Długość: | 0,00 m |
| Szerokość: | 0,00 m |
| Wysokość: | 0,00 m |