Pepperl+Fuchs 250935

NJ3-18GK-S1N

Inductive sensor

Na prośbę. Prześlij nam wiadomość e-mail z zapytaniem o cenę i dostępność.
"ucnguBrctvdgcxgt0eqo"

Opis

Series: Cylindrical type, Housing material: Crastin (PBT), black, Output type: 2-wire, Installation: flush in mild steel, Type of voltage: DC, Connection type: cable silicone , 2 m, Degree of protection: IP68fa

Parametry techniczne

Switching function: Normally open (NO)
Output type: NAMUR with safety function
Rated operating distance: 3 mm
Installation: flush in mild steel
Assured operating distance: 0 ... 2.4 mm
Actual operating distance: 2.7 ... 3.3 mm typ.
Reduction factor rAl: 1
Reduction factor rCu: 1
Reduction factor r304: 0
Safety Integrity Level (SIL): up to SIL3 acc. to IEC 61508 Danger! In safety-related applications the sensor must be operated with a qualified fail safe interface from Pepperl+Fuchs, such as KFD2-SH-EX1. Consider the "exida Functional Safety Assessment" document which is available on www.pepperl-fuchs.com as an integral part of this product's documentation.
Output type: 2-wire
Nominal voltage: 8.2 V
Switching frequency: 0 ... 200 Hz
Suitable for 2:1 technology: yes , Reverse polarity protection diode not required
Current consumption: Measuring plate not detected: ≤ 1 mA
Current consumption: Measuring plate detected: ≥ 3 mA
Safety Integrity Level (SIL): SIL 3
MTTFd: 7666 a
Mission Time (TM): 20 a
Diagnostic Coverage (DC): 0 %
Standard conformity: Standards: EN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012
EAC conformity: TR CU 012/2011
FM approval: Control drawing: 116-0165
UL approval: cULus Listed, General Purpose
FM approval: Ordinary Location: E87056
FM approval: Hazardous Location: E501628
FM approval: Control drawing: 116-0454
CCC approval: CCC approval / marking not required for products rated ≤36 V
Ambient temperature: -25 ... 100 °C (-13 ... 212 °F)
Connection type: cable silicone , 2 m
Core cross-section: 0.75 mm2
Housing material: Crastin (PBT), black
Sensing face: Crastin (PBT), black
Degree of protection: IP68
Cable: Cable diameter: 6.8 mm ± 0.2 mm
Cable: Bending radius: > 10 x cable diameter
Note: only for non-ferrous metal
Use in the hazardous area: see instruction manuals

Parametry logistyczne

ECCN:
Kraj pochodzenia: ID
EAN:
Waga: 0,00 kg
Długość: 0,00 m
Szerokość: 0,00 m