241590
KFD0-CS-Ex1.54-Y2
Repeater
This isolated barrier is used for intrinsic safety applications. It provides control and signal transfer for SMART compatible fire and smoke alarm transmitters inside hazardous areas. 1-channel isolated barrier, 24 V DC supply (loop powered), SMART fire alarm input, Current input 1 mA .. 20 mA, Transfer direction: to the control systempa. The typical application for the barrier is connection of a fire detector loop to a control panel through a System Sensor® translator device (typically an IST200). The fall time of the digital signal must be less than 50 s, the current in the hazardous area must be bigger than 1 mA. Since this isolator is loop-powered, use the technical data to verify that proper voltage is available to the field devices.
| Signal type: | Analog input |
| Rated voltage: | loop powered |
| Power dissipation: | 0.2 W |
| Connection: | terminals 11+, 12- |
| Current: | 0 ... 20 mA |
| Transmission range: | current: 1 ... 20 mA voltage: 0 ... 24 V |
| Connection: | terminals 1+, 2- |
| Short-circuit current: | ≤ 65 mA |
| Deviation: After calibration: | ≤ 3.5 mA current loss at 20 mA load current |
| Deviation: Influence of ambient temperature: | ± 20 µA / K |
| Rise time/fall time: | ≤ 50 µs (load current ≥ 1 mA) |
| Input/Output: | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Labeling: | space for labeling at the front |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1:2013 (industrial locations) |
| Electromagnetic compatibility: | NE 21:2006 |
| Degree of protection: | IEC 60529:2001 |
| Protection against electrical shock: | UL 61010-1 |
| Ambient temperature: | -20 ... 60 °C (-4 ... 140 °F) |
| Degree of protection: | IP20 |
| Connection: | screw terminals |
| Mass: | approx. 100 g |
| Dimensions: | 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1 |
| Mounting: | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| EU-Type Examination Certificate: | BAS 00 ATEX 7087 |
| Electromagnetic compatibility: Marking: | II (1)G [Ex ia Ga] IIC , II (1)D [Ex ia Da] IIIC , I (M1) [Ex ia Ma] I (-20 °C ≤ Tamb ≤ 60 °C) |
| Electromagnetic compatibility: Voltage: | 25.2 V |
| Electromagnetic compatibility: Current: | 43 mA |
| Electromagnetic compatibility: Power: | 271 mW |
| Supply: Maximum safe voltage: | 250 V (Attention! The rated voltage can be lower.) |
| Certificate: | TÜV 99 ATEX 1499 X |
| Supply: Marking: | II 3G Ex nA II T4 [device in zone 2] |
| Galvanic isolation: Input/Output: | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Directive conformity: Directive 2014/34/EU: | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
| FM approval: Control drawing: | 116-0129 (cFMus) |
| UL approval: Control drawing: | 116-0348 (cULus) |
| IECEx approval: | IECEx BAS 08.0079 IECEx BAS 10.0007X |
| UL approval: Approved for: | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Ex nA II T4 Gc |
| Supplementary information: | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| ECCN: | |
| Kraj pochodzenia: | SG |
| EAN: | |
| Waga: | 0,00 kg |
| Długość: | 0,00 m |
| Szerokość: | 0,00 m |
| Wysokość: | 0,00 m |