240531
Z042
Zener Barrier
The Zener Barrier prevents the transfer of unacceptably high energy from the safe area into the hazardous area. 2-channel, DC version, positive polarity, Working voltage 1 V at 1 µA, Series resistance max. 209.5 Ω, Fuse rating 100 mA, DIN rail mountable, Number of channels: 2-channelpa. The zener diodes in the Zener Barrier are connected in the reverse direction. The breakdown voltage of the diodes is not exceeded in normal operation. If this voltage is exceeded, due to a fault in the safe area, the diodes start to conduct, causing the fuse to blow. The Zener Barrier has a positive polarity, i. e. the anodes of the zener diodes are grounded. Depending on the application, increased or decreased intrinsic safety parameters apply for serial or parallel connection. For the detailed parameters refer to the Zener Barrier certificate. Application examples can be found in the system description of the Zener Barriers.
| Type: | DC version, positive polarity |
| Nominal resistance: | 206.5 Ω |
| Series resistance: | max. 209.5 Ω |
| Fuse rating: | 100 mA |
| Connection: | terminals 1, 2; 3, 4 |
| Connection: | terminals 5, 6; 7, 8 |
| Working voltage: Supply loop: | max. 5 V |
| Working voltage: Measurement loop: | max. 3 V at 10 µA (1 V at 1 µA) |
| Deviation: Influence of ambient temperature: | max. 0.05 Ω/K |
| Degree of protection: | IEC 60529 |
| Ambient temperature: | -20 ... 60 °C (-4 ... 140 °F) |
| Storage temperature: | -25 ... 70 °C (-13 ... 158 °F) |
| Relative humidity: | max. 75 % , without condensation |
| Degree of protection: | IP20 |
| Connection: | screw terminals |
| Core cross-section: | max. 2 x 2.5 ... mm2 |
| Mass: | approx. 150 g |
| Dimensions: | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) |
| Construction type: | modular terminal housing , see system description |
| Mounting: | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| EU-type examination certificate: | BAS 01 ATEX 7005 |
| Deviation: Marking: | II (1)G [Ex ia Ga] IIC, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I (-20 °C ≤ Tamb ≤ 60 °C) |
| Deviation: Voltage: | terminals 1, 2: 5.88 V / terminals 3, 4: 5.88 V |
| Deviation: Current: | terminals 1, 2: 30 mA / terminals 3, 4: 30 mA |
| Deviation: Power: | terminals 1, 2: 44 mW / terminals 3, 4: 44 mW |
| Supply: Maximum safe voltage: | 250 V |
| Series resistance: | min. 196.7 Ω |
| Certificate: | TÜV 99 ATEX 1484 X |
| Supply: Marking: | II 3G Ex nA IIC T4 Gc [device in zone 2] |
| Directive conformity: Directive 2014/34/EU: | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
| IECEx approval: | IECEx BAS 09.0142 IECEx BAS 17.0091X |
| Directive conformity: Approved for: | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
| Supplementary information: | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| ECCN: | |
| Kraj pochodzenia: | ID |
| EAN: | |
| Waga: | 0,00 kg |
| Długość: | 0,00 m |
| Szerokość: | 0,00 m |
| Wysokość: | 0,00 m |