Pepperl+Fuchs 238483

FB1302B2

Digital Input

Na prośbę. Prześlij nam wiadomość e-mail z zapytaniem o cenę i dostępność.
"ucnguBrctvdgcxgt0eqo"

Opis

The device accepts digital input signals of NAMUR sensors or mechanical contacts from the hazardous area. 3-channel, Fully compatible replacement for FB1302**, Inputs with plug-in Ex e terminals, Installation in suitable enclosures in Zone 1pa. Open and short-circuit line faults are detected. The device is supplied with plug-in Ex e terminals and protective cover. The inputs are galvanically isolated from the bus and the power supply.

Parametry techniczne

Occupied slots: 1
Connection: backplane bus
Rated voltage: 12 V DC , only in connection with the power supplies FB92**
Power dissipation: 0.75 W
Power consumption: 0.75 W
Connection: backplane bus
Interface: manufacturer-specific bus to standard com unit
Number of channels: 3
Sensor interface: Connection: NAMUR sensor
Sensor interface: Connection [2]: volt-free contact
Sensor interface: Connection [3]: active binary signal 24 V DC
Connection: channel I: 1+, 4-; channel II: 2+, 5-; channel III: 3+, 6-
Rated values: acc. to EN 60947-5-6 (NAMUR)
Switching point/switching hysteresis: 1.2 ... 2.1 mA / ± 0.2 mA
Internal resistor: 1 kΩ
Line fault detection: can be switched on/off for each channel via configuration tool
Sensor interface: Connection: mechanical switch with additional resistors (see connection diagram) proximity switches without additional wiring
Sensor interface: Short-circuit: < 360 Ω
Sensor interface: Open-circuit: < 0.35 mA
Minimum pulse duration: 20 ms
LED indication: LED green: supply LED red: line fault, per channel LED yellow: signal (status), per channel
Coding: optional mechanical coding via front socket
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2006
Electromagnetic compatibility: NE 21:2007
Degree of protection: IEC 60529:2000
Environmental test: EN 60068-2-14:2009
Shock resistance: EN 60068-2-27:2009
Vibration resistance: EN 60068-2-6:2008
Damaging gas: EN 60068-2-42:2003
Relative humidity: EN 60068-2-78:2001
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Relative humidity: 95 % non-condensing
Shock resistance: shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistance: frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gas: designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Degree of protection: IP20 (module) , a separate housing is required acc. to the system description
Connection: Ex e spring terminal with protective cover
Mass: approx. 350 g
Dimensions: 28 x 107 x 132 mm (1.1 x 4.2 x 5.2 inch)
EU-Type Examination Certificate: BVS 11 ATEX E 093 X
Electromagnetic compatibility: Marking: II 2 G Ex db eb IIC T4
Galvanic isolation: Input/power supply, internal bus: safe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2009 EN 60079-1:2007 EN 60079-7:2007
ATEX approval: BVS 11 ATEX E 093X
INMETRO: Brazil: TÜV 14.1599X
EAC approval: Russia: RU C-IT.MIII06.B.00129
Marine approval: Lloyd Register: 15/20021
Marine approval: American Bureau of Shipping: T1450280/UN
Marine approval: Bureau Veritas Marine: 22449/B0 BV
System information: The module has to be mounted in appropriate backplanes (FB92**) in Zone 1, 2, or outside hazardous areas. Observe the corresponding EC-type examination certificate.
Supplementary information: EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Parametry logistyczne

ECCN:
Kraj pochodzenia: Deutschland
EAN: 4050143074280
Waga: 0,90 kg
Długość: 0,00 m
Szerokość: 0,00 m
Wysokość: 0,00 m