237499
VBA-2A-G11-I-V1
AS-Interface analog module
The analog module VBA-2A-G11-I-V1 has two analog current outputs (0 mA .. 20 mA). Power is supplied to the outputs through the yellow AS-Interface cable. Analog value conversion and data transfer are provided asynchronously according to AS-Interface profile 7.3. The rise time of the analog signals is approx. 2 ms. G11 analog module. 2 analog outputsfa, channel. Peripheral faults are not signaled when there is no active connection to an actuator. If the internal “watchdog” monitoring function is enabled, the output signals are reset to zero if communication with the AS-Interface fails. The G11 module with IP68/IP69K protection is particularly suitable for demanding field applications. The connection to the actuators is established via M12 connectors. The module can be preaddressed by connecting it to the handheld programming unit VBP-HH1. The connection to the AS-Interface transfer line is established via an M12 connector. Note:. A lead breakage or an output value outside the value range is also transmitted to the ASInterface master via the 'peripheral fault' function. Communication via the AS-Interface continues.
| Slave type: | Standard slave |
| AS-Interface specification: | V3.0 |
| Required master specification: | ≥ V2.1 |
| UL File Number: | E223772 |
| MTTFd: | 370 a |
| Mission Time (TM): | 20 a |
| Diagnostic Coverage (DC): | 0 % |
| LED AS-i/FAULT: | Status display; multi-colour LED Green: normal operation Red: communication fault Flashing yellow/red: address 0 Flashing green/red: peripheral fault |
| LED ANALOG: | Status of output signal; yellow LED Yellow: 0 mA ≤ I ≤ 23 mA Yellow flashing: lead breakage or I > 23 mA |
| Rated operating voltage: | 26.5 ... 31.6 V from AS-Interface |
| Rated operating current: | ≤ 100 mA |
| Protection class: | III |
| Surge protection: | Ue: Over voltage category III, safe isolated power supplies (PELV) |
| Number/Type: | 2 analog outputs (current), 0 ... 20 mA |
| Supply: | from AS-Interface |
| Load: | max. 600 Ω |
| Resolution: | 6 µA |
| Accuracy: | 0.15 % of full-scale value |
| Temperature influence: | 1 µA/K |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 62026-2:2013 |
| Degree of protection: | EN 60529:2000 |
| Fieldbus standard: | EN 62026-2:2013 |
| Emitted interference: | EN 61000-6-4:2007 |
| AS-Interface: | EN 62026-2:2013 |
| Noise immunity: | EN 61000-6-2:2005, EN 61326-1:2006, IEC 62026-2:2008 |
| Profile: | S-7.3.5 |
| IO code: | 7 |
| ID code: | 3 |
| ID1 code: | F |
| ID2 code: | 5 |
| Data bits (function via AS-Interface): | The transfer of the data value is based on AS-Interface Profile 7.3. |
| Parameter bits (programmable via AS-i): | function |
| Electromagnetic compatibility: P0: | Watchdog: P0=1 (default), watchdog active P0=0, watchdog inactive |
| Electromagnetic compatibility: P1: | not used |
| Electromagnetic compatibility: P2: | Indication of peripheral fault: P2=1 (default), peripheral fault is reported P2=0, peripheral fault is not reported |
| Electromagnetic compatibility: P3: | not used |
| Ambient temperature: | -25 ... 70 °C (-13 ... 158 °F) |
| Storage temperature: | -25 ... 85 °C (-13 ... 185 °F) |
| Relative humidity: | 85 % , noncondensing |
| Climatic conditions: | For indoor use only |
| Altitude: | ≤ 2000 m above MSL |
| Pollution degree: | 3 |
| Degree of protection: | IP68 / IP69K |
| Connection: | AS-Interface: M12 round connector Outputs: M12 round connector |
| Material: Housing: | PBT PC |
| Material: Mounting screw: | Stainless steel 1.4305 / AISI 303 |
| Mass: | 200 g |
| Tightening torque, housing screws: | 1.8 Nm |
| Tightening torque, cable gland: | 0.4 Nm |
| Mounting: | Mounting plate |
| ECCN: | |
| Kraj pochodzenia: | Singapur |
| EAN: | 4050143083862 |
| Waga: | 0,20 kg |
| Długość: | 0,00 m |
| Szerokość: | 0,00 m |
| Wysokość: | 0,00 m |