Pepperl+Fuchs 237499

VBA-2A-G11-I-V1

AS-Interface analog module

Na prośbę. Prześlij nam wiadomość e-mail z zapytaniem o cenę i dostępność.
"ucnguBrctvdgcxgt0eqo"

Opis

The analog module VBA-2A-G11-I-V1 has two analog current outputs (0 mA .. 20 mA). Power is supplied to the outputs through the yellow AS-Interface cable. Analog value conversion and data transfer are provided asynchronously according to AS-Interface profile 7.3. The rise time of the analog signals is approx. 2 ms. G11 analog module. 2 analog outputsfa, channel. Peripheral faults are not signaled when there is no active connection to an actuator. If the internal “watchdog” monitoring function is enabled, the output signals are reset to zero if communication with the AS-Interface fails. The G11 module with IP68/IP69K protection is particularly suitable for demanding field applications. The connection to the actuators is established via M12 connectors. The module can be preaddressed by connecting it to the handheld programming unit VBP-HH1. The connection to the AS-Interface transfer line is established via an M12 connector. Note:. A lead breakage or an output value outside the value range is also transmitted to the ASInterface master via the 'peripheral fault' function. Communication via the AS-Interface continues.

Parametry techniczne

Slave type: Standard slave
AS-Interface specification: V3.0
Required master specification: ≥ V2.1
UL File Number: E223772
MTTFd: 370 a
Mission Time (TM): 20 a
Diagnostic Coverage (DC): 0 %
LED AS-i/FAULT: Status display; multi-colour LED Green: normal operation Red: communication fault Flashing yellow/red: address 0 Flashing green/red: peripheral fault
LED ANALOG: Status of output signal; yellow LED Yellow: 0 mA ≤ I ≤ 23 mA Yellow flashing: lead breakage or I > 23 mA
Rated operating voltage: 26.5 ... 31.6 V from AS-Interface
Rated operating current: ≤ 100 mA
Protection class: III
Surge protection: Ue: Over voltage category III, safe isolated power supplies (PELV)
Number/Type: 2 analog outputs (current), 0 ... 20 mA
Supply: from AS-Interface
Load: max. 600 Ω
Resolution: 6 µA
Accuracy: 0.15 % of full-scale value
Temperature influence: 1 µA/K
Electromagnetic compatibility: Directive 2014/30/EU: EN 62026-2:2013
Degree of protection: EN 60529:2000
Fieldbus standard: EN 62026-2:2013
Emitted interference: EN 61000-6-4:2007
AS-Interface: EN 62026-2:2013
Noise immunity: EN 61000-6-2:2005, EN 61326-1:2006, IEC 62026-2:2008
Profile: S-7.3.5
IO code: 7
ID code: 3
ID1 code: F
ID2 code: 5
Data bits (function via AS-Interface): The transfer of the data value is based on AS-Interface Profile 7.3.
Parameter bits (programmable via AS-i): function
Electromagnetic compatibility: P0: Watchdog: P0=1 (default), watchdog active P0=0, watchdog inactive
Electromagnetic compatibility: P1: not used
Electromagnetic compatibility: P2: Indication of peripheral fault: P2=1 (default), peripheral fault is reported P2=0, peripheral fault is not reported
Electromagnetic compatibility: P3: not used
Ambient temperature: -25 ... 70 °C (-13 ... 158 °F)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Relative humidity: 85 % , noncondensing
Climatic conditions: For indoor use only
Altitude: ≤ 2000 m above MSL
Pollution degree: 3
Degree of protection: IP68 / IP69K
Connection: AS-Interface: M12 round connector Outputs: M12 round connector
Material: Housing: PBT PC
Material: Mounting screw: Stainless steel 1.4305 / AISI 303
Mass: 200 g
Tightening torque, housing screws: 1.8 Nm
Tightening torque, cable gland: 0.4 Nm
Mounting: Mounting plate

Parametry logistyczne

ECCN:
Kraj pochodzenia: Singapur
EAN: 4050143083862
Waga: 0,20 kg
Długość: 0,00 m
Szerokość: 0,00 m
Wysokość: 0,00 m