Pepperl+Fuchs 233751

KFA5-SOT2-Ex2

Switch Amplifier

Na prośbę. Prześlij nam wiadomość e-mail z zapytaniem o cenę i dostępność.
"ucnguBrctvdgcxgt0eqo"

Opis

2-channel isolated barrier, 115 V AC supply, Dry contact or NAMUR inputs, Passive transistor output, non-polarized, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 acc. to IEC 61508pa. This isolated barrier is used for intrinsic safety applications. It transfers digital signals (NAMUR sensors/mechanical contacts) from a hazardous area to a safe area. Each proximity sensor or switch controls a passive transistor output for the safe area load. The normal output state can be reversed using switch S1 for channel I and switch S2 for channel II. Switch S3 enables or disables line fault detection of the field circuit. During an error condition, the transistors revert to their de-energized state and LEDs indicate the fault according to NAMUR NE44.

Parametry techniczne

Signal type: Digital Input
Safety Integrity Level (SIL): SIL 2
Connection: terminals 14, 15
Rated voltage: 103.5 ... 126.5 V AC , 45 ... 65 Hz
Power dissipation: 1 W
Power consumption: max. 1.5 W
Connection side: field side
Connection: terminals 1+, 2+, 3-; 4+, 5+, 6-
Rated values: acc. to EN 60947-5-6 (NAMUR), see system description for electrical data
Open circuit voltage/short-circuit current: approx. 8 V DC / approx. 8 mA
Switching point/switching hysteresis: 1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detection: breakage I ≤ 0.1 mA , short-circuit I > 6 mA
Connection side: control side
Connection: output I: terminals 7, 8 ; output II: terminals 8, 9
Switching voltage: max. 40 V
Switching current: max. 100 mA , short-circuit protected
Signal level: 1-signal: switching voltage - 2.5 V max. at 10 mA switching current or 3 V max. at 100 mA switching current 0-signal: switched off (off-state current ≤ 10 µA)
Output I, II: signal ; electronic output, passive
Switching frequency: ≤ 5 kHz
Input/Output: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supply: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/power supply: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/Output: not available
Display elements: LEDs
Control elements: DIP-switch
Configuration: via DIP switches
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Low voltage: Directive 2014/35/EU: EN 61010-1:2010
Electromagnetic compatibility: NE 21:2012
Degree of protection: IEC 60529
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Degree of protection: IP20
Connection: screw terminals
Mass: approx. 150 g
Dimensions: 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001
EU-Type Examination Certificate: PTB 98 ATEX 2164
Low voltage: Marking: II (1) G [Ex ia] IIC II (1) D [Ex ia] IIIC
Low voltage: Input: Ex ia IIC, Ex ia IIIC
Low voltage: Voltage: 10.5 V
Low voltage: Current: 13 mA
Low voltage: Power: 34 mW (linear characteristic)
Supply: Maximum safe voltage: 126.5 V AC (Attention! Um is no rated voltage.)
Output: Maximum safe voltage: 253 V AC (Attention! The rated voltage can be lower.)
Galvanic isolation: Input/input: not available
Galvanic isolation: Input/Output: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Galvanic isolation: Input/power supply: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-11:2012
UL approval: Control drawing: 116-0145
CSA approval: Control drawing: 116-0047
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Parametry logistyczne

ECCN:
Kraj pochodzenia: SG
EAN:
Waga: 0,00 kg
Długość: 0,00 m
Szerokość: 0,00 m
Wysokość: 0,00 m