232114
FC-GPCS-RIO16-PF
Termination Board
System board for Honeywell Universal Safety IO, System board for Honeywell Universal Process IO, For 16-channel cards USIO and UPIO, For 16 modules, Recommended modules: HiC2831R2 (DI), HiC2853R2 (DI), HiC2871 (DO), HiC2025 (AI), HiC2031 (AO), Recommended system cable: CAB-HON-**-S37C32-MX-01000, 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: Sub-D connector (male), 37-pinpa. The function of the termination board and the connector pin assignment is exactly fitted to the requirements of Honeywell system. Information about a missing supply voltage of the isolators is available for the system as a volt-free contact. It is possible to transfer a fault signal to channel 1 of the card via the loop-in function. The termination board is supplied with a robust plastic housing. This design permits the fast and reliable installation on 35 mm DIN mounting rail according to. EN 60715 in the switch cabinet.
| Connection: | terminal block TB3 (1-, 2+; 3-, 4+) |
| Nominal voltage: | 24 V DC , in consideration of rated voltage of used isolators |
| Voltage drop: | 0.9 V , voltage drop across the series diode on the termination board must be considered |
| Ripple: | ≤ 10 % |
| Fusing: | 4 A |
| Power dissipation: | ≤ 500 mW , without modules |
| Reverse polarity protection: | yes |
| Supply: | Redundancy available. The supply for the isolators is decoupled, monitored and fused. |
| Output type: | volt-free contact |
| Contact loading: | 30 V DC , 1 A |
| Display elements: | LEDs PWR ON (power supply) - LED power supply I, green LED - LED power supply II, green LED LED Fault (fault indication), red LED |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1:2013 (industrial locations) |
| Electromagnetic compatibility: | NE 21:2017 For further information see system description. |
| Degree of protection: | IEC 60529:2001 |
| Ambient temperature: | -20 ... 60 °C (-4 ... 140 °F) |
| Storage temperature: | -40 ... 70 °C (-40 ... 158 °F) |
| Degree of protection: | IP20 |
| Connection: Field side: | explosion hazardous area: pluggable screw terminals , blue |
| Connection: Control side: | non-explosion hazardous area: 37-pin Sub-D connector |
| Connection: Supply: | pluggable screw terminals , black |
| Connection: Fault output: | pluggable screw terminals , black |
| Core cross-section: | screw terminals: 0.25 ... 2.5 mm2 (24 ... 12 AWG) |
| Material: | housing: polycarbonate |
| Mass: | approx. 825 g |
| Dimensions: | 273 x 155 x 153 mm (L x W x H) , height including module assembly |
| Mounting: | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| EU-Type Examination Certificate: | CESI 06 ATEX 022 |
| Connection: Marking: | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
| Non-hazardous area: Maximum safe voltage: | 250 V (Attention! Um is no rated voltage.) |
| Certificate: | DEMKO 18 ATEX 2116 X |
| Non-hazardous area: Marking: | II 3G Ex ec nC IIC T4 Gc |
| Galvanic isolation: Field circuit/control circuit: | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Directive conformity: Directive 2014/34/EU: | EN 60079-0:2012+A11:2013 , EN 60079-7:2015 , EN 60079-11:2012 , IEC 60079-15:2017 , EN 50303:2000 |
| UL approval: Control drawing: | 116-0327 |
| IECEx approval: IECEx certificate: | IECEx CES 06.0003 IECEx UL 18.0111 X |
| IECEx approval: IECEx marking: | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I Ex ec nC IIC T4 Gc |
| Supplementary information: | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| Designation: | provided accessory: Label Carrier HiALC-HI*TF-SET-1** optional accessories: system cable CAB-HON-**-S37C32-MX-01000 |
| ECCN: | |
| Kraj pochodzenia: | SG |
| EAN: | |
| Waga: | 0,00 kg |
| Długość: | 0,00 m |
| Szerokość: | 0,00 m |
| Wysokość: | 0,00 m |