231291
KFD0-HMS-16
HART-Multiplexer-Slave KFD0-HMS-16
This HART Multiplexer Slave operates up to 16 analog field instruments. It can be operated only with the HART Multiplexer Master KFD2-HMM-16 and is powered by the master across a 14- pin flat cable connection. Up to 15 slaves can be connected to the master. The slave address is set with a 16- position rotary switch (addresses 1 .. 16). If only one slave is connected to the master, then the slave address should be 1. If multiple slaves are connected, slaves must be assigned addresses in ascending order. The analog signals are fed into the slave by means of a 26-pin flat cable. Sixteen leads are reserved for the HART signal of the analog measurement circuits. The remaining 10 leads are assigned to ground.
| Safety Integrity Level (SIL): | SIL 3 |
| Connection: | via 14-channel flat cable form master KFD2-HMM-16 |
| Conformity: | HART field device input (revision 5 to 7) |
| Connection: | 26-pin flat cable for analog connections 14-pin flat cable for master-slave connection between KFD2-HMM-16 and KFD0-HMS-16 |
| Leakage current: | < 3 µA at -20 ... 85 °C (-4 ... 185 °F) |
| Terminating resistor: | external 230 ... 500 Ω standard (up to 1000 Ω possible) |
| Output voltage: | ≥ 400 mV ss (with the terminator resistance specified above) |
| Output resistance: | 100 Ω or smaller, capacitive coupling |
| Input impedance: | according to HART specification |
| Input voltage range: | 0.08 ... 4 V ss ; typ. ± 5.2 V as local reference |
| Labeling: | space for labeling at the front |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1:2013 (industrial locations) |
| Degree of protection: | IEC 60529:2001 |
| Ambient temperature: | -20 ... 60 °C (-4 ... 140 °F) |
| Degree of protection: | IP20 |
| Mass: | approx. 100 g |
| Dimensions: | 20 x 93 x 115 mm (0.8 x 3.7 x 4.5 inch) , housing type B1 |
| Mounting: | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| Certificate: | PF 07 CERT 1143 X |
| Electromagnetic compatibility: Marking: | II 3G Ex nA IIC T4 Gc |
| Directive conformity: Directive 2014/34/EU: | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 |
| Supplementary information: | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| ECCN: | |
| Kraj pochodzenia: | SG |
| EAN: | |
| Waga: | 0,00 kg |
| Długość: | 0,00 m |
| Szerokość: | 0,00 m |
| Wysokość: | 0,00 m |