Pepperl+Fuchs 231225

KFD2-GUT-Ex1.D

Temperature Converter with Trip Values

Na prośbę. Prześlij nam wiadomość e-mail z zapytaniem o cenę i dostępność.
"ucnguBrctvdgcxgt0eqo"

Opis

1-channel isolated barrier, 24 V DC supply (Power Rail), Thermocouple, RTD, potentiometer or voltage input, Redundant TC input, Current output 0/4 mA ... 20 mA, 2 relay contact outputs, Configurable by PACTware or keypad, Line fault (LFD) and sensor burnout detection, Up to SIL 2 acc. to IEC 61508/IEC 61511pa. This isolated barrier is used for intrinsic safety applications. The device converts the signal of a resistance thermometer, thermocouple, potentiometer, or voltage source to a proportional output current. It also provides a relay trip value. The removable terminal block K-CJC-** is available as an accessory for internal cold junction compensation of thermocouples. A fault is signalized by LEDs acc. to NAMUR NE44 and a separate collective error message output. The device is easily configured by the use of the PACTware configuration software. For additional information, refer to the manual and www.pepperl-fuchs.com.

Parametry techniczne

Signal type: Analog input
Safety Integrity Level (SIL): SIL 2
Connection: terminals 23+, 24- or power feed module/Power Rail
Rated voltage: 20 ... 30 V DC
Rated current: approx. 100 mA
Power dissipation/power consumption: ≤ 2 W / 2.2 W
Programming interface: programming socket
Connection side: field side
Connection: terminals 1, 2, 3, 4, 6
RTD: Pt100, Pt500, Pt1000, Ni100, Ni1000
: Types of measuring: 2-, 3-, 4-wire technology
: Lead resistance: max. 50 Ω
: Measurement loop monitoring: sensor breakage, sensor short-circuit
Thermocouples: type B, E, J, K, L, N, R, S, T (IEC 584-1: 1995)
: Cold junction compensation: external and internal
: Measurement loop monitoring: sensor breakage
Potentiometer: 0.8 ... 20 kΩ
: Types of measuring: 2-, 3-, 5-wire technology
Voltage: 0 ... 10 V , 2 ... 10 V , 0 ... 1 V , -100 ... 100 mV
Input resistance: ≥ 250 kΩ (0 ... 10 V) min. 1 MΩ (0 ... 1 V, -100 ... 100 mV)
Measuring current: approx. 400 µA with resistance measuring sensor
Connection side: control side
Connection: output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 output III: terminals 8+, 7-
Output I, II: relay
: Contact loading: 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 DC / 2 A
: Mechanical life: 5 x 107 switching cycles
: Energized/De-energized delay: approx. 20 ms / approx. 20 ms
Output III: Analog current output
: Current range: 0 ... 20 mA or 4 ... 20 mA
: Open loop voltage: max. 24 V DC
: Load: max. 650 Ω
: Fault signal: downscale I ≤ 3.6 mA, upscale I ≥ 21 mA (acc. NAMUR NE43)
Collective error message: Power Rail
Deviation: Temperature effect: Input: 0.005 %/K (50 ppm) of span ; current output: 0.005 %/K (50 ppm) of span
Deviation: RTD: max. 0.2 % of span
Deviation: Thermocouples: max. 10µV deviation of CJC: ±0.8 K
Deviation: Voltage: 0.1 % of span
Deviation: Potentiometer: 0.1 % of span when < 5 kΩ 0.5 % of span when > 5 kΩ
Deviation: Current output: max. 20 µA
Sampling rate: approx. 700 ms
Input/Other circuits: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output I, II against eachother: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output I, II/other circuits: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output III/power supply and collective error: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Interface/power supply: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Display elements: LEDs , display
Control elements: Control panel
Configuration: via operating buttons via PACTware
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Low voltage: Directive 2014/35/EU: EN 61010-1:2010
Electromagnetic compatibility: NE 21:2007
Degree of protection: IEC 60529:2001
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Degree of protection: IP20
Connection: screw terminals
Mass: 300 g
Dimensions: 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3
Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001
EU-type examination certificate: TÜV 03 ATEX 2140
Low voltage: Marking: II (1)G [Ex ia] IIC , II (1)D [Ex iaD]
Low voltage: Input: Ex ia IIC, Ex iaD
Supply: Maximum safe voltage: 40 V DC (Attention! The rated voltage can be lower.)
Input: terminals 2, 6 (for active equipment)
Supply: Voltage: 13.1 V
Supply: Current: 8 mA
Supply: Power: 67 mW
Supply: Voltage: 29 V
Supply: Current: 11 mA
Supply: Power: 200 mW
Inputs: terminals 1, 2, 3, 4, 6 (for passive equipment)
Supply: Voltage Uo: 13.1 V
Supply: Current Io: 21 mA
Supply: Power Po: 67 mW
Output: Contact loading: 253 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load (TÜV 03 ATEX 2140)
Analog output: Maximum safe voltage: 40 V (Attention! The rated voltage can be lower.)
Interface: Maximum safe voltage: 40 V (Attention! The rated voltage can be lower.) , RS 232
Certificate: PF 08 CERT 1213 X
Interface: Marking: II 3G Ex nA nC IIC T4 Gc
Output I, II: Contact loading: 50 V AC/2 A/cos φ > 0.7; 40 V DC/1 A resistive load
Galvanic isolation: Input/Other circuits: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
IECEx approval: IECEx certificate: IECEx TUN 09.0019
IECEx approval: IECEx marking: [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Parametry logistyczne

ECCN:
Kraj pochodzenia: SG
EAN:
Waga: 0,00 kg
Długość: 0,00 m
Szerokość: 0,00 m
Wysokość: 0,00 m