Pepperl+Fuchs 231211

KFA6-DU-Ex1.D

Switch Amplifier, Timer Relay

Na prośbę. Prześlij nam wiadomość e-mail z zapytaniem o cenę i dostępność.
"ucnguBrctvdgcxgt0eqo"

Opis

1-channel isolated barrier, 230 V AC supply, Dry contact or NAMUR inputs, Relay contact and transistor output, Adjustable output timer functions from 10 ms .. 60 min, Input frequency up to 80 Hz; pulse divider up to 1 kHz, Reset function, Configurable by keypad, Line fault detection (LFD)pa. This isolated barrier is used for intrinsic safety applications. It is a highly configurable timer that accepts a digital signal (NAMUR sensor/mechanical contact) from a hazardous area and is commonly used in applications requiring on-delay, off-delay, one-shot, or pulse lengthening. The output relay switch duration is easily adjusted, and a pulse divider function allows step-down ratios from 1:1 to 9999:1. A reset can be activated via dry contact switch and used to terminate a particular time function. The unit is easily programmed by the use of a keypad located on the front of the unit. Line fault detection of the field circuit is indicated by a red LED. For additional information, refer to the manual and www.pepperl-fuchs.com.

Parametry techniczne

Signal type: Digital Input
Connection: terminals 23, 24
Rated voltage: 230 V AC ± 10 %
Rated current: 15 mA
Power consumption: 4 VA
Connection side: field side
Connection: Input I: terminals 1+, 3- ; input II: terminals 13+, 14-
Input I: acc. to EN 60947-5-6 (NAMUR), see system description for electrical data
: Open circuit voltage/short-circuit current: 8.2 V / 10 mA
: Switching point/switching hysteresis: 1.2 ... 2.1 mA / approx. 0.2 mA
: Pulse duration: min. 75 µs / 1 ms see instruction manuals; the maximum input frequency has to be observed.
: Input frequency: 0 ... 80 Hz , pulse divider 0 ... 1 kHz
: Line fault detection: breakage I ≤ 0.15 mA; short-circuit I > 6.5 mA
Input II: reset
: Active/Passive: I > 3 mA / I < 1.5 mA
: Open circuit voltage/short-circuit current: 12 V / 3.5 mA
: Pulse duration: min. 10 ms
Connection side: control side
Connection: output I: terminals 10, 11, 12 ; output II: terminals 19+, 20-
Output I: signal , Relay output
: Contact loading: 253 V AC/ 2 A / cos φ ≥ 0.7 ; 40 V DC/ 2 A
: Mechanical life: 5 x 107 switching cycles
: Energized/De-energized delay: approx. 20 ms / approx. 20 ms
Output II: signal , electronic unit, isolated
: Contact loading: 40 V / 50 mA
: Energized/De-energized delay: after rising input flank 3 ms ; after falling input flank 2 ms
: Signal level: 1-signal: (L+) -2.5 V (50 mA, short-circuit/overload proof) 0-signal: blocked output (off-state current ≤ 10 µA)
Input I: Resolution: < 0.1 % of the set value, min. 10 ms
Input I: Accuracy: 2 ms
Input I: Influence of ambient temperature: 0.003 %/K (50 ppm)
Input I/other circuits: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output I/power supply and reset: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output I, II against eachother: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output II/power supply: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output II/reset: basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Reset/power supply: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Display elements: LEDs , display
Control elements: Control panel
Configuration: via operating buttons
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Low voltage: Directive 2014/35/EU: EN 61010-1:2010
Electromagnetic compatibility: NE 21:2006
Degree of protection: IEC 60529:2001
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Degree of protection: IP20
Connection: screw terminals
Mass: approx. 300 g
Dimensions: 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3
Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001
EU-Type Examination Certificate: TÜV 99 ATEX 1408
Low voltage: Marking: II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
Supply: Maximum safe voltage: 253 V AC (Attention! The rated voltage can be lower.)
Input I: terminals 1+, 3-: Ex ia
Supply: Voltage Uo: 10.1 V
Supply: Current Io: 13.5 mA
Supply: Power Po: 34 mW (linear characteristic)
Input II: terminals 13+, 14- non-intrinsically safe
Supply: Maximum safe voltage Um: 40 V (Attention! The rated voltage can be lower.)
Output I: terminals 10, 11, 12 non-intrinsically safe
Supply: Contact loading: 253 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load (TÜV 99 ATEX 1408) 50 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load (TÜV 02 ATEX 1885 X)
Supply: Maximum safe voltage: 253 V (Attention! The rated voltage can be lower.)
Output II: terminals 19+, 20- non-intrinsically safe
Supply: Maximum safe voltage: 40 V (Attention! The rated voltage can be lower.)
Certificate: TÜV 02 ATEX 1885 X
Supply: Marking: II 3G Ex nA nC IIC T4 Gc
Output I: Contact loading: 50 V AC/2 A/cos φ > 0.7; 40 V DC/1 A resistive load
Galvanic isolation: Input I/other circuits: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
FM approval: Control drawing: 116-0305
UL approval: E223772
IECEx approval: IECEx TUN 03.0000
FM approval: Approved for: [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Parametry logistyczne

ECCN:
Kraj pochodzenia: SG
EAN:
Waga: 0,00 kg
Długość: 0,00 m
Szerokość: 0,00 m
Wysokość: 0,00 m