Pepperl+Fuchs 231207

KFA6-DWB-Ex1.D

Rotation Speed Monitor

Na prośbę. Prześlij nam wiadomość e-mail z zapytaniem o cenę i dostępność.
"ucnguBrctvdgcxgt0eqo"

Opis

1-channel isolated barrier, 230 V AC supply, Dry contact or NAMUR inputs, Input frequency 1 mHz .. 5 kHz, 2 relay contact outputs, Start-up override, Configurable by keypad, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508/IEC 61511, Rated voltage: 230 V AC ± 10 %pa. This isolated barrier is used for intrinsic safety applications. It monitors for an overspeed or underspeed condition of a discrete signal (NAMUR sensor/ mechanical contact) from a hazardous area by comparing the input frequency to the user programmed reference frequency. An overspeed or underspeed condition is signaled via the relay outputs. Line fault detection of the field circuit is indicated by a red LED and relay. The start-up override feature sets relay outputs to default conditions programmed by the user for up to 1,000 seconds. The unit is easily programmed by the use of a keypad located on the front of the unit. For additional information, refer to the manual and www.pepperl-fuchs.com.

Parametry techniczne

Signal type: Digital Input
Safety Integrity Level (SIL): SIL 2
Connection: terminals 23, 24
Rated voltage: 230 V AC ± 10 %
Rated current: 18 mA
Power dissipation/power consumption: ≤ 2 VA / 2 VA
Connection side: field side
Connection: Input I: intrinsically safe: terminals 1+, 3- Input II: non-intrinsically safe: terminals 13+, 14-
Input I: acc. to EN 60947-5-6 (NAMUR)
: Pulse duration: > 50 µs
: Input frequency: 0.001 ... 5000 Hz
: Line fault detection: breakage I ≤ 0.15 mA; short-circuit I > 6.5 mA
Input II: startup override: 1 ... 1000 s, adjustable in steps of 1 s
: Active/Passive: I > 4 mA (for min. 100 ms)/ I < 1 mA
: Open circuit voltage/short-circuit current: 18 V / 5 mA
Connection side: control side
Connection: output I: terminals 10, 11, 12 output II: terminals 16, 17, 18
Output I, II: signal, relay
: Contact loading: 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 V DC / 2 A
: Mechanical life: 5 x 107 switching cycles
: Energized/De-energized delay: approx. 20 ms / approx. 20 ms
Display elements: LEDs , display
Control elements: Control panel
Configuration: via operating buttons
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Low voltage: Directive 2014/35/EU: EN 61010-1:2010
Electromagnetic compatibility: NE 21:2006
Degree of protection: IEC 60529:2001
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Degree of protection: IP20
Connection: screw terminals
Mass: 300 g
Dimensions: 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3
Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001
EU-Type Examination Certificate: TÜV 99 ATEX 1408
Low voltage: Marking: II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
Certificate: TÜV 02 ATEX 1885 X
Low voltage: Marking: II 3G Ex nA nC IIC T4 Gc
Output I, II: Contact loading: 50 V AC/2 A/cos φ > 0.7; 40 V DC/1 A resistive load
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
FM approval: Control drawing: 16-538FM-12
UL approval: E223772
IECEx approval: IECEx TUN 03.0000
FM approval: Approved for: [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I

Parametry logistyczne

ECCN:
Kraj pochodzenia: SG
EAN:
Waga: 0,00 kg
Długość: 0,00 m
Szerokość: 0,00 m
Wysokość: 0,00 m