Opis

The VBA-4E-G11-ZAJ-F is an AS-Interface switch-on module with 4 inputs. 2, 3 and 4 wire sensors can also be connected as mechanical contacts to the 4 sourcing electronic inputs. G11 module. 4 inputsfa. The housing with a central screw enables fast mounting on the base plate. The connection to the sensors is via an M12x1 plug-in connection on the top side of the device. The AS-Interface flat cable and external energy supply are connected via the insulation piercing technology on the underside of the module. The inputs and the connected sensors are powered by the internal supply of the module (from the AS-Interface). The current switching state of each input is indicated via an IN LED. The AS-i/FAULT LED indicates the status of the AS-Interface (normal operation, communication error, peripheral fault, address 0). The switch-on module is compatible with AS-Interface POWER24.

Parametry techniczne

Slave type: A/B slave
AS-Interface specification: V3.0
Required master specification: ≥ V2.1
UL File Number: E223772
MTTFd: 120 a
Mission Time (TM): 20 a
Diagnostic Coverage (DC): 0 %
LED AS-i/FAULT: Status display; multi-colour LED Green: normal operation Red: communication fault Flashing yellow/red: address 0 Flashing green/red: sensor supply overload
LED IN: switching state (input); 4 LED yellow
Rated operating voltage: 18,0 ... 31.6 V from AS-Interface
Rated operating current: ≤ 40 mA (without sensors) / max. 240 mA
Protection class: III
Surge protection: Ue: Over voltage category III, safe isolated power supplies (PELV)
Number/Type: 4 inputs for 2- or 3-wire sensors (PNP), DC option 2 inputs for 4-wire sensors (PNP), DC
Supply: from AS-Interface
Voltage: 12 ... 31 V
Current loading capacity: ≤ 200 mA, overload and short-circuit protected
Input current: ≤ 9 mA (limited internally)
Switching point: according to DIN EN 61131-2 (Type 2)
: 0 (unattenuated): ≤ 3 mA
: 1 (attenuated): ≥ 5 mA
Signal delay: < 1 ms (input/AS-Interface)
Electromagnetic compatibility: Directive 2014/30/EU: EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007
Degree of protection: EN 60529:2000
Fieldbus standard: EN 62026-2:2013
Input: EN 61131-2:2007
Emitted interference: EN 61000-6-4:2007
AS-Interface: EN 62026-2:2013
Noise immunity: EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013
Profile: S-0.A.2
IO code: 0
ID code: A
ID1 code: 7
ID2 code: 2
Data bits (function via AS-Interface): input output
Electromagnetic compatibility: D0: IN1 -
Electromagnetic compatibility: D1: IN2 -
Electromagnetic compatibility: D2: IN3 -
Electromagnetic compatibility: D3: IN4 -
Parameter bits (programmable via AS-i): function
Electromagnetic compatibility: P0: not used
Electromagnetic compatibility: P1: Input filter P1 = 0 input filter on, pulse suppression ≤ 2 ms P1 = 1 input filter off (default settings)
Electromagnetic compatibility: P2: not used
Electromagnetic compatibility: P3: not used
Ambient temperature: -25 ... 70 °C (-13 ... 158 °F)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Relative humidity: 85 % , noncondensing
Climatic conditions: For indoor use only
Altitude: ≤ 2000 m above MSL
Shock and impact resistance: 30 g, 11 ms in 6 spatial directions 3 shocks 10 g, 16 ms in 6 spatial directions 1000 shocks
Vibration resistance: 0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles
Pollution degree: 3
Degree of protection: IP68 / IP69K
Connection: AS-Interface: AS-Interface flat cable Inputs: M12 round connector
Material: Housing: PBT PC
Material: Mounting screw: Stainless steel 1.4305 / AISI 303
Mass: 200 g
Tightening torque, housing screws: 1.8 Nm
Tightening torque, cable gland: 0.4 Nm
Mounting: Mounting plate