214741
KC-LCDC-48-2R-24VDC
Timer, Counter, Tachometer
Counter/Timer/Tachometer, Adding/subtracting via 2 separate inputs, Batch controller with 2 pre-selections, Easy-to-read backlit 2-line LCD display with icons for the displayed preselection and the status of both outputs, Multicolor displayfa
| Pre-selection: | 2-fold |
| Data storage: | > 10 years, EEPROM |
| Programming: | keypad-driven menu |
| MTTFd: | 410 a |
| Mission Time (TM): | 10 a |
| Diagnostic Coverage (DC): | 0 % |
| Type: | 2-line, 2 x 6-digit LC display with leading sign Multicolor, backlit |
| Display value: | digit height 9 mm |
| Pre-selection: | digit height 7 mm |
| Key interlock: | via "high" potential at "LOCK" input |
| Decimal point: | 0 to max 5 fractional digits |
| Scale factor: | 0.0001 ... 99.9999 |
| Reset: | manually or external |
| Fusing: | 10 … 30 V DC: T 0.2 A |
| Operating voltage: | 10 ... 30 V DC |
| Power consumption: | max. 1.5 W |
| Connection: | Counter inputs: A and B Control/reset inputs: LOCK, RESET, GATE, MPI |
| Signal voltage: High: | 0.6 x Ue ... 30 V DC |
| Signal voltage: Low: | 0 ... 0.2 x Ue |
| Counting frequency: | 30 Hz / 55 kHz |
| Minimum pulse duration: | Control/reset inputs: 10 ms / 1 ms |
| Impedance: | 5 kOhm |
| Count modes: Pulse counter: | Counting with counting direction (cnt.dir), difference counting (up.dn), up/down counting (quad), Cumulative counting (up.up), up/down counting x 2 (quad 2), up/down counting x 4 (quad 4), additional functions for counter input A and counter input B: A/B, (A-B)/A x 100% |
| Count modes: Frequency counter: | functions for input A and input B: A, A-B, A+B quad, A/B, (A-B)/A x 100 % |
| Count modes: Timer: | Time measurement via GATE input (FrErun), counter input A: Start, counter input B: Stop (InpA.InpB.), counter input B: Start/Stop (InpB.InpB.), time measuring via RESET input (auto) |
| Relay: | changeover contact , Make contact |
| Count modes: Switching voltage: | max. 250 V AC / 110 V DC |
| Count modes: Switching current: | max. 3 A AC/DC, min. 30 mA DC, |
| Count modes: Switching power: | max. 750 VA / 90 W |
| Sensor supply: | connected power supply is looped through, max. 80 mA |
| Output I: | Relay with make contact, NC or NO progr. |
| Count modes: Mechanical life: | 2 x 107 switching cycles |
| Count modes: Electrical life: | 1 x 105 switching cycles at 3 A |
| Output II: | Relay with changeover contact |
| Count modes: Mechanical life: | 2 x 107 switching cycles |
| Count modes: Electrical life: | 5 x 104 cycles at 3 A |
| Response time: | Relay: approx. 7 ms Frequency counter: 100/600 ms |
| Directive conformity: EMC Directive 2004/108/EC: | EN 61000-6-2:2005 |
| Standard conformity: Emitted interference: | DIN EN 55011:2009, Class B |
| Standard conformity: Mech. capacity: | EN 60068-2-6:2008 10 … 55 Hz / 1 mm / XYZ 30 min in each direction |
| Standard conformity: Shock and impact resistance: | EN 60068-2-27:1995 100 G / 2 ms / XYZ 3 times in each direction |
| Ambient temperature: | -20 ... 65 °C (-4 ... 149 °F) |
| Storage temperature: | -25 ... 75 °C (-13 ... 167 °F) |
| Relative humidity: | ≤ 93 % at 40 °C (noncondensing) |
| Altitude: | 0 ... 2000 m |
| Degree of protection: | IP65 (front) |
| Mass: | approx. 138 g |
| Dimensions: | 48 mm x 48 mm x 109.8 mm |
| ECCN: | |
| Kraj pochodzenia: | DE |
| EAN: | |
| Waga: | 0,00 kg |
| Długość: | 0,00 m |
| Szerokość: | 0,00 m |
| Wysokość: | 0,00 m |