Pepperl+Fuchs 207741

VBG-PB-K30-DMD-S16

AS-Interface Gateway/Safety Monitor

Na prośbę. Prześlij nam wiadomość e-mail z zapytaniem o cenę i dostępność.
"ucnguBrctvdgcxgt0eqo"

Opis

Gateway with integrated Safety Monitorfa. The VBG-PB-K30-DMD-S16* is an IP20-rated PROFIBUS gateway with an integral safety monitor and a double master according to AS-Interface specification 3.0. The VBG-PB-K30-DMD-S16 has four inputs and four outputs. The four inputs are used either for extended EDM device monitoring or as start inputs. Two sets of two outputs act as relay outputs and switch output circuits 1 and 2 and, as semiconductor outputs, output circuits 3 and 4. The K30 model is particularly suitable for installation in a control cabinet. The VBG-PB-K30-DMD-S16* is a combined full-specification AS-Interface PROFIBUS gateway and safety monitor. The product allows a gateway and a safety monitor to be used in a single device. Two safety relays provide a safe interface to the connected consumers. The AS-Interface 3.0 PROFIBUS gateways are used to connect AS-I systems to a higher-level PROFIBUS. They act as a double master for the AS-I segment and as a slave for the PROFIBUS. The AS-I functions are made available on both a cyclic and acyclic basis through PROFIBUS-DP V1. During cyclic data exchange, up to 32 bytes of I/O data (this amount is variable) are transferred as the digital data of an AS-I segment. In addition, analog values as well as the complete command set of the new AS-I specification can be transferred via PROFIBUS using a command interface. Monitoring of the AS-Interface data can be carried out online via PROFIBUS-DP V1 using the serial PROFIBUS master and the AS-I Control Tools. Address assignment, the transfer of the desired configuration and the setting of the Profibus address and baud rate can all be performed using switches. Seven LEDs located on the front panel indicate the current status of the AS-Interface segment. One LED shows the power supply via AUX. A further eight LEDs indicate the status of the inputs and outputs. If the AS-Interface gateway has a graphical display, the commissioning of the AS-Interface circuit and testing of the connected peripherals can take place completely separately from the commissioning of PROFIBUS and the programming. Local operation using the graphical display and the four switches allows all the functions covered on the other AS-Interface masters by AS-i Control Tools software to be visualized on the display. An additional RS-232 socket provides a way of exporting data relating to the gateway, network and operation directly from the gateway for extended local diagnosis purposes.

Parametry techniczne

AS-Interface specification: V3.0
PLC-Functionality: activateable
Duplicate address detection: from AS-Interface slaves
Earth fault detection: integrated
EMC monitoring: integrated
Diagnostics function: Extended function via display
Switch-on delay: < 10 s
Response delay: < 40 ms
UL File Number: E223772 only from low voltage, limited energy source (SELV or PELV) or listed Class 2 source
Safety Integrity Level (SIL): SIL 3
Performance level (PL): PL e
MTTFd: 200 a
B10d: 2 E+7
Display: Illuminated graphical LC display for addressing and error messages
LED PROFIBUS: PROFIBUS master detected; LED green
LED AS-i ACTIVE: AS-Interface operation normal; LED green
LED CONFIG ERR: configuration error; LED red
LED PRG ENABLE: autom. programming; LED green
LED POWER: voltage ON; LED green
LED PRJ MODE: projecting mode active; LED yellow
LED U AS-i: AS-Interface voltage; LED green
LED AUX: ext. auxiliary voltage UAUX ; LED green
LED EDM/Start: External device monitoring circuit inputs closed, 4x yellow LEDs
LED output circuit: Output circuit closed; 4 x green LEDs
Button: 4
Insulation voltage: ≥ 500 V
Rated operating voltage: 26.5 ... 31.6 V from AS-Interface; Output K3 and K4 24 V DC
Rated operating current: ≤ 300 mA off AS interface network 1 ≤ 70 mA off AS interface network 2
Interface type: RS-485
Protocol: PROFIBUS DP V1
Transfer rate: 9.6 kBit/s / 12 MBit/s , Automatic baud rate detection
Interface type: RS 232, serial Diagnostic Interface
Transfer rate: 19,2 kBit/s
Interface type: Chip card slot
Number/Type: 4 EDM/Start inputs: EDM: Inputs for the external device monitoring circuits Start: start inputs: Static switching current 4 mA at 24 V, dynamic 30 mA at 24 V (T=100 μs)
Safety output: Output circuits 1 and 2: 2 potential-free contacts, max. contact load: 3  ADC-13 at 30 VDC, 3 AAC-15 at 30 VAC Output circuits 3 and 4: 2 PNP transistor outputs max. contact load: 0.5  ADC-13 at 30  VDC
PROFIBUS: Sub-D interface
AS-Interface: spring terminals, removable
Electromagnetic compatibility: Directive 2014/30/EU: EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007
Electromagnetic compatibility: EN 61000-6-2:2005, EN 61000-6-4:2007
Degree of protection: EN 60529:2000
Fieldbus standard: PROFIBUS according to DIN 19245 Part 3
AS-Interface: EN 62026-2:2013
Standards: EN 61000-6-2:2005, EN 61000-6-4:2007 EN 954-1:1996 (up to Kategorie 4), IEC 61508:2001 and EN 62061:2005 (up to SIL3) EN 13849:2008 (PL e)
UL approval: An isolated source with a secondary open circuit voltage of ≤ 30 VDC with a 3 A maximum over current protection. Over current protection is not required when a Class 2 source is employed. UL mark does not provide UL certification for any functional safety rating or aspects of the device.
Ambient temperature: 0 ... 55 °C (32 ... 131 °F)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Degree of protection: IP20
Mass: 800 g
Construction type: Low profile housing , Stainless steel

Parametry logistyczne

ECCN:
Kraj pochodzenia: Deutschland
EAN: 4050143025510
Waga: 0,94 kg
Długość: 0,00 m
Szerokość: 0,00 m
Wysokość: 0,00 m